2005-11-29 00:00:00 | DENIED:BUILDING 16 / 2001 FBC |
| 1.PLAN SHEET A-0.0.0 PROJECT |
| INFORMATION INDICATES TYPE VI, |
| UNPROTECTED SPRINKLERED.PLEASE |
| INDICATE WHICH SYSTEM WILL BE UTILIZED |
| (13, 13R, 13D, ETC).PLEASE NOTE, |
| ADDITIONAL COMMENTS MAY BE GENERATED BY |
| THE RESPONSE GIVEN. |
| |
| 2.PLAN SHEET A-4.0.1 KEY NOTES/LEGEND, |
| ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| PLAN SHEET A-13 WAS NOT SUBMITTED FOR |
| REVIEW. |
| |
| 3.PLAN SHEET M1 PLEASE CLARIFY RATING |
| OF THE WALL BETWEEN THE GARAGE & THE |
| RESIDENCE.THE ARCHITECTURAL PLANS ARE |
| NOT CLEAR AS TO WHERE THE 1HR RATING |
| ENDS (AT THE SLAB OR AT THE RATED |
| CEILING).PLEASE NOTE DUCTS PENETRATING |
| RATED WALL SHALL COMPLY WITH 2001 FMC |
| 607.1.3. |
| |
| 4.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH 2001 FMC |
| TABLE 403.3. |
| |
| 5.PLAN SHEET M2, THE DRYER EXHAUST |
| APPEARS TO RUN THROUGH THE AHU.PLEASE |
| NOTE, EXHAUST DUCTS SHALL NOT PASS |
| THROUGH A PLENUM PER 2001 FMC 601.3. |
| |
| 6.DRYER EXHAUST EXCEEDS THE 25 FT |
| MAXIMUM REQUIRED LENGTH PER 2001 FMC |
| 504.6.PLAN SHEET E2.2 INDICATES BF |
| (BOOSTER FAN?).PLEASE NOTE, |
| INSTALLATION OF BOOSTER FANS WILL BE |
| REVIEWED BY THE BUILDING OFFICIAL UNDER |
| "ALTERNATE MATERIALS & METHODS" 2001 FMC |
| 103.7.1.PLEASE PROVIDE THE FOLLOWING |
| INFORMATION FOR REVIEW 1) A LETTER FROM |
| ENGINEER EMPLYED BY THE DRYER |
| MANUFACTURER STATING THE INSTALLATION OF |
| THE BOOSTER FAN IS ACCEPTABLE AND WILL |
| NOT VOID THE WARRANTY OF THE DRYER.2) |
| MEANS OF NOTIFYING THE OWNER SHOULD THE |
| BOOSTER FAN.3) MANUFACTURER'S |
| SUBMITTAL & INSTALLATION DATA FOR THE |
| BOOSTER FAN.4) PROVIDE ALL PERTINENT |
| INFORMATION FOR ALL TRAADES MECHANCIAL, |
| ELECTRICAL, FIRE, ETC. FOR THE |
| INSTALLATION OF BOOSTER FANS. |
| |
| 7.TRANSFER GRILLES SHALL BE SIZED IN |
| ACCORDANCE WITH 2001 FMC 601.4 EXCEPTION |
| 2 & 3. |
| |