Plan Review Notes
Plan Review Notes For Permit 05091647
Permit Number 05091647
Review Stop M
Sequence Number 1
Notes
Date Text
2005-12-01 00:00:00DENIED:BUILDING 12 / 2001 FBC
 1.PLAN SHEET A-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED SPRINKLERED.PLEASE
 INDICATE WHIHC SYSTEM WILL BE UTILIZED
 (13, 13R, 13D?).PLEASE NOTE,
 ADDITIONAL COMMENTS MAY BE GENERATED BY
 THE RESPONSES GIVEN.
  
 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND,
 ITEM #25 '1HR CHASE REFER TO 11/A-13'.
 PLAN SHEET A-13 WAS NOT SUBMITTED FOR
 REVIEW.
  
 3.PLEASE CLARIFY FIRE RATING OF THE
 WALL SEPARATING THE GARAGE & THE
 RESIDENCE, DOES THE RATING CONTINUE TO
 THE SLAB OR THE RATED CEILING?
  
 4.PLAN SHEET M1 INDICATES SUPPLY &
 EXHAUST DUCT PENETRATING RATED WALL.
 DUCT SHALL COMPLY WITH 2001 FMC 607.1.3
 #3 ITEMS 1 THROUGH 4.
  
 5.PLAN SHEET M2 INDICATES DRYER
 EXHAUST GOING THROUGH THE AHU CLOSET
 WHICH APPEARS TO BE A PLENUM.PER 2001
 FMC 601.3 EXHAUST DUCT OR VENTS SHALL
 NOT EXTEND INTO OR PASS THROUGH A
 PLENUM.
  
 6.DRYER EXHAUST EXCEEDS THE 25FT
 MAXIMUM LENGTH WITH THE 5FT REDUCTION
 FOR EACH 90.PLAN SHEET E2.2.4
 INDICATES 'BF' (BOOSTER FAN?).PLEASE
 NOTE, INSTALLATION OF DRYER BOOSTER FANS
 WILL BE REVIEWED BY THE BUILDING
 OFFICIAL UNDER "ALTERNATE MATERIALS &
 METHODS" 2001 FMC 103.7.1.PLEASE
 PROVIDE THE FOLLOWING INFORMATION FOR
 REVIEW:1) A LETTER FRON AN ENGINEER
 EMPLOYED BY THE DRYER MANUFACTURER
 STATING THE INSTALLATION OF THE DRYER
 BOOSTER FAN IS ACCEPTABLE AND WILL NOT
 VOID THE WARRANTY OF THE DRYER.2)
 MEANS OF NOTIFYING THE OWNER SHOULD THE
 BOOSTER FAN FAIL.3) MANUFACTURER'S
 SUBMITTAL & INSTALLATION INSTRUCTIONS
 FOR THE BOOSTER FAN.4) PROVIDE ALL
 PERTINENT INFORMATION FOR ALL TRADES
 MECHANICAL, ELECTRICAL, FIRE, ETC. FOR
 THE INSTALLATION OF THE BOOSTER FANS.
  
 7.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER TABLE 403.3 OFTHE 2001
 FMC.
  
 8.PLEASE PROVIDE A DETAIL OF THE AHU
 LOCATED IN THE CLOSET.PLEASE NOTE,
 MECHANICAL CLOSET SHALL BE CONTRUCTED
 PER 2001 FMC 603.9.NO COMBUSTIBLES
 ALLOWED IN THE RETURN AIR PLENUM PER
 2001 FMC 602.2.1.
  
 9.PLEASE PROVIDE A DETAIL OF THE
 ANCHORING OF THE CONDENSING UNIT PER
 2001 FMC 301.13.
  
 10. R/A TRANSFER GRILLES SHALL BE SIZED
 IN ACCORDANCE WITH 2001 FMC 601.4
 EXCEPTION 2 & 3, THIS IS A REQUIRED
 MINIMUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.