2007-02-11 17:34:08 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6652 |
| E-MAIL: [email protected] |
| |
| REVISION SUBMITTED 12/18/06 FOR CLUBROOM AND FITNESS |
| CENTER BUILDOUT. |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) FBC 704.1.2.3OCCUPANCY SEPARATION FOR FITNESS |
| CENTER AND CLUB LOUNGE.THE PLANS SHALL STATE THE |
| TOTAL AREA OF THE FITNESS CENTER AND TOTAL AREA OF THE |
| CLUB LOUNGE.PER FBC 304.1.2 THEY ARE CLASSIFIED AS |
| ASSEMBLY OCCUPANCY.IF THE AREA EXCEEDS 2,000 SQ FT, |
| THEY SHALL BE SEPARATED FROM THE RESIDENTIAL OCCUPANCY |
| BY 2 HOUR FIRE RESISTANT CONSTRUCTION.THE FITNESS |
| CENTER AND CLUB LOUNGE BOTH EXCEED 750 SQ FT SO, PER |
| FBC 704.1.2.2, THEY CANNOT BE CONSIDERED AS INCIDENTAL |
| TO THE RESIDENTIAL OCCPANCY.AMEND THE PLANS TO STATE |
| THE AREA OF THE FITNESS CENTER AND CLUB LOUNGE, AND |
| INCREASE THE OCCUPANCY SEPARATION FIRE RESISTANCE TO 2 |
| HOURS IF APPROPRIATE. |
| |
| 2) FBC 1012.1.2FITNESS CENTER DOOR 51.THE DOOR TO |
| THE EXIT ACCESS CORRIDOR IS SHOWN SWINGING INTO THE |
| FITNESS CENTER.THE DOOR SHALL OPEN IN THE DIRECTION |
| OF EGRESS.AMEND THE PLANS. |
| |
| 3) FBC 1012.7FITNESS CENTER EGRESS DOORS.PER FBC |
| 1004.1.2 NOT LESS THAN TWO EGRESS DOORS ARE REQUIRED. |
| THE DOOR SCHEDULE ON SHEET A-4.1 SPECIFIES MAGNETIC |
| LOCKS (HARDWARE NOTE 9) FOR DOOR 51 AND DOOR 50 |
| (LEADING TO THE POOL DECK WHICH GIVES ACCESS TO STAIR |
| 3).PER FBC 1012.7 MAGNETIC LOCKS ARE NOT PERMISSABLE |
| FOR REQUIRED EGRESS SERVING ASSEMBLY OCCUPANCIES. |
| SPECIFY PANIC HARDWARE OR FIRE/EXIT HARDWARE FOR DOOR |
| 51.ALSO, EITHER SPECIFY PANIC HARDWARE OR FIRE/EXIT |
| HARDWARE FOR DOOR 50, OR PROVIDE A SECOND DOOR FROM THE |
| FITNESS CENTER TO THE EXIT ACCESS CORRIDOR. |
| |
| 4) FBC 1012.1.2CLUB LOUNGE DOOR 66.THE DOOR TO THE |
| EXIT ACCESS CORRIDOR IS SHOWN SWINGING INTO THE CLUB |
| LOUNGE.THE DOOR SHALL OPEN IN THE DIRECTION OF |
| EGRESS.AMEND THE PLANS. |
| |
| 5) FBC 1012.7CLUB LOUNGE EGRESS DOORS.PER FBC |
| 1004.1.2 NOT LESS THAN TWO EGRESS DOORS ARE REQUIRED. |
| THE DOOR SCHEDULE ON SHEET A-4.1 SPECIFIES MAGNETIC |
| LOCKS (HARDWARE NOTE 9) FOR DOOR 66 AND DOOR 50 |
| (LEADING TO THE POOL DECK WHICH GIVES ACCESS TO STAIR |
| 3).PER FBC 1012.7 MAGNETIC LOCKS ARE NOT PERMISSABLE |
| FOR REQUIRED EGRESS SERVING ASSEMBLY OCCUPANCIES. |
| SPECIFY PANIC HARDWARE OR FIRE/EXIT HARDWARE FOR DOOR |
| 66 AND DOOR 50. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |