Plan Review Notes
Plan Review Notes For Permit 05091646
Permit Number 05091646
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-15 00:00:00***** UNSAT ********
  
 1) NOTE: PLEASE SEE SERVICE IS SHOWN AS
 A 6 UNIT BUILDING INCLUDING LOADS CALCS,
 YET PLANS INDICATE IN 5 UNITS IN TITLE
 BLOCKS AND KEY PLANS?
 PLEASE CORRELATE.
 215.5
  
 2) NOTE:PLEASE SEE #1 GEC SHOWN, WHERE
 A 2/0 MIN IS REQUIRED PER 250.66 BASED
 ON THE PARALLEL SEC'S SHOWN.
  
 3) NOTE: PLEASE SEE 424.3B FOR MIN OCP
 SHALL BE 125% FOR AHU'S. PLEASE SEE OCP
 HAS NOW BEEN DECREASED TO 40A'S???
  
 4) NOTE: PLEASE INDICAT ETHE #, OF
 RECESSED FIXTURES IN LOAD CALCS. SHOWS
 LOADS WHICH ARE OK.
 215.5
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]