Plan Review Notes
Plan Review Notes For Permit 05091674
Permit Number 05091674
Review Stop P
Sequence Number 2
Notes
Date Text
2006-08-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 A. OK
 1. OK
 2. OK
  
 3. SHT A-7 DETAIL "A" SHOW THE FLUSH
 CONTROLS. 11-4.16.5 FOR THE W/C AND
 FAUCET TYPE 11-4.19.5 FOR THE LAV.
 ****RESPONSE NOTED, BUT PER 11-4.16.5
 THE FLUSH CONTROLS SHALL BE ON THE WIDE
 SIDE OF THE W/C.
  
 4. SHT P-1 PLUMBING RISER FOR BUILDING 1
 DOES NOT REFLECT THE FLOOR PLAN.
 BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT
 RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS
 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE
 OPPOSITE SIDE OF THE TOILET ROOM THAN
 THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW
 THE LAV STACKS VENTING THE W/C'S. - L/T
 SHALL NOT DRAIN THROUGH THE WET VENT OF
 THE BATHROOM FIXTURES, BUT SHALL CONNECT DOWNSTREAM OF
 THE BATHROOM GROUP.
 SECTION 909.1. (SEE RED LINE EXAMPLE ONE
 SET OF PLANS).
 ****RESPONSE NOTED, BUT BAYS 9, 10, 13,
 17, 20 DO NOT REFLECT THE FLOOR PLANS.
 THE FIXTURES ARE TURNED TO THE WRONG
 SIDE OF THE VENT PIPING. SEE FLOOR PLAN.
 - SHOW ALL PIPE SIZES.
  
 5. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 2 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE PREVIOUS COMMENT AND ADJUST
 RISER TO FLOOR PLAN AND PIPE PER CODE.
 SECTIONS 106.1.1 & 909.1.
 ****RESPONSE NOTED, BUT SHOW ALL PIPE
 SIZES.
  
 6. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 3 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE COMMENT #4 AND ADJUST RISER
 TO REFLECT THE FLOOR PLAN, AND PIPE PER
 CODE. SECTIONS 106.1.1 & 909.1.
 ****RESPONSE NOTED, BUT SHOW ALL PIPE
 SIZES.
  
 7. SHT P-1 TYPICAL COLD RISER DOES NOT
 REFLECT THE FLOOR PLANS. SUBMIT A WATER
 RISER DIAGRAM FOR EACH BUILDING THAT
 REFLECT THE FLOOR PLAN OF THAT BUILDING.
 SHOW ALL PIPE SIZES, VALVES, INDICATE
 BAY NUMBER, INDICATE PIPING MATERIAL.
 INDICATE IF WATER IS UNDERGROUND OR
 ABOVE GROUND. - AN RPZV BACKFLOW IS
 REQUIRED FOR EACH BUILDING. SECTIONS
 106.1.1, 606.1, 606.2, 608.13.2.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE FIXTURES ARE LOCATED EAST TO WEST IN
 THE TOILET ROOM AND THE FIXTURE LAYOUT
 ON THE RISER IS FROM SOUTH TO NORTH.
 WATER SERVICE IS NOT AS SHOWN ON THE C-1
 SHEET. SEPARATE BACKFLOW REQUIRED FOR
 EACH BUILDING. SHOW ALL PIPE SIZES.
 INDICATE PIPING MATERIAL.
  
 8. OK
 **************NEW COMMENTS**************
  
 1B. DRINKING FOUNTAINS ARE REQUIRED.
 WATER BOTTLES NOT APPROVED FOR OVER 50%
 OF THE FIXTURES REQUIRED. TABLE 403.1.
  
 2B. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 INCLUDING 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 3B. SHT A-4 TYPICAL GUTTER DRAIN DETAIL.
 INDICATE WIDTH OF OPENING TO DETERMINE
 THE OPENING SIZE TO COMPLY WITH TABLE
 1106.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]