Date |
Text |
2006-05-25 00:00:00 | PROVISO:2001 FBC/BUILDING #18/4 UNITS |
| |
| PLEASE REVISE PLANS TO REFLECT THE |
| IMPLEMENTATION OF THE PROVISO'S. |
| |
| COMMENT #6:PLAN SHEET M0.1 AHU DETAIL, |
| NOTE 15 INDICATES NO COMUSTIBLES ALLOWED |
| IN THE AHU CLOSET WHICH SERVES AS THE |
| RETURN AIR PLENUM.THE LOUVERED DOOR |
| LISTED ON PLAN SHEET A-4.0.2 IS |
| CONSTRUCTED OF WOOD.PLEASE NOTE, THE |
| DOOR & FRAME SHALL MEET THE 25 FLAME/50 |
| SMOKE INDEX AS SPECIFIED IN 2001 FMC |
| 602.2.1. |
| |
| COMMENT #9:OUTSIDE AIR CALCULATIONS |
| THAT ARE INDICATED ON PLAN SHEET M0.1 |
| ARE BASED ON INFILTRATION RATE.THE |
| INFILTRATION RATES ARE THE "MAXIMUM" |
| ALLOWED BY CODE AND MAY NOT BE A "TRUE" |
| RATE.PLEASE PROVIDE CALCULATIONS IN |
| ACCORDANCE WITH 2001 FMC 402.2, 402.2.1 |
| OR TABLE 403.3.PLEASE NOTE, 6" OUTSIDE |
| AIR DUCT IS INDICATED ON PLAN SHEEET M2. |
| PLEASE REMOVE FROM THE PLAN IF THE O.A. |
| DUCT WILL NOT BE INSTALLED. |
| |
| PLEASE NOTE, SPECIFIC DRYERS INDICATED |
| ON THE PLAN SHALL BE INSTALLED FOR FINAL |
| INSPECTION. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561)805-6719. |