2006-08-26 00:00:00 | |
| |
| |
| |
| PASSED/PROVISO |
| |
| SHTS P-1 & P-22 FLOOR DRAINS ARE NOT |
| APPROVED IN THE STAIRWELLS. POSITIVE |
| PRESSURES CAUSED BY THE STAIRWELL |
| PRESSURIZATION MAY CONFLICT WITH SECTION |
| 901.2. ALSO PENETRATIONS IN AN EXIT |
| ENCLOSUER ASSEMBLY OTHER THAN THOSE |
| LIMITED TO NFPA 101 SECTION 7.1.3.2.1(5) |
| ARE NOT ALLOWED. - REVISIONS REQUIRED |
| FOR THESE SHEETS |
| |
| |
| |
| |
| GAS APPLIANCE VENTING SHALL BE FIELD |
| INSPECTED AND APPROVED. |
| MANUF. SPECIFICATION SHEETS SHALL BE |
| SUBMITTED AT THE TIME OF GAS PERMIT |
| APPLICATION. MANUF. SPECIFICATIONS |
| SHEETS REQUIRED FOR THE GAS REGULATORS. |
| VENTS FOR REGULATORS SHALL BE MADE OF |
| NON COMBUSTABLE MATERIAL. GAS RISER - A |
| SHUT OFF VALVE SHALL BE INSTALLED PRIOR |
| TO THE REGULATORS WITH A UNION BETWEEN |
| OR AFTER REGULATOR. (SHT P-6). SECTION |
| 410.2(5). REVISIONS REQUIRED FOR THESE |
| SHEETS. |
| |
| |
| |
| |
| SHTS P-4 & P-21A COOLING TOWER WATER |
| RISER DIAGRAM. THE CHECK VALVES TO THE |
| FOUNTAINS AND THE TRASH CHUTES ARE NOT |
| APPROVED. INSTALL N-36 VACUUM BREAKERS |
| FOR THIS APPLICATION. - THE IRRIGATION |
| SYSTEM REQUIRES A PRESSURE VACUUM |
| BREAKER TO THAT LINE SEPARATE FROM THE |
| REST OF THE SYSTEM. - CLARIFY WATER |
| PIPING TO POOL HEATERS AS THERE IS MAKE |
| UP WATER TO THE COLLECTING TANKS. - |
| REVISION REQUIRED FOR THESE SHEETS. |
| |
| |
| |
| |
| SEE PROVISO REQUIREMENTS FOR SHEETS P-1, |
| P-4, P-6, P-21A, & P-22. |
| |
| |