2006-05-26 00:00:00PROVISO:2001 FBC/BUILDING 19/4 UNITS
 RESPONSETO REVIEW COMMETNS OF 11/28/05
  
 PLEASE REVISE PLANS TO REFLECT THE
 IMPLEMENTATION OF THE PROVISO'S.
  
 COMMENT #6:SPECIFIC DRYER TO BE
 INSTALLED WHICH WILL ELIMINATE THE NEED
 OF THE BOOSTER FAN.PLEASE NOTE,
 SPECIFIC DRYER IS TO BE INSTALLED FOR
 FINAL INSPECTION 2001 FMC 504.6.
  
 COMMENT #7:PLAN SHEET M0.1 THE OUTSIDE
 AIR CALCULATIONS ARE BASED ON
 "INFILTRATION RATES".THE INFILTRATION
 RATES ARE "MAXIMUM RATES" ALLOWED BY
 CODE AND MAY NOT ACTUALLY EXIST.THE
 "ACTUAL" RATE IS NOT KNOWN UNLESS
 TESTED.OUTSIDE AIR CALCULATIONS ARE TO
 BE PER 2001 FMC 402.2, 402.2.1 OR TABLE
 403.3.PLEASE PROVIDE CALCULATIONS.
 PLEASE NOTE, PLAN SHEET M2 INDICATES 6"
 OUTSIDE AIR DUCT, PLEASE REMOVE FROM THE
 PLANS IF THIS DUCT IS NOT GOING TO BE
 INSTALLED.
  
 COMMENT #8:AHU CLOSET IS USED AS A
 RETURN AIR PLENUM.PLAN SHEET M0.1 AHU
 DETAIL 15 ANNOTATES "NO COMBUSTIBLES
 ALLOWED IN THE RETURN AIR PLENUM".
 HOWEVER, PLAN SHEETS A-4.0.2 THROUGH
 A-4.5.3, THE DOOR SCHEDULE INDICATES THE
 AHU CLOSET DOOR WILL BE A WOOD LOUVERED
 DOOR.PLEASE NOTE, THE DOOR AND FRAME
 ARE REQUIRED TO MEET THE 25 FLAME/50
 SMOKE INDEX WHEN TESTED UNDER ASTM 84.
 PLEASE VERIFY THE DOOR & FRAME MEET THIS
 REQUIREMENT PER 2001 FMC 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.