2006-06-28 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 BUILDING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| WPB CITY CODE |
| |
| FROM PREVIOUS REVIEW. COMMENT NUMBER |
| SHALL REMAIN THE SAME AS FIRST REVIEW: |
| |
| 4. SHTS A-1.7, A-1.8, A-2.6.1 THRU |
| A-2.6.6, SUBMIT CALCULATIONS FOR PRIMARY |
| AND SECONDARY ROOF DRAINS FOR ALL ROOFS. |
| SHOW THE LOCATION OF ALL SECONDARY ROOF |
| DRAINS FOR ALL ROOFS/DECKS. |
| ***RESPONSE NOTED, BUT SCUPPER SCHEDULE |
| CALCULATIONS & ROOF DRAIN SF ARE |
| DIFFERENT. PLEASE CORRELATE INFORMATION. |
| SECTION 104.2.1. |
| 5. ALL UNIT TYPES SHALL COMPLY WITH |
| FHA-98 DESIGN MANUAL REQUIREMENTS ONE |
| THRU SEVEN. SUBMIT DETAILS. |
| ***RESPONSE NOTED, BUT BATH #2 IN UNITS |
| B-1, C-1, C-2, C-2.1, C-2.2, C-3, C-4, |
| C-5, C-6, C-7, C-8, & D-1, AS WELL AS |
| THE M/B OF UNITS C-9 & C-9.1. SHOW THE |
| OPENING FOR THE W/C'S. OPENINGS SHALL BE |
| A MINIMUM 33" WIDE WITH THE W/C BEING |
| 18" OFF THE WALL TO THE CENTERLINE OF |
| THE FIXTURE & 15" TO ADJACENT FIXTURE OR |
| VANITY CABINET. W/C'S BETWEEN FIXTURES |
| SHALL BE 18" OFF ONE FIXTURE AND 15" OFF |
| THE OTHER WITH A MINIMUM 33" OPENING. |
| SEE PAGES 7.43, 7.44 & 7.45. - |
| REINFORCING FOR FOLDING GRAB BARS MUST |
| BE SUBSTANTIAL BECAUSE OF THEIR |
| CANTILEVERED DESIGN. 20 GAUGE SHEET |
| METAL BACKING DOES NOT APPEAR TO BE |
| SUBSTANTIAL. PLEASE INDICATE WITH |
| CALCULATIONS HOW THIS WILL BE CONSIDERED |
| SUBSTANTIAL. (SEE PAGE 28). |
| |
| 9. SHTS A-2.7.5 & A-10.1 MORE |
| INFORMATION IS REQUIRED FOR THE |
| FOUNTAINS. PLEASE INDICATE IF THERE WILL |
| BE WATER SUPPLY LINES AND OR DRAINAGE |
| LINES FOR FOUNTAINS. IF WATER SUPPLY |
| LINES ARE INSTALLED, BACKFLOW PREVENTION |
| IS REQUIRED. IF DRAINS ARE INSTALLED, |
| THEY SHALL CONNECT TO THE SANT. SYSTEM |
| AND THE OVERFLOW SHALL DRAIN TO STORM. |
| PLEASE CLARIFY. SECTIONS 104.2.1 & 608. |
| ***RESPONSE NOTED, BUT NO BACKFLOW |
| PREVENTORS ARE SHOWN ON PLANS. PLEASE |
| INDICATE WHERE THESE CAN BE FOUND AS |
| THERE IS NO WATER RISER DIAGRAM FOR THE |
| COOLING TOWER WATER. PLEASE SUBMIT A |
| WATER RISER DIAGRAM SHOWING ALL PIPE |
| SIZE, VALVES, BACKFLOWS ETC. FOR THE |
| COOLING TOWER SYSTEM. SECTION 104.3.1.1. |
| - FOUNTAIN AT PORTE-COCHERE PLAZA TO BE |
| BY SEPARATE PERMIT, BUT WILL THE DRAIN |
| LINE, OVERFLOW LINE AND WATER SUPPLY TO |
| THE FOUNTAIN BE RUN TO FOUNTAIN AT THAT |
| TIME? SECTION 104.2.1. |
| |
| 18. SHT P-4 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| SF OF EACH DRAINED AREA PLUS 1/2 AREA OF |
| ALL VERTICAL WALLS INCLUDING PARAPETS, |
| PLUS THE AREA OF ROOFS THAT DRAIN ONTO |
| THE ROOF/DECK AREA FROM ABOVE. |
| ***RESPONSE NOTED, BUT P-6 SCUPPER |
| SCHEDULE CALCULATIONS TOTAL AREA SERVED |
| BY DRAIN ON SCHEDULE DOES NOT REFLECT |
| THE TOTAL SHOWN ON SHT P-5 DECK DRAINS & |
| PLANTER DRAINS. MANY TOTAL AREAS ARE NOT |
| CORRECT. PLEASE RECHECK THE ADDITION. |
| SECTION 104.2.1 AND TABLE 1106.3. |
| |
| 22. SHT P-7 SUBMIT CALCULATION FOR |
| PRIMARY AND SECONDARY ROOF DRAINS. (SEE |
| COMMENT #18). SECTIONS 1106 & 1107. |
| ***RESPONSE NOTED, BUT SCUPPER SCHEDULE |
| CALCULATIONS TOTAL AREA SERVED BY DRAIN |
| DOES NOT REFLECT SF ON ROOF PLAN. PLEASE |
| CORRELATE INFORMATION. SECTION 104.2.1. |
| |
| 33. SHT P-18 RISERS 86, 87, 81, 80 LOWER |
| OFFSET VENTS REQUIRED. (SHOW AT LOWEST |
| OFFSET) SECTION 915.3. |
| ***RESPONSE NOTED, BUT THE LOWER OFFSET |
| VENTS ARE STILL NOT SHOWN ON RISERS 80, |
| 81, AND 87A. |
| |
| 36. THE FOLLOWING INFORMATION IS |
| REQUIRED FOR GAS PERMIT APPLICATION: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| ***RESPONSE NOTED, BUT THE ISOMETRIC |
| INDICATES THE POOL/SPA HEATERS ARE ON |
| THE 8TH FLOOR, BUT THE FLOOR PLAN SHOWS |
| THE HEATERS ON THE 9TH FLOOR. PLEASE |
| CORRELATE RISER WITH FLOOR PLAN. - SOME |
| CUT SECTIONS SHOW NO LENGTH AS REQUIRED. |
| SEE FROM THE METER TO THE FIRST RISER, |
| THE OFFSET ON THE RUN TO THE WATER |
| HEATERS, AND THE DROP TO THE WATER |
| HEATERS IS NOT SHOWN. |
| |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3) |
| ***RESPONSE NOTED, BUT NOT ALL CUT |
| SECTIONS ARE GIVEN TO VERIFY DEVELOPED |
| LENGTH. |
| |
| H. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| ***RESPONSE NOTED, BUT NO VENTING |
| INFORMATION INDICATED. |
| |
| I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2. |
| ***RESPONSE NOTED, BUT MANUF. |
| SPECIFICATION SHEETS FOR ALL GAS |
| EQUIPMENT SHALL BE SUBMITTED FOR REVIEW. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| **************NEW COMMENTS************** |
| |
| 1B. SHT A-2.7.5 MORE INFORMATION IS |
| REQUIRED FOR THE SCUPPERS. SUBMIT A |
| DETAIL INDICATING WHERE THE SCUPPER WILL |
| BE PIPED TO. SHOW SCUPPER HEIGHT & |
| WIDTH, AND INDICATE THE DISTANCE FROM |
| THE DECK TO THE FLOW LINE. SHOW THE AREA |
| TO BE DRAINED BY EACH EOS AND INDICATE |
| THE SQUARE FOOTAGE BEING DRAINED BY EACH |
| EOS. - INDICATE THE TERMINATION POINT |
| FOR EACH EOS. SECTION 104.2.1. |
| |
| 2B. EMERGENCY OVERFLOW SCUPPERS SHALL BE |
| LOCATED AS CLOSE AS PRACTICABLE TO THE |
| REQUIRED VERT LEADERS, AND SHALL BE A |
| MINIMUM 4" IN HEIGHT. SECTION 1503.4.2. |
| |
| 3B. SUBMIT A EMERGENCY OVERFLOW SCUPPER |
| ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE |
| SIZES. SECTION 1O3.1.1. |
| |
| 3B. SHT P-1 RELIEF VENT REQUIRED FOR |
| AAV'S, (STUDOR VENTS). SECTION 917.3.2. |
| |
| 4B. SHT P-1 SANITARY RISERS 44A, & 51A |
| ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE |
| CLARIFY. SECTION 104.2.1. |
| |
| 5B. SHT P-1 CONDENSATE LINE IS CONNECTED |
| TO THE SANITARY BUILDING DRAIN BETWEEN |
| RISERS 43 & 39. THIS IS NOT APPROVED. |
| MUNICIPAL CODE SECTION 90-125(5). |
| |
| 6B. SHT P-1 10 DD'S SHOWN AS RWL'S. |
| PLEASE CORRELATE INFORMATION. SECTION |
| 104.2.1. |
| |
| 7B. SHT P-2 RWL DESIGNATIONS COVERED UP |
| BY RECTANGLE GRID REFERANCES AT COL. |
| LINES 57.1-R.1, 57.1-N.1, 57.1-C.1 AND |
| OVER A SANT. RISER DESIGNATION AT COL. |
| LINE 57.1-B.2. PLEASE MOVE REFERENCES. |
| SECTION 104.2.1. |
| |
| 8B. SHT P-2 10 3" DD'S ARE SHOWN AS |
| RWL'S. PLEASE CORRELATE INFORMATION. |
| SECTION 104.2.1. |
| |
| 9B. SHT P-2 6"RWL 3500SF UP & DOWN IS |
| SHOWN AS 3200SF AT ROOF DRAIN. PLEASE |
| CORRELATE INFORMATION. SECTION 104.2.1. |
| |
| 10B. SHT P-3 3RD FLOOR AND 7TH FLOOR ARE |
| DIFFERENT FROM FLOORS 4, 5, & 6 AND EACH |
| OTHER, SO HOW CAN ALL FLOORS BE TYPICAL? |
| PLEASE CLARIFY. SECTION 104.2.1. |
| |
| 11B. SHT P-3 PLEASE INDICATE THE SQUARE |
| FOOTAGE FOR ALL DECK DRAINS. SECTION |
| 104.2.1 AND TABLE 1106.3. |
| |
| 12B. SHT P-36"RWL 3500SF UP & DOWN IS |
| SHOWN AS 3200SF @ THE ROOF DRAIN. PLEASE |
| CORRELATE INFORMATION. SECTION 104.2.1. |
| |
| 13B. SHT P-4RWL'S INDICATED AS PD'S OR |
| DD'S ON STORM RISERS. PLEASE CLARIFY. |
| SECTION 104.2.1. |
| |
| 14B. SHT P-6 SCUPPER SCHEDULE |
| CALCULATIONS, CHECK ADDITION OF SF ON |
| AREAS 22, 62, 79, & 106. SECTION |
| 102.1.1. |
| |
| 15B. SHT P-7 WHITE-OUT IS NOT APPROVED |
| ON SIGNED/SEALED SETS OF PLANS SUBMITTED |
| FOR RECORD. SECTION 104.2.1.3. |
| |
| 16B. SHT P-7 SUBMIT A WATER RISER |
| DIAGRAM ISOMETRIC FOR PIPING IN BOILER |
| ROOM THAT REFLECTS THE LAYOUT ON THE |
| FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES, |
| VACUUM RELIEF VALVES, CIRCULATION PUMPS, |
| THERMAL EXPANSION CONTROL, THERMOMETERS, |
| ETC. FOR THE DOMESTIC WATER HEATER & |
| STORAGE TANK. SECTION 104.3.1.1. |
| |
| 17B. SHT P-7 BOILER ROOM DETAIL THE COLD |
| WATER SUPPLY APPEARS TO BE PASSING THRU |
| THE HOT WATER STORAGE TANK. PLEASE |
| CLARIFY. SECTION 104.2.1. |
| |
| 18B. SHT P-13 PLEASE INDICATE WHAT IS AT |
| THE TOP OF ALL COLD WATER RISERS. NO |
| REFERENCE SYMBOL IS SHOWN ON SHT P-2 |
| PLUMBING LEGEND. IF THEY ARE AIR |
| CHAMBERS, THEY ARE NOT APPROVED. |
| SECTIONS 104.2.1, 604.9, & PDI-WH 201. |
| |
| 19B. SHT P-16 RISER 44A/51A MAXIMUM 20 |
| FIXTURE UNITS ON 4" STACK PER TABLE |
| 912.3. |
| |
| 20B. SHT P-17 RISERS 52A, & 84AARE NOT |
| FOUND ON THE HORIZONTAL BUILDING |
| SANITARY DRAIN ISOMETRIC RISER DIAGRAM. |
| SHTP-22. PLEASE CLARIFY. SECTION |
| 104.2.1. |
| |
| 21B. SHT P-18 RISER 87A NOT FOUND ON THE |
| HORIZONTAL BUILDING SANITARY DRAIN |
| ISOMETRIC RISER DIAGRAM. SHT P-22 PLEASE |
| CLARIFY. SECTION 104.2.1. |
| |
| 22B. SHT P-19 RISER 34/57 SHOWS NO |
| CONNECTION TO STACK FOR FLOORS 15, 17, & |
| 19. PLEASE CLARIFY. SECTION 104.2.1. |
| |
| 23B. SHT P-20 SPRINKLER DRAIN DETAIL. A |
| TRAP AND A VENT ARE REQUIRED FOR THIS |
| LINE. SECTIONS 901.2.1. & 1002.1. |
| |
| 24B. SHT P-22 HORIZONTAL SANITARY RISER |
| DOES NOT REFLECT THE FLOOR PLAN. NO |
| DRAIN LINES FOR THE FIRE SPRINKLER |
| DRAINS. - FUTURE LINE, (4" 20FU), |
| UPSTREAM OF RISER 68,69,70,72,73,74 NOT |
| SHOWN. - FLOOR DRAIN UPSTREAM OF RISER |
| 59-67 & 71 NOT SHOWN. - OFFSET FOR RISER |
| 6 NOT SHOWN. - 2ND FLOOR OFFSET FOR |
| RISER 22-26, 33-36, & 41 NOT SHOWN. |
| SECTION 104.2.1. |
| |
| 25B. SHT P-22 RELIEF VENTS REQUIRED FOR |
| ALL AAV'S, (STUDOR VENTS). SECTION |
| 917.3.2. |
| |
| 26B. SHT P-22 SHOW THE VENT PIPING FOR |
| ALL FUTURE LINES SHOWING ALL PIPE SIZES, |
| AND INDICATE WHICH STACK THE VENTS |
| CONNECT INTO. SECTION 104.2.1 AND TABLE |
| 916.1. |
| |
| 27B. SHT P-22 RECHECK ALL DFU'S ADDITION |
| IN SANITARY RISER. SOME ADDITION IS NOT |
| CORRECT AND THIS AFFECT THE PIPE SIZING |
| IN SOME CASES. (SEE RED LINE CORRECTIONS |
| ON ONE SET OF PLANS. SECTION 104.2.1 AND |
| TABLE 710.1(1). (NOTE: BATHROOM GROUP |
| CONSISTING OF W/C, LAV, BIDET, AND TUB |
| OR SHOWER IS 5FU, AND WITH AN EXTRA LAV |
| AND SHOWER IS 8FU. - SOME RISERS APPEAR |
| TO INDICATE MORE FIXTURE UNITS THAN ARE |
| ACTUALLY SHOWN. - TRAPS FOR FIXTURES |
| OVER 2" SHALL BE SIZED PER TABLE 709.2. |
| (EXAMPLE: 3" FLOOR DRAIN IS 5FU). |
| |
| 28B. SHT P-22 RISER 22,23,24 DOES NOT |
| SHOW PIPING FROM POOL EQUIPMENT ROOM, |
| NOR FROM THE 2 FOUNTAINS AS INDICATED ON |
| SHT P-3. PLEASE CORRELATE. SECTION |
| 104.2.1. |
| |
| 29B. SHT P-22 SHOW THE CLEANOUTS WHERE |
| REQUIRED PER SECTIONS 708.3.1, 708.3.3 & |
| 708.3.5. (ALSO SHOW ON SHT P-1). |
| |
| 30B. SHT P-22 SHOW TRAPS AND VENTING FOR |
| THE FIRE SPRINKLER DRAIN LINES AS |
| REQUIRED IN SECTIONS 901.2.1 & 1002.1. |
| |
| 31B. SHT P-23 STORM RISER DIAGRAM, SHOW |
| SF DRAINED BY EACH DD. - 4" RD(2000SF) |
| DOES NOT REFLECT THE ROOF PLAN, NOR |
| CALCULATIONS (1900SF). - 6" DD (4350SF) |
| DOES NOT REFLECT 9TH FLOOR PLAN. (SHTS |
| P-1 & P-3 4450SF) PLEASE CORRELATE |
| SECTION 104.2.1. - CLEANOUTS REQUIRED |
| PER SECTION 1101.8. (ALSO SHOW ON SHT |
| P-1. |
| |
| 32B. SHT P-23A STORM RISER DIAGRAM DOES |
| NOT REFLECT THE FLOOR PLAN. FOUNTAIN |
| OVERFLOWS ARE NOT SHOWN. - OFFSET ON THE |
| 9TH FLOOR FOR ROOF DRAIN 3200SF IS SHOWN |
| ON THE 8TH FLOOR ON THE FLOOR PLAN. - |
| SHOME SF FOR SOME DRAINS DO NOT REFLECT |
| THE FLOOR PLAN AND/OR CALCULATIONS. |
| PLEASE CORRELATE. - NO SF SHOWN FOR MANY |
| DD'S AND CAN NOT VERIFY PIPE SIZE UNTIL |
| SF FOR ALL DD'S IS SHOWN. SECTION |
| 104.2.1 AND TABLE 1106.3. |
| |
| 33B. SHT P-32A CLEANOUTS REQUIRED PER |
| SECTION 1101.8 SHALL BE SHOWN. (ALSO ON |
| SHT P-1). |
| |
| 34B. BACKFLOW PREVENTION REQUIRED FOR |
| IRRIGATION ON THE 9TH FLOOR. SECTION |
| 608.13. |
| |
| 35B. A SEPARATE RPZV BACKFLOW IS |
| REQUIRED FOR THE COOLING TOWER WATER |
| SUPPLY LINE. (NOT SHOWN ON CIVIL SHEETS) |
| |
| 36B. SEE ATTACHED SHEET CONCERNING THE |
| DESIGN PROFESSIONALS AND FS 53.80(2)(B). |
| THIS IS GIVEN AS A NOTICE ONLY. |
| |
| REVIEW BY KEN STEVENS |