Plan Review Notes
Plan Review Notes For Permit 05091425
Permit Number 05091425
Review Stop P
Sequence Number 4
Notes
Date Text
2007-01-23 07:21:32 
 REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P1 THE DRAINS FROM THE FIRE SPRINKLER SHALL BE
 INDIRECT WASTED AND REQUIRES A TRAP. SECTIONS 802.1.4 &
 901.2.1. A FLOOR SINK OR HUB DRAIN IS REQUIRED. (SEE
 REVISION 13 - REVISION STATES BLDG DEPT COMMENT. I
 BELIEVE THE COMMENT WAS THAT INDIRECT WASTE RECEPTORS
 ARE NOT ALLOWED IN THE STAIRWELL, NOT THAT THE WASTE
 RECEPTORS ARE NOT NEEDED. SEE PROVISO ON PLANS). PLEASE
 CLARIFY.
  
 2. SHT P-1 PLEASE TURN OFF ALL PREVIOUS REVISIONS AS
 THIS SLOWS THE REVISION PROCESS DOWN. ONLY INDICATE THE
 REVISIONS BE SUBMITTED AT THIS TIME ON THE PLANS.
 SECTION 104.2.1.-- THERE ARE CHANGES TO THE ROUTING
 OF THEWATER SUPPLY TO THE FIRE PUMP AS WELL AS A
 BYPASS THAT HAS NOT BEEN CLOUDED, NOR INDICATED AS A
 REVISION. CLOUD AND NUMBER ALL REVISIONS. - - MANY
 REVISIONS SHOWN HAVE NO CHANGES TO STAMPED SET OF
 PLANS. PLEASE CLARIFY. (SEE REVISIONS 10 & 12).
  
  
 **********APPROVED SHEETS**********
 P-2, P-3, P-4, P-5, AND NEW SHEET P-5A.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]