Notes
Date Text
2006-05-23 00:00:00PROVISO:2001 FBC/BUILDING 16/6 UNITS
 RESPONSE TO COMMENTS FROM REVIEW DATED
 11/29/05:
  
 PLEASE REVISE PLANS TO REFLECT THE
 IMPLEMENTATION OF THE PROVISO'S.
  
 COMMENT #4:OUTSIDE AIR CALCULATIONS
 ARE INDICATED ON PLAN SHEET M0.1. PLEASE
 NOTE, INFLITRATION RATES ARE "MAXIMUM"
 RATES AND MAY NOT ACTUALLY EXIST. PLEASE
 SHOW COMPLIANCE WITH 2001 FMC 402.2,
 402.2.1 OR TABLE 403.3.PLEASE NOTE,
 PLAN SHEET M2 ALSO INDICATES O.A. DUCT.
 PROVIDE CALCULATIONS.
  
 COMMENT #5:RESPONSE TO COMMENT
 INDICATES DRYER DUCT WILL BE ABOVE THE
 AHU CLOSET.PLAN SHEET M0.1 THE AHU
 MOUNTING DETAIL ALSO STATES NO
 COMBUSTIBLES ALLOWED IN THE AHU CLOSET
 AS IT SERVES AS A PLENUM.THE DOOR
 SCHEDULE INDICATES THE LOUVERED DOOR IS
 WOOD.PLEASE CLARIFY IF THIS WILL MEET
 THE 25 FLAME/50 SMOKE INDEX WHEN TESTED
 IN ACCORDANCE WITH ASTM 84.
  
 COMMENT 6:OK. PLEASE NOTE, SPECIFIC
 DRYERS ARE TO BE INSTALLED FOR FINAL
 INSPECTION.
  
 COMMENT #7: OK.PLEASE NOTE, PLAN SHEET
 M1 UNIT #46 A(R) DOES NOT REFLECT THE
 ARCHITECTURAL PLAN SHOWN ON A-2.0.1 &
 A-4.0.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.