2006-08-05 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| A. OK |
| 1. OK |
| 2. OK |
| |
| 3. SHT A-7 DETAIL "A" SHOW THE FLUSH |
| CONTROLS. 11-4.16.5 FOR THE W/C AND |
| FAUCET TYPE 11-4.19.5 FOR THE LAV. |
| ****RESPONSE NOTED, BUT PER 11-4.16.5 |
| THE FLUSH CONTROLS SHALL BE ON THE WIDE |
| SIDE OF THE W/C. |
| |
| 4. SHT P-1 PLUMBING RISER FOR BUILDING 1 |
| DOES NOT REFLECT THE FLOOR PLAN. |
| BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT |
| RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS |
| 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE |
| OPPOSITE SIDE OF THE TOILET ROOM THAN |
| THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW |
| THE LAV STACKS VENTING THE W/C'S. - L/T |
| SHALL NOT DRAIN THROUGH THE WET VENT OF |
| THE BATHROOM FIXTURES, BUT SHALL CONNECT DOWNSTREAM OF |
| THE BATHROOM GROUP. |
| SECTION 909.1. (SEE RED LINE EXAMPLE ONE |
| SET OF PLANS). |
| ****RESPONSE NOTED, BUT BAYS 9, 10, 13, |
| 17, 20 DO NOT REFLECT THE FLOOR PLANS. |
| THE FIXTURES ARE TURNED TO THE WRONG |
| SIDE OF THE VENT PIPING. SEE FLOOR PLAN. |
| - SHOW ALL PIPE SIZES. |
| |
| 5. SHT P-1 PLUMBING RISER DIAGRAM FOR |
| BUILDING 2 DOES NOT REFLECT THE FLOOR |
| PLAN. (SEE PREVIOUS COMMENT AND ADJUST |
| RISER TO FLOOR PLAN AND PIPE PER CODE. |
| SECTIONS 106.1.1 & 909.1. |
| ****RESPONSE NOTED, BUT SHOW ALL PIPE |
| SIZES. |
| |
| 6. SHT P-1 PLUMBING RISER DIAGRAM FOR |
| BUILDING 3 DOES NOT REFLECT THE FLOOR |
| PLAN. (SEE COMMENT #4 AND ADJUST RISER |
| TO REFLECT THE FLOOR PLAN, AND PIPE PER |
| CODE. SECTIONS 106.1.1 & 909.1. |
| ****RESPONSE NOTED, BUT SHOW ALL PIPE |
| SIZES. |
| |
| 7. SHT P-1 TYPICAL COLD RISER DOES NOT |
| REFLECT THE FLOOR PLANS. SUBMIT A WATER |
| RISER DIAGRAM FOR EACH BUILDING THAT |
| REFLECT THE FLOOR PLAN OF THAT BUILDING. |
| SHOW ALL PIPE SIZES, VALVES, INDICATE |
| BAY NUMBER, INDICATE PIPING MATERIAL. |
| INDICATE IF WATER IS UNDERGROUND OR |
| ABOVE GROUND. - AN RPZV BACKFLOW IS |
| REQUIRED FOR EACH BUILDING. SECTIONS |
| 106.1.1, 606.1, 606.2, 608.13.2. |
| ****RESPONSE NOTED, BUT THE WATER RISER |
| DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| THE FIXTURES ARE LOCATED EAST TO WEST IN |
| THE TOILET ROOM AND THE FIXTURE LAYOUT |
| ON THE RISER IS FROM SOUTH TO NORTH. |
| WATER SERVICE IS NOT AS SHOWN ON THE C-1 |
| SHEET. SEPARATE BACKFLOW REQUIRED FOR |
| EACH BUILDING. SHOW ALL PIPE SIZES. |
| INDICATE PIPING MATERIAL. |
| |
| 8. OK |
| **************NEW COMMENTS************** |
| |
| 1B. DRINKING FOUNTAINS ARE REQUIRED. |
| WATER BOTTLES NOT APPROVED FOR OVER 50% |
| OF THE FIXTURES REQUIRED. TABLE 403.1. |
| |
| 2B. SUBMIT A DETAIL SHOWING COMPLIANCE |
| WITH SECTION 11-4.15 AND ALL SUBSECTIONS |
| INCLUDING 11-4.1.3(10)(A) PROVISIONS FOR |
| THOSE WHO HAVE DIFFICULTY BENDING OR |
| STOOPING. |
| |
| 3B. SHT A-4 TYPICAL GUTTER DRAIN DETAIL. |
| INDICATE WIDTH OF OPENING TO DETERMINE |
| THE OPENING SIZE TO COMPLY WITH TABLE |
| 1106.3. |
| |