Plan Review Notes For Permit 05091490 |
Permit Number |
05091490 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-24 00:00:00 | PROVISO:2001 FBC/BUILDING 15/6 UNITS | | RESPONSE TO COMMENTS FROM REVIEW DATED | | 2/7/06: | | | | PLEASE REVISE PLANS TO REFLECT THE | | IMPLEMENTATION OF THE PROVISO'S. | | | | COMMENT #6:SPECIFIC DRYERS ARE TO BE | | INSTALLED FOR FINAL INSPECTION. | | | | COMMENT #7:OUTSIDE AIR CALCULATIONS | | ARE INDICATED ON PLAN SHEET M0.1. | | PLEASE NOTE, INFILTRATION RATES ARE THE | | "MAXIMUM" ALLOWABLE RATES AND MAY NOT | | ACTUALLY EXIST.PLEASE SHOW COMPLIANCE | | WITH 2001 FMC 402.2, 402.2.1 OR TABLE | | 403.3.PROVIDE CALCULATIONS.PLAN | | SHEET M2 INDICATES 6" O.A. DUCT. | | | | COMMENT #8:NO COMBUSTIBLES ALLOWED IN | | THE RETURN AIR PLENUM IS ANNOTATED IN | | NOTE #15 OF THE AHU DETAIL ON PLAN SHEET | | M0.1.HOWEVER THE LOUVERED DOOR | | INDICATED ON PLAN SHEET A-4.1.1, 4.4.1 & | | 4.4.5 SHOW A WOOD LOUVERED DOOR.PLEASE | | VERIFY THE 25 FLAME/50 SMOKE INDEX WHEN | | TESTED IN ACCORDANCE WTIH ASTM 84 PER | | 2001 FMC 602.2.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|