Date |
Text |
2005-12-01 00:00:00 | DENIED:BUILDING 12 / 2001 FBC |
| 1.PLAN SHEET A-0.0.0 PROJECT |
| INFORMATION INDICATES TYPE VI, |
| UNPROTECTED SPRINKLERED.PLEASE |
| INDICATE WHIHC SYSTEM WILL BE UTILIZED |
| (13, 13R, 13D?).PLEASE NOTE, |
| ADDITIONAL COMMENTS MAY BE GENERATED BY |
| THE RESPONSES GIVEN. |
| |
| 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND, |
| ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| PLAN SHEET A-13 WAS NOT SUBMITTED FOR |
| REVIEW. |
| |
| 3.PLEASE CLARIFY FIRE RATING OF THE |
| WALL SEPARATING THE GARAGE & THE |
| RESIDENCE, DOES THE RATING CONTINUE TO |
| THE SLAB OR THE RATED CEILING? |
| |
| 4.PLAN SHEET M1 INDICATES SUPPLY & |
| EXHAUST DUCT PENETRATING RATED WALL. |
| DUCT SHALL COMPLY WITH 2001 FMC 607.1.3 |
| #3 ITEMS 1 THROUGH 4. |
| |
| 5.PLAN SHEET M2 INDICATES DRYER |
| EXHAUST GOING THROUGH THE AHU CLOSET |
| WHICH APPEARS TO BE A PLENUM.PER 2001 |
| FMC 601.3 EXHAUST DUCT OR VENTS SHALL |
| NOT EXTEND INTO OR PASS THROUGH A |
| PLENUM. |
| |
| 6.DRYER EXHAUST EXCEEDS THE 25FT |
| MAXIMUM LENGTH WITH THE 5FT REDUCTION |
| FOR EACH 90.PLAN SHEET E2.2.4 |
| INDICATES 'BF' (BOOSTER FAN?).PLEASE |
| NOTE, INSTALLATION OF DRYER BOOSTER FANS |
| WILL BE REVIEWED BY THE BUILDING |
| OFFICIAL UNDER "ALTERNATE MATERIALS & |
| METHODS" 2001 FMC 103.7.1.PLEASE |
| PROVIDE THE FOLLOWING INFORMATION FOR |
| REVIEW:1) A LETTER FRON AN ENGINEER |
| EMPLOYED BY THE DRYER MANUFACTURER |
| STATING THE INSTALLATION OF THE DRYER |
| BOOSTER FAN IS ACCEPTABLE AND WILL NOT |
| VOID THE WARRANTY OF THE DRYER.2) |
| MEANS OF NOTIFYING THE OWNER SHOULD THE |
| BOOSTER FAN FAIL.3) MANUFACTURER'S |
| SUBMITTAL & INSTALLATION INSTRUCTIONS |
| FOR THE BOOSTER FAN.4) PROVIDE ALL |
| PERTINENT INFORMATION FOR ALL TRADES |
| MECHANICAL, ELECTRICAL, FIRE, ETC. FOR |
| THE INSTALLATION OF THE BOOSTER FANS. |
| |
| 7.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS PER TABLE 403.3 OFTHE 2001 |
| FMC. |
| |
| 8.PLEASE PROVIDE A DETAIL OF THE AHU |
| LOCATED IN THE CLOSET.PLEASE NOTE, |
| MECHANICAL CLOSET SHALL BE CONTRUCTED |
| PER 2001 FMC 603.9.NO COMBUSTIBLES |
| ALLOWED IN THE RETURN AIR PLENUM PER |
| 2001 FMC 602.2.1. |
| |
| 9.PLEASE PROVIDE A DETAIL OF THE |
| ANCHORING OF THE CONDENSING UNIT PER |
| 2001 FMC 301.13. |
| |
| 10. R/A TRANSFER GRILLES SHALL BE SIZED |
| IN ACCORDANCE WITH 2001 FMC 601.4 |
| EXCEPTION 2 & 3, THIS IS A REQUIRED |
| MINIMUM. |
| |