Plan Review Notes For Permit 05091645
Permit Number 05091645
Review Stop M
Sequence Number 1
Notes
Date Text
2005-11-22 00:00:00DENIED:BUILDING #14
 1.PLAN SHEET A-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED SPRINKLERED.PLEASE
 INDICATE WHICH SPRINKLERED SYSTEM WILL
 BE UTILIZED - (13, 13R, 13D, ETC).
 PLEASE NOTE ADDITIONAL COMMENTS MAY BE
 GENERATED BY THE RESPONSES GIVEN.
  
 2.PLEASE CLARIFY DUCT PENETRATION
 THROUGH THE SEPARATION WALL BETWEEN THE
 GARAGE & THE RESIDENCE.PLAN SHEET
 A-4.0.2 & A-10.0.0, INDICATES THIS
 SEPARATION AS 1 HR.PLAN M1 ONLY
 INDICATES A FIRE DAMPER AT THE CEILING
 PENETRATION.DUCTS LESS THAN 100 SQ
 INCHES SHALL COMPLY WITH 2001 FMC
 607.1.3 #3 ITEMS 1 THROUGH 4.
  
 3.PLAN SHEET M2 DRYER EXHAUST EXCEEDS
 25FT REQUIREMENT WITH REDEUCTIONS FOR
 90'S PER 2001 FMC 504.6.PLAN SHEET
 E2.2.4 INDICATES "BF" (BOOSTER FAN?).
 PLEASE NOTE, INSTALLATION OF BOOSTER
 FANS WILL BE REVIEWED BY THE BUILDING
 OFFICIAL UNDER "ALTERNATE MATERIALS &
 MEDTHODS" 2001 FMC 103.7.1.PLEASE
 PROVIDE THE DFOLLOWING INFORMATION FOR
 REVIEW:1) A LETTER FROM AN ENGINEER
 EMPLOYED BY THE DRYER MANUFACTURER
 STATING THE INSTALLLATION OF THE DRYER
 BOOSTER FAN IS ACCEPTABLE & WILL NOT
 VOID THE WARRANTY OF THE DRYER. 2) MEANS
 OF NOTIFYING THE OWNER SHOULD THE
 BOOSTER FAN FAIL.3) MANUFACTURER'S
 SUBMITTAL & INSTALLATION DATA FOR THE
 BOOSTER FANS.4) PROVIDE ALL PERTINENT
 INFORMATION FOR ALL TRADES MECHANICAL,
 ELECTRICAL, FIRE, ETC.
  
 4.PLAN SHEET M2 THE O.A. INTAKE IS
 WITHIN 10 FT OF THE TOILET & DRYER
 EXHAUST TERMINATIONS.EXHAUST
 CONTAMINANTES SHALL NOT BE RECIRCULATED
 PER 2001 FMC 501.3.
  
 5.PLEASE PROVIDE OUTSIDE CALCULATIONS
 IN ACCORDANCE WITH 2001 FMC TABLE 403.3.
  
 6.PLEASE NOTE RETURN AIR TRANSFER
 GRILLES ARE NOT SIZED PROPERLY, SEE 2001
 FMC 601.4 EXCEPTION 2 & 3.PLEASE SIZE
 TRANSFER GRILLES ACCORDINGLY.
  
 7.PLEASE PROVIDE DETAIL FOR THE AHU
 LOCATED IN THE CLOSET.PLEASE NOTE,
 MECHANICAL CLOSET SHALL BE CONSTRUCTED
 PER 2001 FMC 603.9 & 610.1.ABC.3.7 OF
 CHAPTER 13 OF THE 2001 FBC.
  
 8.NO COMBUSTIBLES ALLOWED IN THE
 MECHANICAL CLOSET PER 2001 FMC 602.2.1.
  
 9.CONDENSATE DRAIN SHALL TERMINTE A
 MINIMUM OF 12" FROM THE BUILDING
 STRUCTURE PER 2001 FBC 1503.4.4.
  
 10. AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FMC
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.