2006-05-15 00:00:00***** NOTES REDLINED *******
  
 REVISE ONLY IF THERE ARE OTHER
 ELECTRICAL REVISIONS BEFORE ROUGH.
  
 ** PLEASE SEE #1 GEC SHOWN, WHERE A 2/0
 MIN IS REQUIRED PER 250.66.
  
 ** PLEASE SEE 424.3B FOR MIN OCP SHALL
 BE 125% FOR AHU'S. PLEASE SEE OCP HAS
 NOW BEEN DECREASED TO 40A'S???
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  