Plan Review Notes For Permit 05091646 |
Permit Number |
05091646 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-15 00:00:00 | ***** UNSAT ******** | | | | 1) NOTE: PLEASE SEE SERVICE IS SHOWN AS | | A 6 UNIT BUILDING INCLUDING LOADS CALCS, | | YET PLANS INDICATE IN 5 UNITS IN TITLE | | BLOCKS AND KEY PLANS? | | PLEASE CORRELATE. | | 215.5 | | | | 2) NOTE:PLEASE SEE #1 GEC SHOWN, WHERE | | A 2/0 MIN IS REQUIRED PER 250.66 BASED | | ON THE PARALLEL SEC'S SHOWN. | | | | 3) NOTE: PLEASE SEE 424.3B FOR MIN OCP | | SHALL BE 125% FOR AHU'S. PLEASE SEE OCP | | HAS NOW BEEN DECREASED TO 40A'S??? | | | | 4) NOTE: PLEASE INDICAT ETHE #, OF | | RECESSED FIXTURES IN LOAD CALCS. SHOWS | | LOADS WHICH ARE OK. | | 215.5 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|