Plan Review Notes
Plan Review Notes For Permit 05091661
Permit Number 05091661
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-28 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- A) WIND LOAD CHART NEEDS TO BE SIGNED
 AND SEALED BY THE ENGINEER OR ARCHITECT
 WHO MADE THE CALCULATIONS USING ASCE
 7-98. SECTION 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 B) CLARIFY NOTE: "IF ANY TYPE
 BUILDING EXCEEDS 60' IN HEIGHT, ALL
 VALUES ARE THE SAME". ARE THE DESIGN
 PRESSURES THE SAME IF THE BUILDING IS
 TALLER THAN 60'? WHY?.
  
 3- A) PROVIDE KEY PLAN TO DETERMINE
 LOCATION OF OPENING (END OR INTERIOR
 ZONE FOR THE DESIGN PRESSURES) AND
 COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE.
 B) CLEARLY MARK ON SHUTTER DRAWINGS
 SPECIFIC ANCHOR TYPE AND SPACING TO BE
 USED ACCORDING THE THE DESIGN PRESSURES,
 SHUTTER SPAN, EDGE DISTANCE, CONNECTION
 TYPE, GLASS DISTANCE, AND STRUCTURE TO
 BE ATTACHED TO (CONCRETE, CONCRETE BLOCK
 OR WOOD).
  
 4- ACCORDION SHUTTERS DRAWINGS ARE NOT
 LEGIBLE. PROVIDE LEGIBLE DRAWINGS.
  
 5- CLEARLY IDENTIFY MULLION SIZE AND
 ANCHORS TO BE USED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712