Plan Review Notes
Plan Review Notes For Permit 05091651
Permit Number 05091651
Review Stop M
Sequence Number 1
Notes
Date Text
2005-11-30 00:00:00DENIED:BUILDING 18 / 2001 FBC
 1.PLAN SHEET A-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED SPRINKLERED.PLEASE
 INDICATE WHICH SYSTEM WILL BE UTILIZED
 (13, 13R, 13D?).PLEASE NOTE,
 ADDITIONAL COMMENTS MAY BE GENERATED BY
 RESPONSES GIVEN.
  
 2.PLAN SHEET A-4.0.1 KEY NOTES/LEGEND,
 ITEM #25 '1HR CHASE REFER TO 11/A-13'.
 PLAN SHEET A-13 WAS NOT SUBMITTED FOR
 REVIEW.
  
 3.PLEASE CLARIFY FIRE RATING OF THE
 WALL SEPARATING THE GARAGE & THE
 RESIDENCE, DOES THE RATING CONTINUE TO
 THE SLAB OR STOP AT THE RATED CEILING?
  
 4.PLAN SHEET M1 INDICATES SUPPLY DUCT
 & EXHAUST PENETRATING A RATED WALL.
 DUCT SHALL COMPLY WITH 2001 FMC 607.1.3
 #3 ITEMS 1 THROUGH 4.
  
 5.PLAN SHEET M2 THE DRYER EXHAUST
 APPEARS TO RUN THROUGH THE MECHANICAL
 CLOSET WHICH IS A PLENUM.PER 2001 FMC
 601.3 EXHAUST DUCT OR VENTS SHALL NOT
 EXTEND INTO OR PASS THROUGH PLENUMS.
  
 6.AHU CLOSET SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH 2001 FMC 603.9.NO
 COMBUSTIBLES ALLOWED IN THE RETURN AIR
 PLENUM PER 2001 FMC 602.2.1.
  
 7.PLEASE PROVIDE A DETAIL OF THE AHU
 CLOSET.
  
 8.PLEASE PROVIDE A DETAIL FOR THE
 MOUNTING OF THE CONDESING UNITS.SHOW
 COMPLIANCE WITH 2001 FMC 301.13.
  
 9.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER TABLE 403.3 OF THE 2001
 FMC.
  
 10. R/A TRANSFER GRILLES SHALL COMPLY
 WITH 2001 FMC 601.4 EXCEPTION 2 & 3 FOR
 PROPER SIZING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved