Date |
Text |
2005-11-28 00:00:00 | DENIED:BUILDING 19 / 2001 FBC |
| 1.PLAN SHEET A-0.0.0 PROJECT |
| INFORMATION INDICATES TYPE VI, |
| UNPROTECTED SPRINKLERED.PLEASE |
| INDICATE WHICH SYSTEM WILL BE UTILIZED |
| (13, 13R, 13D ETC).PLEASE NOTE |
| ADDTIONAL COMMENTS MAY BE GENERATED BY |
| THE RESPONSE GIVEN. |
| |
| 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND, |
| ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| PLAN SHEET A-13 WAS NOT SUBMITTED FOR |
| REVIEW. |
| |
| 3.PLAN SHEET M-1 INDICATES 8" SUPPLY |
| DUCT & 3" EXHAUST PENETRATING THE RATED |
| WALL BETWEEN THE GARAGE AND THE |
| RESIDENCE.THE ARCHITECTURAL PLANS ARE |
| NOT CLEAR IF THE WALL CONTINUES PAST THE |
| RATED CEILING.PLEASE NOTE, EXHAUST |
| DUCTS PENETRATING A FIRE RATED WALL |
| SHALL COMPLY WITH 2001 FMC 607.1.3 #3. |
| |
| 4.PLAN SHEET M2 DRYER EXHAUST EXCEEDS |
| THE 25 FT REQUIREMENT WITH REDUCTIONS |
| FOR 90'S PER 2001 FMC 504.6.PLAN SHEET |
| E2.2 INDICATES 'BF' (BOOSTER FAN?). |
| PLEASE NOTE, INSTALLATION OF BOOSTER |
| FANS WILL BE REVIEWED BY THE BUILDING |
| OFFICIAL UNDER "ALTERNATE MATERIALS & |
| METHODS" 2001 FMC 103.7.1.PLEASE |
| PROVIDE THE FOLLOWING INFORMATION FOR |
| REVIEW:1) A LETTER FROIM AN ENGINEER |
| EMPLOYED BY THE DRYER MANUFACTURER |
| STATING THE INSTALLATION OF THE BOOSTER |
| FAN IS ACCEPTABLE AND WILL NOT VOID THE |
| WARRANTY OFTHE DRYER.2) MEANS OF |
| NOTIFYING THE OWNER SHOULD THE BOOSTER |
| FAN FAIL.3) MANUFACTURER'S SUBMITTAL & |
| INSTALLATION DATA FOR THE BOOSTER FAN. |
| 4) PROVIDE ALL PERTINENT INFORMATION FOR |
| ALL TRADES MECHANICAL, ELECTRICAL, FIRE |
| ETC. FOR THE INSTALLATION OF BOOSTER |
| FANS. |
| |
| 5.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH TABLE |
| 403.3 OF THE 2001 FMC. |
| |
| 6.PLEASE PROVIDE DETAIL FOR THE AHU |
| LOCATED IN THE CLOSET.PLEASE NOTE, |
| MECHANICAL CLOSET SHALL BE CONSTRUCTED |
| PER 2001 FMC 603.9 & 610.1.ABC.3.7 OF |
| CHAPTER 13 OF THE 2001 FBC. |
| |
| 7.PLAN SHEET M.2 DRYER EXHAUST APPEARS |
| TO RUN THROUGH THE PLENUM IN THE AHU |
| CLOSET.PLEASE CLARIFY.PER 2001 FMC |
| 601.3, EXHAUST DUCTS SHALL NOT EXTEND |
| INTO OR PASS THROUGH RETURN AIR PLENUMS. |
| |
| 8.PLEASE NOTE, TRANSFER GRILLES FROM |
| THE BEDROOM AREAS SHALL COMPLY WITH 2001 |
| FMC 601.4 EXCEPTION 2 & 3. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561)805-6719. |