2005-11-30 00:00:00 | DENIED:BUILDING 13 /2001 FBC |
| 1.PLAN SHEET A-0.0.0 PROJECT |
| INFORMATION INDICATES TYPE VI, |
| UNPROTECTED SPRINKLERED.PLEASE |
| INDICATE WHICH SYSTEM WILL BE UTILIZED |
| (13, 13R, 13D?).PLEASE NOTE, |
| ADDITIONAL COMMENTS MAY BE GENERATED BY |
| THE RESPONSES GIVEN. |
| |
| 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND, |
| ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| PLAN SHEET A-13 WAS NOT SUBMITTED FOR |
| REVIEW. |
| |
| 3.PLEASE CLARIFY FIRE RATING OF THE |
| WALL SEPARATING THE GARAGE & THE |
| RESIDENCE, DOES THE RATING CONTINUE TO |
| THE SLAB OR STOP AT THE RATED CEILING? |
| |
| 5.PLAN SHEET M1 INDICATES 8" SUPPLY |
| DUCT & 3" EXHAUST PENETRATING A RATED |
| WALL.DUCT SHALL COMPLY WITH 2001 FMC |
| 607.1.3 #3 ITEMS 1 THROUGH 4. |
| |
| 6.PLAN SHEET M2 THE DRYER EXHAUST |
| APPEARS TO RUN THROUGH THE MECHANICAL |
| CLOSET WHICH IS A PLENUM.PER 2001 FMC |
| 601.3 EXHAUST DUCTS OR VENTS SHALL NOT |
| EXTEND INTO OR PASS THROUGH PLENUMS. |
| |
| 7.AHU CLOSET SHALL BE CONSUTRUCTED IN |
| ACCORDANCE WITH 2001 FMC 603.9.NO |
| COMUMBUSTIBLES ALLOWED IN THE RETURN AIR |
| PLENUM PER 2001 FMC 602.2.1. |
| |
| 8.PLEASE PROVIDE A DETAIL OF THE AHU |
| CLOSET. |
| |
| 9.PLEASE PROVIDE DETAIL FOR THE |
| ANCHORING OF THE CONDENSING UNITS.SHOW |
| COMPLIANCE WITH 2001 FMC 301.13. |
| |
| 10. R/A TRANSFER GRILLES SHALL COMPLY |
| WITH 2001 FMC 601.4 EXCEPTION 2 & 3 FOR |
| PROPER SIZING. |
| |
| 11.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH 2001 FMC |
| TABLE 403.3. |
| |