Plan Review Notes
Plan Review Notes For Permit 05091645
Permit Number 05091645
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-15 00:00:00********* UNSAT *********
  
  
  
 1) NOTE: PLEASE SEE KEY PLAN AND TITLE
 BLOCKS INDICATES A 5 UNIT BUILDING,
 HOWEVER SERVICE, RISER AND CALCS
 INDICATE 6 UNITS? PLEASE CORRELATE.
  
 2) NOTE: PLEASE SEE #1 GEC SHOWN, WHERE
 A 2/0 MIN IS REQUIRED PER 250.66 BASED
 ON THE SEC'S SHOWN ON RISER AND PLANS.
  
 3) NOTE: PLEASE SEE 424.3B FOR MIN OCP
 SHALL BE 125% FOR AHU'S. PLEASE SEE OCP
 HAS NOW BEEN DECREASED TO 40A'S???
  
 4) NOTE: PLEASE INDICATE THE # OF
 RECESSED LTS ON PANEL SCHEDULE CALCS.
 THE LOAD IS SHOWN AND IS OK.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  