Plan Review Notes For Permit 05091425 |
Permit Number |
05091425 |
|
Review Stop |
M |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2007-03-22 18:51:38 | DENIED | | | | PAGES AC-4 AND AC-7 | | | | COMMENTS FOR THIS REVIEW ARE NUMBERED TO CORRELATE WITH | | PREVIOUS PLAN REVIEW COMMENTS FOR CONTINUITY. | | | | 1. OK | | | | 2. RESPONSE TO THIS COMMENT STATES "NO CHANGE. NOT PART | | OF THIS REV." IF THAT IS THE CASE, PLEASE REMOVE THE | | CLOUD AND THE DELTA-12 DESIGNATION. FBC 106.1.3. | | | | 3. AC-13 WAS MISTAKENLY OMITTED FROM THIS COMMENT. | | THERE ARE FOUR UNPROTECTED OPENINGS RESULTING FROM DUCT | | PENETRATIONS RELATED TO THIS SYSTEM. PLEASE SEE REVISED | | ARCHITECTURAL DRAWING A-2.4.5 REV. 6 FOR LOCATIONS OF | | ALL RATED WALLS WHICH MAY BE AFFECTED BY BY THESE DUCT | | SYSTEMS. ALL SUCH OPENINGS ARE TO BE PROTECTED PER | | FBC,M 607.1.2. | | | | 4. THIS AREA IS PART OF THE REVISION AS EF 28 AND | | RELATED DUCTS DO NOT APPEAR ON THE PREVIOUSLY REVIEWED | | PLAN (SEE REVISION 11 DATED 2/24/06). THE ADDED WORK ON | | THIS PAGE MAKES IT PART OF THIS REVISION EVEN IF IT IS | | INCORRECTLY DESIGNATED AS BEING PART OF A PREVIOUS | | REVISION. PLEASE CORRECT AND RESUBMIT. FBC 106.1.3. | | | | 5. OK | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|