Plan Review Notes For Permit 05091653 |
Permit Number |
05091653 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-15 00:00:00 | **** UNSAT **** | | | | 1) NOTE: PLEASE SEE BUILDING IS SHOWN AS | | A FIVE UNTI BUIDING, HOWEVER SERVICE AS | | SHOWN IS FOR FOUR UNITS ONLY.? | | PLEASE CORRELATE SIZE OF SERVICE.215.5 | | | | 2)NOTE: PLEASESEE #4 GEC SHOWN, WHERE | | A 3/0 MIN IS REQUIRED PER 250.66 FOR THE | | SEC'S SHOWN. | | | | ** PLEASE SEE ALL OTHER ELECTRICAL | | SHEETS ARE STAMPED IN BOTH SETS. BOTH | | SETS WITH THESE STAMPED SHEETS MUST BE | | RETURNED IN SETS WHEN RESUBMITTING | | PALNS. | | PLEASE SEE SHEET 6.1 WAS VOIDEDIN BOTH | | SETS AS THIS WAS STAMPED IN ERROR. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|