Date |
Text |
2005-11-28 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| |
| 1. SHTS P2.1.1, P-2.2.4, P-3.1.1, P-3.2 |
| AND P-3.2.4 WATER HAMMER ARRESTORS ARE |
| REQUIRED AT THE WASH MACHINES OF ALL |
| UNITS. PER SECTION 604.9. - ALL WATER |
| HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| THE FIXTURES IN AN "EFFECTIVE RANGE", |
| NOT IN THE CEILING AS SHOWN IN SOME |
| CASES. PDI-WH 201 AND MANUF INSTALLATION |
| INSTRUCTIONS. |
| 2. IF INDIVIDUAL METERS NO BACKFLOW |
| DEVISE IS REQUIRED, BUT IF SINGLE METER |
| AN RPZV BACKFLOW WILL BE REQUIRED ON THE |
| WATER SERVICE. PLEASE CLARIFY. SECTION |
| 608.13.2. |
| 3. SHT P3.2.4 RISER AND FLOOR PLAN FOR |
| UNIT B. RISER DOES NOT REFLECT THE FLOOR |
| PLAN, AND AS SHOWN, KITCHEN SINK ARMS |
| ARE RUNNING IN FRONT OF THE RANGE ABOVE |
| THE FLOOR. PLEASE CLARIFY. SECTION |
| 104.2.1. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |
| DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| |
| 1. SHTS P2.1.1, P-2.2.4, P-3.1.1, P-3.2 |
| AND P-3.2.4 WATER HAMMER ARRESTORS ARE |
| REQUIRED AT THE WASH MACHINES OF ALL |
| UNITS. PER SECTION 604.9. - ALL WATER |
| HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| THE FIXTURES IN AN "EFFECTIVE RANGE", |
| NOT IN THE CEILING AS SHOWN IN SOME |
| CASES. PDI-WH 201 AND MANUF INSTALLATION |
| INSTRUCTIONS. |
| 2. IF INDIVIDUAL METERS NO BACKFLOW |
| DEVISE IS REQUIRED, BUT IF SINGLE METER |
| AN RPZV BACKFLOW WILL BE REQUIRED ON THE |
| WATER SERVICE. PLEASE CLARIFY. SECTION |
| 608.13.2. |
| |