2006-05-25 00:00:00PROVISO: 2001 FBC/BUILDING 17/5 UNITS
  
 PLEASE REVISE PLANS TO REFLECT THE
 IMPLEMENTATION OF THE PROVISO'S.
  
 COMMENT #4: REVISED PLANS REMOVED THE
 BOOSTER FANS.PLANS REFLECT SPECIFIC
 DRYER TO BE INSTALLED PER MANUFACTURE'S
 INSTRUCTIONS TO COMPLY WITH 2001 FMC
 504.6.PLEASE NOTE, SPECIFIC DRYER TO
 BE INSTALLED FOR FINAL INSPECTION.
  
 COMMENT #5:OUTSIDE AIR CALCULATIONS
 ARE INDICATED ON PLAN SHEET M0.1.
 PLEASE NOTE, INFILTRATION RATES ARE
 "MAXIMUM" RATES AND MAY NOT ACTUALLY
 EXIST AT THE RATE SPECIFIED ON THE PLAN.
 PLEASE SHOW COMPLIANCE WITH 2001 FMC
 402.2, 402.2.1 OR TABLE 403.3.PROVIDE
 CALCUATIONS.PLAN SHEET M2 INDICATES A
 6" O.A. DUCT, PLEASE REMOVE IF THIS IS
 NOT BEING INSTALLED.
  
 COMMENT #6:AHU CLOSET IS TO BE
 CONSTRUCTED IN ACCORDANCE WITH 2001 FMC
 603.9 & 610.1.ABC.3.7 OF CHAPTER 13 OF
 THE 2001 FBC.THIS INCLUDES THE
 LOUVERED DOOR & FRAME ALSO.
 ARCHITECTURAL PLAN A-4.0.2 SHOWS THE
 LOUVERED DOOR AS WOOD.THE DOOR & FRAME
 MUST HAVE A FLAME SPREAD INDEX NOT
 GREATER THAN 25 & A SMOKE DEVELOPED
 INDEX NOT MORE THAN 50 WHEN TESTED IN
 ACCORDANCE WITH ASTM 84.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  