Plan Review Notes
Plan Review Notes For Permit 05091425
Permit Number 05091425
Review Stop P
Sequence Number 2
Notes
Date Text
2006-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 FROM PREVIOUS REVIEW. COMMENT NUMBER
 SHALL REMAIN THE SAME AS FIRST REVIEW:
  
 4. SHTS A-1.7, A-1.8, A-2.6.1 THRU
 A-2.6.6, SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS FOR ALL ROOFS.
 SHOW THE LOCATION OF ALL SECONDARY ROOF
 DRAINS FOR ALL ROOFS/DECKS.
 ***RESPONSE NOTED, BUT SCUPPER SCHEDULE
 CALCULATIONS & ROOF DRAIN SF ARE
 DIFFERENT. PLEASE CORRELATE INFORMATION.
 SECTION 104.2.1.
 5. ALL UNIT TYPES SHALL COMPLY WITH
 FHA-98 DESIGN MANUAL REQUIREMENTS ONE
 THRU SEVEN. SUBMIT DETAILS.
 ***RESPONSE NOTED, BUT BATH #2 IN UNITS
 B-1, C-1, C-2, C-2.1, C-2.2, C-3, C-4,
 C-5, C-6, C-7, C-8, & D-1, AS WELL AS
 THE M/B OF UNITS C-9 & C-9.1. SHOW THE
 OPENING FOR THE W/C'S. OPENINGS SHALL BE
 A MINIMUM 33" WIDE WITH THE W/C BEING
 18" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE & 15" TO ADJACENT FIXTURE OR
 VANITY CABINET. W/C'S BETWEEN FIXTURES
 SHALL BE 18" OFF ONE FIXTURE AND 15" OFF
 THE OTHER WITH A MINIMUM 33" OPENING.
 SEE PAGES 7.43, 7.44 & 7.45. -
 REINFORCING FOR FOLDING GRAB BARS MUST
 BE SUBSTANTIAL BECAUSE OF THEIR
 CANTILEVERED DESIGN. 20 GAUGE SHEET
 METAL BACKING DOES NOT APPEAR TO BE
 SUBSTANTIAL. PLEASE INDICATE WITH
 CALCULATIONS HOW THIS WILL BE CONSIDERED
 SUBSTANTIAL. (SEE PAGE 28).
  
 9. SHTS A-2.7.5 & A-10.1 MORE
 INFORMATION IS REQUIRED FOR THE
 FOUNTAINS. PLEASE INDICATE IF THERE WILL
 BE WATER SUPPLY LINES AND OR DRAINAGE
 LINES FOR FOUNTAINS. IF WATER SUPPLY
 LINES ARE INSTALLED, BACKFLOW PREVENTION
 IS REQUIRED. IF DRAINS ARE INSTALLED,
 THEY SHALL CONNECT TO THE SANT. SYSTEM
 AND THE OVERFLOW SHALL DRAIN TO STORM.
 PLEASE CLARIFY. SECTIONS 104.2.1 & 608.
 ***RESPONSE NOTED, BUT NO BACKFLOW
 PREVENTORS ARE SHOWN ON PLANS. PLEASE
 INDICATE WHERE THESE CAN BE FOUND AS
 THERE IS NO WATER RISER DIAGRAM FOR THE
 COOLING TOWER WATER. PLEASE SUBMIT A
 WATER RISER DIAGRAM SHOWING ALL PIPE
 SIZE, VALVES, BACKFLOWS ETC. FOR THE
 COOLING TOWER SYSTEM. SECTION 104.3.1.1.
 - FOUNTAIN AT PORTE-COCHERE PLAZA TO BE
 BY SEPARATE PERMIT, BUT WILL THE DRAIN
 LINE, OVERFLOW LINE AND WATER SUPPLY TO
 THE FOUNTAIN BE RUN TO FOUNTAIN AT THAT
 TIME? SECTION 104.2.1.
  
 18. SHT P-4 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SF OF EACH DRAINED AREA PLUS 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS,
 PLUS THE AREA OF ROOFS THAT DRAIN ONTO
 THE ROOF/DECK AREA FROM ABOVE.
 ***RESPONSE NOTED, BUT P-6 SCUPPER
 SCHEDULE CALCULATIONS TOTAL AREA SERVED
 BY DRAIN ON SCHEDULE DOES NOT REFLECT
 THE TOTAL SHOWN ON SHT P-5 DECK DRAINS &
 PLANTER DRAINS. MANY TOTAL AREAS ARE NOT
 CORRECT. PLEASE RECHECK THE ADDITION.
 SECTION 104.2.1 AND TABLE 1106.3.
  
 22. SHT P-7 SUBMIT CALCULATION FOR
 PRIMARY AND SECONDARY ROOF DRAINS. (SEE
 COMMENT #18). SECTIONS 1106 & 1107.
 ***RESPONSE NOTED, BUT SCUPPER SCHEDULE
 CALCULATIONS TOTAL AREA SERVED BY DRAIN
 DOES NOT REFLECT SF ON ROOF PLAN. PLEASE
 CORRELATE INFORMATION. SECTION 104.2.1.
  
 33. SHT P-18 RISERS 86, 87, 81, 80 LOWER
 OFFSET VENTS REQUIRED. (SHOW AT LOWEST
 OFFSET) SECTION 915.3.
 ***RESPONSE NOTED, BUT THE LOWER OFFSET
 VENTS ARE STILL NOT SHOWN ON RISERS 80,
 81, AND 87A.
  
 36. THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT APPLICATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 ***RESPONSE NOTED, BUT THE ISOMETRIC
 INDICATES THE POOL/SPA HEATERS ARE ON
 THE 8TH FLOOR, BUT THE FLOOR PLAN SHOWS
 THE HEATERS ON THE 9TH FLOOR. PLEASE
 CORRELATE RISER WITH FLOOR PLAN. - SOME
 CUT SECTIONS SHOW NO LENGTH AS REQUIRED.
 SEE FROM THE METER TO THE FIRST RISER,
 THE OFFSET ON THE RUN TO THE WATER
 HEATERS, AND THE DROP TO THE WATER
 HEATERS IS NOT SHOWN.
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3)
 ***RESPONSE NOTED, BUT NOT ALL CUT
 SECTIONS ARE GIVEN TO VERIFY DEVELOPED
 LENGTH.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 ***RESPONSE NOTED, BUT NO VENTING
 INFORMATION INDICATED.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT MANUF.
 SPECIFICATION SHEETS FOR ALL GAS
 EQUIPMENT SHALL BE SUBMITTED FOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **************NEW COMMENTS**************
  
 1B. SHT A-2.7.5 MORE INFORMATION IS
 REQUIRED FOR THE SCUPPERS. SUBMIT A
 DETAIL INDICATING WHERE THE SCUPPER WILL
 BE PIPED TO. SHOW SCUPPER HEIGHT &
 WIDTH, AND INDICATE THE DISTANCE FROM
 THE DECK TO THE FLOW LINE. SHOW THE AREA
 TO BE DRAINED BY EACH EOS AND INDICATE
 THE SQUARE FOOTAGE BEING DRAINED BY EACH
 EOS. - INDICATE THE TERMINATION POINT
 FOR EACH EOS. SECTION 104.2.1.
  
 2B. EMERGENCY OVERFLOW SCUPPERS SHALL BE
 LOCATED AS CLOSE AS PRACTICABLE TO THE
 REQUIRED VERT LEADERS, AND SHALL BE A
 MINIMUM 4" IN HEIGHT. SECTION 1503.4.2.
  
 3B. SUBMIT A EMERGENCY OVERFLOW SCUPPER
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES. SECTION 1O3.1.1.
  
 3B. SHT P-1 RELIEF VENT REQUIRED FOR
 AAV'S, (STUDOR VENTS). SECTION 917.3.2.
  
 4B. SHT P-1 SANITARY RISERS 44A, & 51A
 ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 5B. SHT P-1 CONDENSATE LINE IS CONNECTED
 TO THE SANITARY BUILDING DRAIN BETWEEN
 RISERS 43 & 39. THIS IS NOT APPROVED.
 MUNICIPAL CODE SECTION 90-125(5).
  
 6B. SHT P-1 10 DD'S SHOWN AS RWL'S.
 PLEASE CORRELATE INFORMATION. SECTION
 104.2.1.
  
 7B. SHT P-2 RWL DESIGNATIONS COVERED UP
 BY RECTANGLE GRID REFERANCES AT COL.
 LINES 57.1-R.1, 57.1-N.1, 57.1-C.1 AND
 OVER A SANT. RISER DESIGNATION AT COL.
 LINE 57.1-B.2. PLEASE MOVE REFERENCES.
 SECTION 104.2.1.
  
 8B. SHT P-2 10 3" DD'S ARE SHOWN AS
 RWL'S. PLEASE CORRELATE INFORMATION.
 SECTION 104.2.1.
  
 9B. SHT P-2 6"RWL 3500SF UP & DOWN IS
 SHOWN AS 3200SF AT ROOF DRAIN. PLEASE
 CORRELATE INFORMATION. SECTION 104.2.1.
  
 10B. SHT P-3 3RD FLOOR AND 7TH FLOOR ARE
 DIFFERENT FROM FLOORS 4, 5, & 6 AND EACH
 OTHER, SO HOW CAN ALL FLOORS BE TYPICAL?
 PLEASE CLARIFY. SECTION 104.2.1.
  
 11B. SHT P-3 PLEASE INDICATE THE SQUARE
 FOOTAGE FOR ALL DECK DRAINS. SECTION
 104.2.1 AND TABLE 1106.3.
  
 12B. SHT P-36"RWL 3500SF UP & DOWN IS
 SHOWN AS 3200SF @ THE ROOF DRAIN. PLEASE
 CORRELATE INFORMATION. SECTION 104.2.1.
  
 13B. SHT P-4RWL'S INDICATED AS PD'S OR
 DD'S ON STORM RISERS. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 14B. SHT P-6 SCUPPER SCHEDULE
 CALCULATIONS, CHECK ADDITION OF SF ON
 AREAS 22, 62, 79, & 106. SECTION
 102.1.1.
  
 15B. SHT P-7 WHITE-OUT IS NOT APPROVED
 ON SIGNED/SEALED SETS OF PLANS SUBMITTED
 FOR RECORD. SECTION 104.2.1.3.
  
 16B. SHT P-7 SUBMIT A WATER RISER
 DIAGRAM ISOMETRIC FOR PIPING IN BOILER
 ROOM THAT REFLECTS THE LAYOUT ON THE
 FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES,
 VACUUM RELIEF VALVES, CIRCULATION PUMPS,
 THERMAL EXPANSION CONTROL, THERMOMETERS,
 ETC. FOR THE DOMESTIC WATER HEATER &
 STORAGE TANK. SECTION 104.3.1.1.
  
 17B. SHT P-7 BOILER ROOM DETAIL THE COLD
 WATER SUPPLY APPEARS TO BE PASSING THRU
 THE HOT WATER STORAGE TANK. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 18B. SHT P-13 PLEASE INDICATE WHAT IS AT
 THE TOP OF ALL COLD WATER RISERS. NO
 REFERENCE SYMBOL IS SHOWN ON SHT P-2
 PLUMBING LEGEND. IF THEY ARE AIR
 CHAMBERS, THEY ARE NOT APPROVED.
 SECTIONS 104.2.1, 604.9, & PDI-WH 201.
  
 19B. SHT P-16 RISER 44A/51A MAXIMUM 20
 FIXTURE UNITS ON 4" STACK PER TABLE
 912.3.
  
 20B. SHT P-17 RISERS 52A, & 84AARE NOT
 FOUND ON THE HORIZONTAL BUILDING
 SANITARY DRAIN ISOMETRIC RISER DIAGRAM.
 SHTP-22. PLEASE CLARIFY. SECTION
 104.2.1.
  
 21B. SHT P-18 RISER 87A NOT FOUND ON THE
 HORIZONTAL BUILDING SANITARY DRAIN
 ISOMETRIC RISER DIAGRAM. SHT P-22 PLEASE
 CLARIFY. SECTION 104.2.1.
  
 22B. SHT P-19 RISER 34/57 SHOWS NO
 CONNECTION TO STACK FOR FLOORS 15, 17, &
 19. PLEASE CLARIFY. SECTION 104.2.1.
  
 23B. SHT P-20 SPRINKLER DRAIN DETAIL. A
 TRAP AND A VENT ARE REQUIRED FOR THIS
 LINE. SECTIONS 901.2.1. & 1002.1.
  
 24B. SHT P-22 HORIZONTAL SANITARY RISER
 DOES NOT REFLECT THE FLOOR PLAN. NO
 DRAIN LINES FOR THE FIRE SPRINKLER
 DRAINS. - FUTURE LINE, (4" 20FU),
 UPSTREAM OF RISER 68,69,70,72,73,74 NOT
 SHOWN. - FLOOR DRAIN UPSTREAM OF RISER
 59-67 & 71 NOT SHOWN. - OFFSET FOR RISER
 6 NOT SHOWN. - 2ND FLOOR OFFSET FOR
 RISER 22-26, 33-36, & 41 NOT SHOWN.
 SECTION 104.2.1.
  
 25B. SHT P-22 RELIEF VENTS REQUIRED FOR
 ALL AAV'S, (STUDOR VENTS). SECTION
 917.3.2.
  
 26B. SHT P-22 SHOW THE VENT PIPING FOR
 ALL FUTURE LINES SHOWING ALL PIPE SIZES,
 AND INDICATE WHICH STACK THE VENTS
 CONNECT INTO. SECTION 104.2.1 AND TABLE
 916.1.
  
 27B. SHT P-22 RECHECK ALL DFU'S ADDITION
 IN SANITARY RISER. SOME ADDITION IS NOT
 CORRECT AND THIS AFFECT THE PIPE SIZING
 IN SOME CASES. (SEE RED LINE CORRECTIONS
 ON ONE SET OF PLANS. SECTION 104.2.1 AND
 TABLE 710.1(1). (NOTE: BATHROOM GROUP
 CONSISTING OF W/C, LAV, BIDET, AND TUB
 OR SHOWER IS 5FU, AND WITH AN EXTRA LAV
 AND SHOWER IS 8FU. - SOME RISERS APPEAR
 TO INDICATE MORE FIXTURE UNITS THAN ARE
 ACTUALLY SHOWN. - TRAPS FOR FIXTURES
 OVER 2" SHALL BE SIZED PER TABLE 709.2.
 (EXAMPLE: 3" FLOOR DRAIN IS 5FU).
  
 28B. SHT P-22 RISER 22,23,24 DOES NOT
 SHOW PIPING FROM POOL EQUIPMENT ROOM,
 NOR FROM THE 2 FOUNTAINS AS INDICATED ON
 SHT P-3. PLEASE CORRELATE. SECTION
 104.2.1.
  
 29B. SHT P-22 SHOW THE CLEANOUTS WHERE
 REQUIRED PER SECTIONS 708.3.1, 708.3.3 &
 708.3.5. (ALSO SHOW ON SHT P-1).
  
 30B. SHT P-22 SHOW TRAPS AND VENTING FOR
 THE FIRE SPRINKLER DRAIN LINES AS
 REQUIRED IN SECTIONS 901.2.1 & 1002.1.
  
 31B. SHT P-23 STORM RISER DIAGRAM, SHOW
 SF DRAINED BY EACH DD. - 4" RD(2000SF)
 DOES NOT REFLECT THE ROOF PLAN, NOR
 CALCULATIONS (1900SF). - 6" DD (4350SF)
 DOES NOT REFLECT 9TH FLOOR PLAN. (SHTS
 P-1 & P-3 4450SF) PLEASE CORRELATE
 SECTION 104.2.1. - CLEANOUTS REQUIRED
 PER SECTION 1101.8. (ALSO SHOW ON SHT
 P-1.
  
 32B. SHT P-23A STORM RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. FOUNTAIN
 OVERFLOWS ARE NOT SHOWN. - OFFSET ON THE
 9TH FLOOR FOR ROOF DRAIN 3200SF IS SHOWN
 ON THE 8TH FLOOR ON THE FLOOR PLAN. -
 SHOME SF FOR SOME DRAINS DO NOT REFLECT
 THE FLOOR PLAN AND/OR CALCULATIONS.
 PLEASE CORRELATE. - NO SF SHOWN FOR MANY
 DD'S AND CAN NOT VERIFY PIPE SIZE UNTIL
 SF FOR ALL DD'S IS SHOWN. SECTION
 104.2.1 AND TABLE 1106.3.
  
 33B. SHT P-32A CLEANOUTS REQUIRED PER
 SECTION 1101.8 SHALL BE SHOWN. (ALSO ON
 SHT P-1).
  
 34B. BACKFLOW PREVENTION REQUIRED FOR
 IRRIGATION ON THE 9TH FLOOR. SECTION
 608.13.
  
 35B. A SEPARATE RPZV BACKFLOW IS
 REQUIRED FOR THE COOLING TOWER WATER
 SUPPLY LINE. (NOT SHOWN ON CIVIL SHEETS)
  
 36B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONALS AND FS 53.80(2)(B).
 THIS IS GIVEN AS A NOTICE ONLY.
  
 REVIEW BY KEN STEVENS