2006-08-04 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| FROM PREVIOUS LIST: |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED.THE NOC PROVIDED |
| IS EXPIRED; OVER 90 DAYS WITHOUT |
| COMMENCING WORK, FS713.13(2). |
| |
| 2.)SEPARATE PERMITS FOR EACH BUILDING |
| AND THE DUMPSTER WILL BE REQUIRED FOR |
| INSPECTION PURPOSES.SEPARATE PLANS ARE |
| NOT REQUIRED. |
| |
| 3.)ADDRESSED. |
| |
| 4.)FBC* 105.3RESIDENT INSPECTOR. |
| SUBMIT INSPECTOR RESUME' AND LICENSE |
| DOCUMENTS TO HAROLD PISKURA, 805-6711. |
| ARESIDENT INSPECTOR PROGRAM IS |
| REQUIRED, ON THIS PROJECT, DUE TO ONE OR |
| MORE OF THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE |
| DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - PILE DRIVING |
| - BUILDINGS OVER 20,000 SQ FT IN AREA |
| - BUILDINGS OVER 2 STORIES IN HEIGHT |
| - BUILDING/STRUCTURES OF UNUSUAL DESIGN |
| OR METHODS OF CONSTRUCTION |
| |
| 5.)ADDRESSED. |
| |
| 6.)PRODUCT APPROVALS ARE TO BE |
| REVIEWED BY DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR PERMITTING, FBC*106.3.3. |
| |
| NEW COMMENT: FIRST REVIEW WAS IN |
| JANUARY. IN FEBRUARY THE STATE OF |
| FLORIDA INFORMED ME THAT THE 2001 |
| FLORIDA STATE PRODUCT APPROVALS WERE NO |
| LONGER GRANDFATHERED IN. PLEASE PRINT |
| THE 2004 FLORIDA STATE PRODUCT |
| APPROVALS. |
| |
| 7.-15.)ADDRESSED. |
| |
| 16.)FOR THE ROOF, INDICATE WHICH |
| APPROVED ASSEMBLY YOU ARE USING IN THE |
| PRODUCT APPROVAL. |
| |
| 2ND REVIEW - YOU HAVE HIGHLIGHTED ONE OF |
| THE COMPONENTS.PLEASE CHOOSE AN |
| APPROVED ASSEMBLY, BETWEEN PAGES 9-16. |
| |
| NEW COMMENT: |
| |
| 17.)YOU HAVE DECLARED A TYPE VA IN |
| RESPONSE TO ANOTHER COMMENT.THIS |
| REQUIRES 1 HOUR FOR STRUCTURAL ELEMENTS |
| LISTED IN FBC TABLE 601.PROVIDE |
| CALCULATED FIRE RESISTANCE OR APPROVED |
| ASSEMBLY, DETAILS, AND NOTE ON THE PLAN. |