2005-11-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHTS P2.1.1, P-2.2.4, P-3.1.1, P-3.2
 AND P-3.2.4 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINES OF ALL
 UNITS. PER SECTION 604.9. - ALL WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE",
 NOT IN THE CEILING AS SHOWN IN SOME
 CASES. PDI-WH 201 AND MANUF INSTALLATION
 INSTRUCTIONS.
 2. IF INDIVIDUAL METERS NO BACKFLOW
 DEVISE IS REQUIRED, BUT IF SINGLE METER
 AN RPZV BACKFLOW WILL BE REQUIRED ON THE
 WATER SERVICE. PLEASE CLARIFY. SECTION
 608.13.2.
 3. SHT P2.2.4 SANT. RISER AND FLOOR PLAN
 FOR UNIT A. RISER DOES NOT REFLECT THE
 FLOOR PLAN, AND, AS SHOWN, KITCHEN SINK
 ARMS ARE RUN IN FRONT OF THE RANGE ABOVE
 THE FLOOR. PLEASE CLARIFY. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]