2006-01-18 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 A. PLANS TO BE DESIGNED & REVIEWED PER
 THE FBC-2004 EDITION. PLEASE INDICATE ON
 PLANS.
 1. SHTS S-7, S-8, S-9 ROOF CALCULATIONS
 ARE NOT CLEAR AND CAN NOT BE VERIFIED.
 INDICAE THE SQUARE FEET OF EACH BAY ROOF
 AREA, SHOW 1/2 AREA OF THE VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO EACH
 AREA. THE ROOF INDICATES SLOPE ON SOME
 BAYS, BUT NOT ALL. INDICATE SLOPE OF
 EACH BAY. SOME BAYS SHOW DRAINS ON
 EITHER SIDE OF THE BUILDING SO PLEASE
 INDICATE IF THE ROOF SLOPES TO EITHER
 SIDE OF THE BUILDING. IF SO PLEASE SHOW
 THE HIGH SPOT OF THE ROOF AND INDICATE
 THE SQUARE FOOTAGE DRAINING TO EACH
 DRAIN. NOTE INDICATES GUTTERS, BUT
 GUTTERS ARE NOT SHOWN ON THE ROOF PLANS
 NOR ARE THEY SHOWN ON THE BUILDING
 ELEVATIONS. CALCULATIONS INDICATE 6"
 GUTTERS & 7" DOWNSPOUTS, BUT ROOF PLAN
 SHOWS NO GUTTERS AND 5" CAST IRON
 DOWNSPOUTS AND ALSO 5" PVC DOWNSPOUTS.
 PLEASE CLARIFY. - GUTTER SIZING
 CALCULATIONS ONLY POINT TO BAYS 5, 14,
 20 & 28. WHAT ARE THE CALCULATIONS FOR
 THE OTHER BAYS? PLEASE CLARIFY. NO BAYS
 SHOWN FOR BUILDING 3. - NO SECONDARY
 ROOF DRAINS OR SCUPPERS ARE SHOWN.
 PLEASE CLARIFY. SECTIONS 106.1.1, 1106 &
 1107.
 2. SHTS A-4, A-5, & A-6, INDICATE THE
 ELEVATION OF THE ROOF LEVEL. THE TOP OF
 THE PARAPET FOR EAST ELEVATIONS
 BUILDINGS 1 & 2 AND WEST ELEVATION DOES
 NOT INDICATE THE HEIGHT OF THE HIGH
 PARAPET SECTIONS.- NO GUTTERS SHOWN.
 SECTION 106.1.1.
 3. SHT A-7 DETAIL "A" SHOW THE FLUSH
 CONTROLS. 11-4.16.5 FOR THE W/C AND
 FAUCET TYPE 11-4.19.5 FOR THE LAV.
 4. SHT P-1 PLUMBING RISER FOR BUILDING 1
 DOES NOT REFLECT THE FLOOR PLAN.
 BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT
 RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS
 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE
 OPPOSITE SIDE OF THE TOILET ROOM THAN
 THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW
 THE LAV STACKS VENTING THE W/C'S. - L/T
 SHALL NOT DRAIN THROUGH THE WET VENT OF
 THE BATHROOM FIXTURES, BUT SHALL CONNECT
 DOWNSTREAM OF THE BATHROOM GROUP.
 SECTION 909.1. (SEE RED LINE EXAMPLE ONE
 SET OF PLANS).
 5. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 2 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE PREVIOUS COMMENT AND ADJUST
 RISER TO FLOOR PLAN AND PIPE PER CODE.
 SECTIONS 106.1.1 & 909.1.
 6. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 3 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE COMMENT #4 AND ADJUST RISER
 TO REFLECT THE FLOOR PLAN, AND PIPE PER
 CODE. SECTIONS 106.1.1 & 909.1.
 7. SHT P-1 TYPICAL COLD RISER DOES NOT
 REFLECT THE FLOOR PLANS. SUBMIT A WATER
 RISER DIAGRAM FOR EACH BUILDING THAT
 REFLECT THE FLOOR PLAN OF THAT BUILDING.
 SHOW ALL PIPE SIZES, VALVES, INDICATE
 BAY NUMBER, INDICATE PIPING MATERIAL.
 INDICATE IF WATER IS UNDERGROUND OR
 ABOVE GROUND. - AN RPZV BACKFLOW IS
 REQUIRED FOR EACH BUILDING. SECTIONS
 106.1.1, 606.1, 606.2, 608.13.2.
 8. SUBMIT A HORIZONTAL PIPING LAYOUT
 FLOOR PLAN SHEET FOR EACH BUILDING
 SHOWING ALL PIPE SIZES. SECTION
 106.3.5.1.3(3)(4)(8)(9)(10) - SHOW WHERE
 THE SANT., STORM EXIT THE BUILDING AND
 WHERE THE WATER ENTERS THE BUILDING. -
 SUBMIT A STORM BUILDING DRAIN ISOMETRIC
 AND STORM RISER DIAGRAM. SHOW ALL PIPE
 SIZES, OFFSETS SQUARE FOOTAGE OF EACH
 RISER AND SHOW SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. INDICATE THE
 TERMINATION POINT OF STORM SYSTEM.
 SECTION 106.3.5.1.3.
  