Plan Review Notes For Permit 05091490 |
Permit Number |
05091490 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-15 00:00:00 | ***** NOTES REDLINED ******* | | | | REVISE ONLY IF THERE ARE OTHER | | ELECTRICAL REVISIONS BEFORE ROUGH. | | | | ** PLEASE SEE #1 GEC SHOWN, WHERE A 2/0 | | MIN IS REQUIRED PER 250.66. | | | | ** PLEASE SEE 424.3B FOR MIN OCP SHALL | | BE 125% FOR AHU'S. PLEASE SEE OCP HAS | | NOW BEEN DECREASED TO 40A'S??? | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|