Plan Review Notes For Permit 05091490 |
Permit Number |
05091490 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-27 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | FROM PREVIOUS REVIEW: | | | | 1. SHT P2.2 WATER HAMMER ARRESTOR SHALL | | BE LOCATED NEAR THE FIXTURES IN AN | | "EFFECTIVE RANGE" NOT IN THE CEILING AS | | SHOWN. PDI-WH 201 AND MANUF. | | INSTALLATION INSTRUCTIONS. | | ***COMMENT RESPONSE NOTED. THIS WAS NOT | | SEEN FIRST REVIEW. | | | | 3. SHT P3.2.4 RISER AND FLOOR PLAN FOR | | UNIT B. RISER DOES NOT REFLECT THE FLOOR | | PLAN AND AS SHOWN, KITCHEN SINK ARMS ARE | | RUNNING IN FRONT OF THE RANGE ABOVE THE | | FLOOR. PLEASE CLARIFY. SECTION 104.2.1. | | ***RESPONSE NOTED, BUT FLOOR PLAN HAS | | BEEN CHANGE, AND RISER STILL DOES NOT | | REFLECT THE FLOOR PLAN. - ALSO SEE SHT | | P2.2.4 FOR THE SAME CONDITION. | | | | **************NEW COMMENT************** | | | | 1B. SHTS P2.1.1, P2.1, P3.1.1, & P3.1 | | SANITARY BUILDING DRAIN SHALL BE A | | MINIMUM OF 4 FT OFF THE FOOTER PER | | SECTION 307.4. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|