2005-11-29 00:00:00 | DENIED:BUILDING 7 / 2001 FBC |
| 1.PLAN SHEET A-0.0.0 PROJECT |
| INFORMATION INDICATES TYPE VI, |
| UNPROTECTED SPRINKLERED.PLEASE |
| INDICATE WHICH SYSTEM WILL BE USED |
| (13,13R, 13D ETC).PLEASE NOTE, |
| ADDITIONAL COMMENTS MAY BE GENERATED BY |
| THE RESPONSE GIVEN. |
| |
| 2.PLAN SHEET A-4.6.2 KEY NOTES/LEGEND, |
| ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| PLAN SHEET A-13 WAS NOT SUBMITTED FOR |
| REVIEW. |
| |
| 3.PLAN SHEET M0.1 EQUIPMENT SCHEDULE |
| INDICATES AHU-1 AS A 5 TON UNIT.NOTE |
| #2 INDICATES AREA SMOKE DETECTORS TO |
| SHUT DOWN AHU.PLEASE INDICATE THIS ON |
| THE ELECTRICAL PLANS FOR UNITS 97D & |
| 93D. |
| |
| 4.PLEASE CLARIFY RATING OF THE WALL |
| BETWEEN THE GARAGE & THE RESIDENCE.THE |
| ARCHITECTURAL PLANS ARE NOT CLEAR AS TO |
| WHERE THE 1HR RATING ENDS (AT THE SLAB |
| OR AT THE RATED CEILING). |
| |
| 5.PLAN SHEET M1 R/A JUMPER FROM THE |
| GUEST SUITE IN UNITS 97D & 93D IS NOT |
| SIZE IN ACCORDANCE WITH 2001 FMC 601.4 |
| EXCEPTION 1 & 3. R/A JUMPER FROM THE |
| GUEST SUITE SHALL BE A MINIMUM OF 12". |
| |
| 6.PLAN SHEET M3 R/A TRANSFER GRILLES |
| ARE NOT SIZED PROPERLY.SHOW COMPLIANCE |
| WITH 2001 FMC 601.4 EXCEPTION 2 & 3. |
| |
| 7.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH 2001 FMC |
| TABLE 403.3. |
| |
| 8.PLAN SHEET M3, THE DRYER EXHAUST |
| EXCEEDS THE REQUIRED 25FT MAXIMUM |
| DISTANCE PER 2001 FMC 504.6. |
| |
| 9.PLEASE PROVIDE A DETAIL FOR THE AHU |
| LOCATED IN THE 2ND FLOOR CLOSET.SHOW |
| COMPLIANCE WITH 2001 FMC 603.9 & |
| 610.1.ABC.3.7 OF THE 2001 FBC. |
| |