Plan Review Notes
Plan Review Notes For Permit 05091425
Permit Number 05091425
Review Stop M
Sequence Number 3
Notes
Date Text
2006-08-23 00:00:00PROVISO:
 RESPONSE TO COMMENT #3:ELEVATION
 PROVIDED ON PLAN SHEET AC-5.PLEASE
 NOTE, EXHAUST FROM EF-23 SHALL NOT
 TERMINATE IN A MANNER THAT NOXIOUS
 CONTAMINANTS MY BE DRAWN BACK INTO THE
 FRESH AIR INTAKE (INTAKE LOUVER).
 PLEASE PROVIDE CO SENSOR IN THIS ROOM.
  
 RESPONSE TO COMMENT #11: PLAN SHEET AC-4
 VENTLATION FOR THE POOL EQUIPMENT ROOM
 #1 MAKE-UP AIR AND THE EXHAUST AIR WILL
 BE INTO THE GARAGE.PLEASE PROVIDE CO
 SENSOR IN THIS ROOM.
  
 PLAN SHEET AC-7 TERMINATION OF EF-12 IS
 WITHIN 3FT THE POOL EQUIPMENT ROOM #2.
 PER 2001 FMC 401.5 OPENING LOCATION FOR
 EXHAUST AND INTAKES SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM BUILDINGS ON THE
 SAME LOT.
  
 RESPONSE TO COMMENT #19:INIDCATES
 GYPSUM BOARD OVER EXPOSED SURFACES OF
 THE DOOR.THIS IS NOT ACCEPTABLE.
 PLEASE PROVIDE SOLUTION / SUBMITTAL
 WITHIN 60 DAYS OF THE PERMIT ISSUANCE.
  
 COMMENT 20:THE FOLLOWING RESIDENTIAL
 HEAT PUMPS AC-7 & AC-8 ARE REQUIRED TO
 HAVE FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 OR BY AREA SMOKE DETECTORS PER 2001 FMC
 606.2.1 & 606.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.