2006-08-23 00:00:00 | PROVISO: |
| RESPONSE TO COMMENT #3:ELEVATION |
| PROVIDED ON PLAN SHEET AC-5.PLEASE |
| NOTE, EXHAUST FROM EF-23 SHALL NOT |
| TERMINATE IN A MANNER THAT NOXIOUS |
| CONTAMINANTS MY BE DRAWN BACK INTO THE |
| FRESH AIR INTAKE (INTAKE LOUVER). |
| PLEASE PROVIDE CO SENSOR IN THIS ROOM. |
| |
| RESPONSE TO COMMENT #11: PLAN SHEET AC-4 |
| VENTLATION FOR THE POOL EQUIPMENT ROOM |
| #1 MAKE-UP AIR AND THE EXHAUST AIR WILL |
| BE INTO THE GARAGE.PLEASE PROVIDE CO |
| SENSOR IN THIS ROOM. |
| |
| PLAN SHEET AC-7 TERMINATION OF EF-12 IS |
| WITHIN 3FT THE POOL EQUIPMENT ROOM #2. |
| PER 2001 FMC 401.5 OPENING LOCATION FOR |
| EXHAUST AND INTAKES SHALL BE LOCATED A |
| MINIMUM OF 10 FT FROM BUILDINGS ON THE |
| SAME LOT. |
| |
| RESPONSE TO COMMENT #19:INIDCATES |
| GYPSUM BOARD OVER EXPOSED SURFACES OF |
| THE DOOR.THIS IS NOT ACCEPTABLE. |
| PLEASE PROVIDE SOLUTION / SUBMITTAL |
| WITHIN 60 DAYS OF THE PERMIT ISSUANCE. |
| |
| COMMENT 20:THE FOLLOWING RESIDENTIAL |
| HEAT PUMPS AC-7 & AC-8 ARE REQUIRED TO |
| HAVE FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| OR BY AREA SMOKE DETECTORS PER 2001 FMC |
| 606.2.1 & 606.4. |
| |