Plan Review Notes For Permit 05091645 |
Permit Number |
05091645 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-15 00:00:00 | ********* UNSAT ********* | | | | | | | | 1) NOTE: PLEASE SEE KEY PLAN AND TITLE | | BLOCKS INDICATES A 5 UNIT BUILDING, | | HOWEVER SERVICE, RISER AND CALCS | | INDICATE 6 UNITS? PLEASE CORRELATE. | | | | 2) NOTE: PLEASE SEE #1 GEC SHOWN, WHERE | | A 2/0 MIN IS REQUIRED PER 250.66 BASED | | ON THE SEC'S SHOWN ON RISER AND PLANS. | | | | 3) NOTE: PLEASE SEE 424.3B FOR MIN OCP | | SHALL BE 125% FOR AHU'S. PLEASE SEE OCP | | HAS NOW BEEN DECREASED TO 40A'S??? | | | | 4) NOTE: PLEASE INDICATE THE # OF | | RECESSED LTS ON PANEL SCHEDULE CALCS. | | THE LOAD IS SHOWN AND IS OK. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|