Plan Review Notes
Plan Review Notes For Permit 05091674
Permit Number 05091674
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-11-17 00:00:00******DENIED******
  
 1) SHTS A-1, A-2 AND A-3 INDICATE
 INCORRECT CODE REFERENCE. NFPA 101, 2003
 EDITION SHALL BE REFERENCED.
  
 2) ADDRESS NUMBERS ARE REQUIRED ON THE
 BUILDINGS, TO BE A MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING WITH THE
 BACKGROUND.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND MOUNTED AT DISTANCES TO
 SATISFY THE 75' TRAVEL REQUIREMENT.
  
 4) PLEASE ILLUSTRATE ALL EXISTING WATER
 SUPPLIES PERTINENT TO THIS PROPERTY.
  
 5) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241 AND
 OTHER APPLICABLE CODES.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722