2006-05-25 00:00:00 | PROVISO: 2001 FBC/BUILDING 17/5 UNITS |
| |
| PLEASE REVISE PLANS TO REFLECT THE |
| IMPLEMENTATION OF THE PROVISO'S. |
| |
| COMMENT #4: REVISED PLANS REMOVED THE |
| BOOSTER FANS.PLANS REFLECT SPECIFIC |
| DRYER TO BE INSTALLED PER MANUFACTURE'S |
| INSTRUCTIONS TO COMPLY WITH 2001 FMC |
| 504.6.PLEASE NOTE, SPECIFIC DRYER TO |
| BE INSTALLED FOR FINAL INSPECTION. |
| |
| COMMENT #5:OUTSIDE AIR CALCULATIONS |
| ARE INDICATED ON PLAN SHEET M0.1. |
| PLEASE NOTE, INFILTRATION RATES ARE |
| "MAXIMUM" RATES AND MAY NOT ACTUALLY |
| EXIST AT THE RATE SPECIFIED ON THE PLAN. |
| PLEASE SHOW COMPLIANCE WITH 2001 FMC |
| 402.2, 402.2.1 OR TABLE 403.3.PROVIDE |
| CALCUATIONS.PLAN SHEET M2 INDICATES A |
| 6" O.A. DUCT, PLEASE REMOVE IF THIS IS |
| NOT BEING INSTALLED. |
| |
| COMMENT #6:AHU CLOSET IS TO BE |
| CONSTRUCTED IN ACCORDANCE WITH 2001 FMC |
| 603.9 & 610.1.ABC.3.7 OF CHAPTER 13 OF |
| THE 2001 FBC.THIS INCLUDES THE |
| LOUVERED DOOR & FRAME ALSO. |
| ARCHITECTURAL PLAN A-4.0.2 SHOWS THE |
| LOUVERED DOOR AS WOOD.THE DOOR & FRAME |
| MUST HAVE A FLAME SPREAD INDEX NOT |
| GREATER THAN 25 & A SMOKE DEVELOPED |
| INDEX NOT MORE THAN 50 WHEN TESTED IN |
| ACCORDANCE WITH ASTM 84. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561)805-6719. |
| |