2007-04-04 10:59:13REVISION/DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT A-1 SHOW ALL PIPE SIZES DOWNSTREAM OF THE 6" HUB
 DRAINS. TABLE 710.1(1). THESE PIPES SHALL NOT REDUCE IN
 THE DIRECTION OF FLOW PER SECTION 704.2.
  
 2. SHT A-1 SHOW ALL CLEANOUTS REQUIRED BY SECTIONS
 708.3.1 & 708.3.3 IN LINES TO NEW 6" HUB DRAINS.
  
 3. SHT A-1 REVISIONS 10 THRU 15 NOT INDICATED WITH
 CLOUDS OR NUMBERED TRIANGLES. THESE REVISIONS ARE NOT
 APPROVED. SECTION 104.2.1.
  
 4. ALL CHANGES TO THE SANITARY ON THEFLOOR PLAN SHALL
 BE REFLECTED ON THE SANITARY RISER DIAGRAM. REVISIONS
 WILL BE REQUIRED FOR THE RISER DIAGRAM. SECTION
 104.2.1.
  
 5. SHT P-20 DETAIL FOR THE SPRINKLER DRAIN DOES NOT
 REFLECT WHAT IS SHOWN ON THE FLOOR PLAN SHEET P-1. NO
 TRAP IS SHOWN, NO HUB IS SHOWN, NO VENT IS SHOWN AND
 PIPE SIZE WILL BE REQUIRED TO BE 6". SECTIONS 704.2,
 901.2.1, 1002.1 & 104.2.1.
  
 6. SHT P-20 NOTESSTATES PROVIDE FLEXIBLE CONNECTION
 TO SITE DRAINAGE. PLEASE PROVIDE A DETAIL SHOWING THE
 CONNECTION AND INDICATING THE MATERIAL TO BE USED.
 SECTIONS 104.2.1, 301.2 & 301.3.
  
 REVIEW BY KEN STEVENS