Plan Review Notes For Permit 05091425 |
Permit Number |
05091425 |
|
Review Stop |
M |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-02-09 08:56:54 | -----------------DENIED---------------- | | | | 1. PG AC-4: EF-29 MAY NOT DISCHARGE INTO SHAFT GE3. | | THIS SHOULD BE AN INDIPENDENT SYSTEM DISCHARGING | | DIRECTLY TO THE OUTDOORS PER FBC,M 501.2 AND 501.3. | | | | 2. PG AC-4: REVISION DELTA12 DATED 9/22/06 - I AM | | UNABLE TO DETERMINE ANY CHANGE FROM PREVIOUS PLAN. | | PLEASE CLARIFY. | | | | 3. PG AC-7: BASED ON REVISED ARCHITECTURAL PAGE A-2.4.5 | | DATED 11/17/06, THE DUCT SYSTEM FOR AC-14 HAS SEVERAL | | UNPROTECTED OPENINGS IN RATED WALLS. PLEASE SHOW HOW | | THESE OPENINGS WILL BE PROTECTED IN THE RATED | | ASSEMBLIES PER FBC,M 607.1.2. | | | | 4. PG AC-7: ELEVATOR LOBBY AND STORAGE HVAC PLAN - THIS | | AREA IS MARKED AS REVISION DELTA11 BUT IT DOES NOT | | APPERAR ON PG AC-7 DATED 2/24/06 WHERE DELTA 11 | | ORIGINATED. PLEASE CLARIFY. SAME CONDITION OCCURS ON PG | | AC-23 REGARDING THE ADDITION OF EF 13,14,15 TO | | SCHEDULE. | | | | 5. AC-7: ELEVATOR LOBBY SYSTEM AC-15 HAS SEVERAL | | UNPROTECTED OPENINGS WHERE DUCTS PENETRATE RATED WALLS | | AS SHOWN ON REVISED PAGE A-2.4.3. PLEASE SHOW HOW HESE | | OPENINGS WILL BE PROTECTED PER FBC,M 607.1.2. | | | | RONALD J REGUEIRO | | 561-805-6734 | | [email protected] |
|