2005-11-28 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- A) WIND LOAD CHART NEEDS TO BE SIGNED |
| AND SEALED BY THE ENGINEER OR ARCHITECT |
| WHO MADE THE CALCULATIONS USING ASCE |
| 7-98. SECTION 104.2.1.2 CITY AMENDMENTS |
| TO FBC 2001. |
| B) CLARIFY NOTE: "IF ANY TYPE |
| BUILDING EXCEEDS 60' IN HEIGHT, ALL |
| VALUES ARE THE SAME". ARE THE DESIGN |
| PRESSURES THE SAME IF THE BUILDING IS |
| TALLER THAN 60'? WHY?. |
| |
| 3- A) PROVIDE KEY PLAN TO DETERMINE |
| LOCATION OF OPENING (END OR INTERIOR |
| ZONE FOR THE DESIGN PRESSURES) AND |
| COMPLETE INSTALLATION SCHEDULE. SEE |
| ATTACHED SAMPLE. |
| B) CLEARLY MARK ON SHUTTER DRAWINGS |
| SPECIFIC ANCHOR TYPE AND SPACING TO BE |
| USED ACCORDING THE THE DESIGN PRESSURES, |
| SHUTTER SPAN, EDGE DISTANCE, CONNECTION |
| TYPE, GLASS DISTANCE, AND STRUCTURE TO |
| BE ATTACHED TO (CONCRETE, CONCRETE BLOCK |
| OR WOOD). |
| |
| 4- ACCORDION SHUTTERS DRAWINGS ARE NOT |
| LEGIBLE. PROVIDE LEGIBLE DRAWINGS. |
| |
| 5- CLEARLY IDENTIFY MULLION SIZE AND |
| ANCHORS TO BE USED TO VERIFY COMPLIANCE |
| WITH THE DESIGN PRESSURES. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |