Plan Review Notes
Plan Review Notes For Permit 05091649
Permit Number 05091649
Review Stop M
Sequence Number 1
Notes
Date Text
2005-11-29 00:00:00DENIED:BUILDING 17 / 2001 FBC
 1.PLAN SHEET A-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED SPRINKLERED.PLEASE
 INDICATE WHICH SYSTEM WILL BE USED (13,
 13R, 13D ETC).PLEASE NOTE, ADDITIONAL
 COMMENTS MAY BE GENERATED BY THE
 RESPONSE GIVEN.
  
 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND,
 ITEM #25 '1HR CHASE REFER TO 11/A-13'.
 PLAN SHEET A-13 WAS NOT SUBMITTED FOR
 REVIEW.
  
 3.PLAN SHEET M-1 IDNCIATES 8" SUPPLY
 DUCT & 3" EXHAUST PENETRATING THE RATED
 WALL BETWEEN THE GARAGE AND THE
 ERESIDENCE.THE ARCHITECTURAL PLANS ARE
 NOT CLEAR IF THE WALL CONTINUES PAST THE
 RATED CEILING.PLEASE NOTE, EXHAUST
 DUCTS PENETRATING A FIRE REATED WALL
 SHALL COMPLY WITH 2001 FMC 607.1.3 #3.
  
 4.PLAN SHEET M2 DRYER EXHAUST EXCEEDS
 THE 25 FT REQUIREMENT WITH REDUCTIONS
 FOR 90'S PER 2001 FMC 504.6.PLAN SHEET
 E2.2.4 INDICATES 'BF' (BOOSTER FAN?).
 PLEASE NOTE, INSTALLATION OF BOOSTER
 FANS WILL BE REVIEWED BY THE BUILDING
 OFFICIAL UNDER "ALTERNATE MATERIALS &
 METHODS" 2001 FMC 103.7.1.PLEASE
 PROVIDE THE FOLLOWING INFORMATION FOR
 REVIEW:1) A LETTER FROM AN ENGINEER
 EMPLOYED BY THE DRYER MANUFACTURER
 STATING THE INSTALLATION OF THE BOOSTER
 FAN IS ACCEPTABLE AND WILL NOT VOID THE
 WARRANTY OF THE DRYER.2) MEANS OF
 NOTIFYING THE OWNER SHOULD THE BOOSTER
 FAN FAIL.3) MANUFACTURER'S SUBMITTAL &
 INSTALLATION DATA FOR THE BOOSTER FAN.
 4) PROVIDE ALL PERTINENT INFORMATION FOR
 ALL TRADES MECHANICAL, ELECTRICAL, FIRE,
 ETC. FOR THE INSTALLATION OF BOOSTER
 FANS.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH TABLE
 403.3 OF THE 2001 FMC.
  
 6.PLEASE PROVIDE DETAIL FOR THE AHU
 LOCATED IN IN THE CLOSET.PLEASE NOTE
 MECHANICAL CLOSET SHALL BE CONSTRUCTED
 PER 2001 FMC 603.9 & 610.1.ABC.3.7 OF
 CHAPTER 13 OF THE 2001 FBC.
  
 7.PLAN SHEET M2, THE DRYER EXHAUST
 APPEARS TO RUN THROUGH THE PLENUM IN THE
 AHU CLOSET.PLEASE CLARIFY.PER 2001
 FMV 601.3, EXHAUST DUCTS SHALL NOT
 EXTEND INTO OR PASS THROUGH RETURN AIR
 PLENUMS.
  
 8.PLEASE NOTE, TRANSFER GRILLES FROM
 THE BEDROOM AREAS SHALL COMPLY WITH 2001
 FMC 601.4 EXCEPTION 2 & 3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.