2006-06-06 00:00:00 | PROVISO:2001 FBC/BUIDLING 7/5 UNITS |
| |
| PLEASE REVISE THE PLANS TO REFLECT THE |
| IMPLEMENTATION OF THE PROVISO'S. |
| |
| 1.PLAN SHEET M0.1, DETAIL ON THE AHU |
| MOUNTING NOTE #15 STATES "NO |
| COMBUSTIBLES ALLOWED IN THE MECHANICAL |
| CLOSET" AS IT SERVES AS A PLENUM.THE |
| DOOR SCHEDULE ON PLAN SHEET A-4.7.3 |
| INDICATES THE AHU CLOSET DOOR AS A WOOD |
| LOUVERED DOOR.PLEASE CLARIFYNWITH THE |
| DOOR MANUFACTURE THAT THIS DOOR MEETS |
| THE 25 FLAME/50 SMOKE INDEX AS SPECIFIED |
| IN 2001 FMC 602.2.1. |
| |
| 2.O.A. CALCULATIONS INDICATED ON PLAN |
| SHEET M0.1 ARE BASED ON INFILTRATION |
| RATES.THE INFILTRATION RATES ARE THE |
| MAXIMUM ALLOWED BY CODE AND MAY NOT |
| REFLECT A "TRUE" RATE.PLEASE PROVIDE |
| CALCS IN ACCORDANCE WTIH 2001 FMC 402.2, |
| 402.2.1 OR TABLE 403.3.PLEASE NOTE, |
| PLAN SHEET M2 INDICATES A 6" O.A. DUCT. |
| PLEASE DELETE FROM THE PLAN IF THIS IS |
| NOT GOING TO BE INSTALLED. |
| |
| 3.SPECIFICDRYERS AS TO BE INSTALLED |
| BY FINAL INSPECTION. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561)805-6719. |