Plan Review Notes
Plan Review Notes For Permit 05091652
Permit Number 05091652
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-15 00:00:00***** UNSAT*******
  
 1) NOTE: PLEASE SEE PLANS ARE FOR A FOUR
 UNIT BUILDING, HOWEVER THE ELECTRICAL
 SERVICE SUBMITTED IS FOR A 6 UNIT
 BUILDING.
 PLEASE CORRELATE. PLEASE ALSO SHOW THE
 "SITE KEY PLAN" FOR LOCATION OF SERVICE
 AS SHOWN ON OTHER PLANS.
  
 2) NOTE:PLEASE SEE NO, SERVICE
 ENTRANCE CONDUIT OR SERVICE ENTRANCE
 CONDUCTORS ARE SHOWN ON RISER FROM FPL
 TO 1000A SERVICE MAIN.
 PLEASE SEE SEC'S ARE NOTED IN FAULT
 CURRENT CALCS ONLY.
 215.5
  
 3) NOTE: PLEASE SEE #4 GEC SHOWN, WHERE
 A 3/0 MIN IS REQUIRED PER 250.66 BASED
 ON THE SEC'S SHOWN ON THE ELECTRICAL
 RISER IN FAULT CURRENT CALCS.
  
 4) NOTE: PLEASE SEE 424.3B FOR MIN OCP
 SHALL BE 125% FOR AHU'S. PLEASE SEE OCP
 HAS NOW BEEN DECREASED TO 40A'S???
  
 ** PLEASE SEE SHEET 6.1 HAS BEEN VOIDED
 AS THIS WAS STAMPED IN ERROR. PLEASE
 KNOW, ALL OTHER ELETRICAL SHEETS WERE
 STAMPED AND THOSE SHEETS MUST BE LEFT IN
 THE COMPLETED ROLL S TO AVOID A FULL
 REVIEW OF ALL SHEETS WHEN RESUBMITTING
 PLANS.
 ONLY SHEET 6.1, SHOULD BE CHANGED OUT.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]