2005-11-22 00:00:00 | DENIED:BUILDING #14 |
| 1.PLAN SHEET A-0.0.0 PROJECT |
| INFORMATION INDICATES TYPE VI, |
| UNPROTECTED SPRINKLERED.PLEASE |
| INDICATE WHICH SPRINKLERED SYSTEM WILL |
| BE UTILIZED - (13, 13R, 13D, ETC). |
| PLEASE NOTE ADDITIONAL COMMENTS MAY BE |
| GENERATED BY THE RESPONSES GIVEN. |
| |
| 2.PLEASE CLARIFY DUCT PENETRATION |
| THROUGH THE SEPARATION WALL BETWEEN THE |
| GARAGE & THE RESIDENCE.PLAN SHEET |
| A-4.0.2 & A-10.0.0, INDICATES THIS |
| SEPARATION AS 1 HR.PLAN M1 ONLY |
| INDICATES A FIRE DAMPER AT THE CEILING |
| PENETRATION.DUCTS LESS THAN 100 SQ |
| INCHES SHALL COMPLY WITH 2001 FMC |
| 607.1.3 #3 ITEMS 1 THROUGH 4. |
| |
| 3.PLAN SHEET M2 DRYER EXHAUST EXCEEDS |
| 25FT REQUIREMENT WITH REDEUCTIONS FOR |
| 90'S PER 2001 FMC 504.6.PLAN SHEET |
| E2.2.4 INDICATES "BF" (BOOSTER FAN?). |
| PLEASE NOTE, INSTALLATION OF BOOSTER |
| FANS WILL BE REVIEWED BY THE BUILDING |
| OFFICIAL UNDER "ALTERNATE MATERIALS & |
| MEDTHODS" 2001 FMC 103.7.1.PLEASE |
| PROVIDE THE DFOLLOWING INFORMATION FOR |
| REVIEW:1) A LETTER FROM AN ENGINEER |
| EMPLOYED BY THE DRYER MANUFACTURER |
| STATING THE INSTALLLATION OF THE DRYER |
| BOOSTER FAN IS ACCEPTABLE & WILL NOT |
| VOID THE WARRANTY OF THE DRYER. 2) MEANS |
| OF NOTIFYING THE OWNER SHOULD THE |
| BOOSTER FAN FAIL.3) MANUFACTURER'S |
| SUBMITTAL & INSTALLATION DATA FOR THE |
| BOOSTER FANS.4) PROVIDE ALL PERTINENT |
| INFORMATION FOR ALL TRADES MECHANICAL, |
| ELECTRICAL, FIRE, ETC. |
| |
| 4.PLAN SHEET M2 THE O.A. INTAKE IS |
| WITHIN 10 FT OF THE TOILET & DRYER |
| EXHAUST TERMINATIONS.EXHAUST |
| CONTAMINANTES SHALL NOT BE RECIRCULATED |
| PER 2001 FMC 501.3. |
| |
| 5.PLEASE PROVIDE OUTSIDE CALCULATIONS |
| IN ACCORDANCE WITH 2001 FMC TABLE 403.3. |
| |
| 6.PLEASE NOTE RETURN AIR TRANSFER |
| GRILLES ARE NOT SIZED PROPERLY, SEE 2001 |
| FMC 601.4 EXCEPTION 2 & 3.PLEASE SIZE |
| TRANSFER GRILLES ACCORDINGLY. |
| |
| 7.PLEASE PROVIDE DETAIL FOR THE AHU |
| LOCATED IN THE CLOSET.PLEASE NOTE, |
| MECHANICAL CLOSET SHALL BE CONSTRUCTED |
| PER 2001 FMC 603.9 & 610.1.ABC.3.7 OF |
| CHAPTER 13 OF THE 2001 FBC. |
| |
| 8.NO COMBUSTIBLES ALLOWED IN THE |
| MECHANICAL CLOSET PER 2001 FMC 602.2.1. |
| |
| 9.CONDENSATE DRAIN SHALL TERMINTE A |
| MINIMUM OF 12" FROM THE BUILDING |
| STRUCTURE PER 2001 FBC 1503.4.4. |
| |
| 10. AUXILIARY DRAIN PAN WITH OVERFLOW |
| PROTECTION REQUIRED PER 2001 FMC |
| 307.2.3. |
| |