2006-05-15 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE BUILDING IS SHOWN AS
 A FIVE UNTI BUIDING, HOWEVER SERVICE AS
 SHOWN IS FOR FOUR UNITS ONLY.?
 PLEASE CORRELATE SIZE OF SERVICE.215.5
  
 2)NOTE: PLEASESEE #4 GEC SHOWN, WHERE
 A 3/0 MIN IS REQUIRED PER 250.66 FOR THE
 SEC'S SHOWN.
  
 ** PLEASE SEE ALL OTHER ELECTRICAL
 SHEETS ARE STAMPED IN BOTH SETS. BOTH
 SETS WITH THESE STAMPED SHEETS MUST BE
 RETURNED IN SETS WHEN RESUBMITTING
 PALNS.