Plan Review Notes
Plan Review Notes For Permit 05091661
Permit Number 05091661
Review Stop B
Sequence Number 3
Notes
Date Text
2005-12-19 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- A)ENGINEER'S WIND LOAD SCHEDULE IS
 FOR 130 MPH BASIC WIND SPEED. NEED WIND
 LOAD SCHEDULE FOR 140 MPH, WHICH IS THE
 APPROPRIATE WIND LOAD FOR THE CITY OF
 WEST PALM.
  
 B)NEED 2 ORIGINAL SIGNED AND SEALED WIND
 LOAD SCHEDULES. ONLY ONE WAS PROVIDED.
 COPIES ARE NOT ACCEPTABLE. CHAPTER 471
 FLORIDA STATUTES
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712