2007-03-22 18:51:38DENIED
  
 PAGES AC-4 AND AC-7
  
 COMMENTS FOR THIS REVIEW ARE NUMBERED TO CORRELATE WITH
 PREVIOUS PLAN REVIEW COMMENTS FOR CONTINUITY.
  
 1. OK
  
 2. RESPONSE TO THIS COMMENT STATES "NO CHANGE. NOT PART
 OF THIS REV." IF THAT IS THE CASE, PLEASE REMOVE THE
 CLOUD AND THE DELTA-12 DESIGNATION. FBC 106.1.3.
  
 3. AC-13 WAS MISTAKENLY OMITTED FROM THIS COMMENT.
 THERE ARE FOUR UNPROTECTED OPENINGS RESULTING FROM DUCT
 PENETRATIONS RELATED TO THIS SYSTEM. PLEASE SEE REVISED
 ARCHITECTURAL DRAWING A-2.4.5 REV. 6 FOR LOCATIONS OF
 ALL RATED WALLS WHICH MAY BE AFFECTED BY BY THESE DUCT
 SYSTEMS. ALL SUCH OPENINGS ARE TO BE PROTECTED PER
 FBC,M 607.1.2.
  
 4. THIS AREA IS PART OF THE REVISION AS EF 28 AND
 RELATED DUCTS DO NOT APPEAR ON THE PREVIOUSLY REVIEWED
 PLAN (SEE REVISION 11 DATED 2/24/06). THE ADDED WORK ON
 THIS PAGE MAKES IT PART OF THIS REVISION EVEN IF IT IS
 INCORRECTLY DESIGNATED AS BEING PART OF A PREVIOUS
 REVISION. PLEASE CORRECT AND RESUBMIT. FBC 106.1.3.
  