Date Text
2005-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHTS P2.1.1, P2.2.2,P-2.3.1,
 P3.1.1, P-3.2, & P3.3.2 WATER HAMMER
 ARRESTORS ARE REQUIRED AT THE WASH
 MACHINES OF ALL UNITS. PER SECTION
 604.9. - ALL WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN IN SOME CASES. PDI-WH 201 AND
 MANUF INSTALLATION INSTRUCTIONS.
 2. IF INDIVIDUAL METERS NO BACKFLOW
 DEVISE IS REQUIRED, BUT IF SINGLE METER
 AN RPZV BACKFLOW WILL BE REQUIRED ON THE
 WATER SERVICE. PLEASE CLARIFY. SECTION
 608.13.2.
  