2007-02-11 17:34:08BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 12/18/06 FOR CLUBROOM AND FITNESS
 CENTER BUILDOUT.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 704.1.2.3OCCUPANCY SEPARATION FOR FITNESS
 CENTER AND CLUB LOUNGE.THE PLANS SHALL STATE THE
 TOTAL AREA OF THE FITNESS CENTER AND TOTAL AREA OF THE
 CLUB LOUNGE.PER FBC 304.1.2 THEY ARE CLASSIFIED AS
 ASSEMBLY OCCUPANCY.IF THE AREA EXCEEDS 2,000 SQ FT,
 THEY SHALL BE SEPARATED FROM THE RESIDENTIAL OCCUPANCY
 BY 2 HOUR FIRE RESISTANT CONSTRUCTION.THE FITNESS
 CENTER AND CLUB LOUNGE BOTH EXCEED 750 SQ FT SO, PER
 FBC 704.1.2.2, THEY CANNOT BE CONSIDERED AS INCIDENTAL
 TO THE RESIDENTIAL OCCPANCY.AMEND THE PLANS TO STATE
 THE AREA OF THE FITNESS CENTER AND CLUB LOUNGE, AND
 INCREASE THE OCCUPANCY SEPARATION FIRE RESISTANCE TO 2
 HOURS IF APPROPRIATE.
  
 2) FBC 1012.1.2FITNESS CENTER DOOR 51.THE DOOR TO
 THE EXIT ACCESS CORRIDOR IS SHOWN SWINGING INTO THE
 FITNESS CENTER.THE DOOR SHALL OPEN IN THE DIRECTION
 OF EGRESS.AMEND THE PLANS.
  
 3) FBC 1012.7FITNESS CENTER EGRESS DOORS.PER FBC
 1004.1.2 NOT LESS THAN TWO EGRESS DOORS ARE REQUIRED.
 THE DOOR SCHEDULE ON SHEET A-4.1 SPECIFIES MAGNETIC
 LOCKS (HARDWARE NOTE 9) FOR DOOR 51 AND DOOR 50
 (LEADING TO THE POOL DECK WHICH GIVES ACCESS TO STAIR
 3).PER FBC 1012.7 MAGNETIC LOCKS ARE NOT PERMISSABLE
 FOR REQUIRED EGRESS SERVING ASSEMBLY OCCUPANCIES.
 SPECIFY PANIC HARDWARE OR FIRE/EXIT HARDWARE FOR DOOR
 51.ALSO, EITHER SPECIFY PANIC HARDWARE OR FIRE/EXIT
 HARDWARE FOR DOOR 50, OR PROVIDE A SECOND DOOR FROM THE
 FITNESS CENTER TO THE EXIT ACCESS CORRIDOR.
  
 4) FBC 1012.1.2CLUB LOUNGE DOOR 66.THE DOOR TO THE
 EXIT ACCESS CORRIDOR IS SHOWN SWINGING INTO THE CLUB
 LOUNGE.THE DOOR SHALL OPEN IN THE DIRECTION OF
 EGRESS.AMEND THE PLANS.
  
 5) FBC 1012.7CLUB LOUNGE EGRESS DOORS.PER FBC
 1004.1.2 NOT LESS THAN TWO EGRESS DOORS ARE REQUIRED.
 THE DOOR SCHEDULE ON SHEET A-4.1 SPECIFIES MAGNETIC
 LOCKS (HARDWARE NOTE 9) FOR DOOR 66 AND DOOR 50
 (LEADING TO THE POOL DECK WHICH GIVES ACCESS TO STAIR
 3).PER FBC 1012.7 MAGNETIC LOCKS ARE NOT PERMISSABLE
 FOR REQUIRED EGRESS SERVING ASSEMBLY OCCUPANCIES.
 SPECIFY PANIC HARDWARE OR FIRE/EXIT HARDWARE FOR DOOR
 66 AND DOOR 50.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS