2005-11-29 00:00:00DENIED:BUILDING 7 / 2001 FBC
 1.PLAN SHEET A-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED SPRINKLERED.PLEASE
 INDICATE WHICH SYSTEM WILL BE USED
 (13,13R, 13D ETC).PLEASE NOTE,
 ADDITIONAL COMMENTS MAY BE GENERATED BY
 THE RESPONSE GIVEN.
  
 2.PLAN SHEET A-4.6.2 KEY NOTES/LEGEND,
 ITEM #25 '1HR CHASE REFER TO 11/A-13'.
 PLAN SHEET A-13 WAS NOT SUBMITTED FOR
 REVIEW.
  
 3.PLAN SHEET M0.1 EQUIPMENT SCHEDULE
 INDICATES AHU-1 AS A 5 TON UNIT.NOTE
 #2 INDICATES AREA SMOKE DETECTORS TO
 SHUT DOWN AHU.PLEASE INDICATE THIS ON
 THE ELECTRICAL PLANS FOR UNITS 97D &
 93D.
  
 4.PLEASE CLARIFY RATING OF THE WALL
 BETWEEN THE GARAGE & THE RESIDENCE.THE
 ARCHITECTURAL PLANS ARE NOT CLEAR AS TO
 WHERE THE 1HR RATING ENDS (AT THE SLAB
 OR AT THE RATED CEILING).
  
 5.PLAN SHEET M1 R/A JUMPER FROM THE
 GUEST SUITE IN UNITS 97D & 93D IS NOT
 SIZE IN ACCORDANCE WITH 2001 FMC 601.4
 EXCEPTION 1 & 3. R/A JUMPER FROM THE
 GUEST SUITE SHALL BE A MINIMUM OF 12".
  
 6.PLAN SHEET M3 R/A TRANSFER GRILLES
 ARE NOT SIZED PROPERLY.SHOW COMPLIANCE
 WITH 2001 FMC 601.4 EXCEPTION 2 & 3.
  
 7.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001 FMC
 TABLE 403.3.
  
 8.PLAN SHEET M3, THE DRYER EXHAUST
 EXCEEDS THE REQUIRED 25FT MAXIMUM
 DISTANCE PER 2001 FMC 504.6.
  
 9.PLEASE PROVIDE A DETAIL FOR THE AHU
 LOCATED IN THE 2ND FLOOR CLOSET.SHOW
 COMPLIANCE WITH 2001 FMC 603.9 &
 610.1.ABC.3.7 OF THE 2001 FBC.
  