2006-07-06 00:00:00 | |
| RESPONSE TO COMMENTS FROM REVIEW DATED |
| 12/28/05 |
| |
| COMMENT #1 - OK |
| COMMENT #2 - OK (SEE COMMENT #3) |
| |
| COMMENT #3 - REPONSE INDICATES SHEET |
| AC-5 PROVIDES MUFFLER ELEVATION.PLAN |
| ONLY INDICATES MUFFLER EXHAUST TO |
| TERMINATE A MINIMUM OF 10 FT FROM O/A |
| INTAKES.PLEASE PROVIDE ELEVATION FROM |
| THE ADJOINGING GRADE LEVEL.PLEASE |
| NOTE, MUFFLER AND EF-23 EXHAUST |
| TERMINATIONS ARE WITHIN 10 FT OF THE |
| FRESH AIR INTAKE TO THE GENERATOR ROOM. |
| |
| COMMENT #4 - OK - PLEASE PROVIDE |
| INFORMATION ON WHAT WILL BE STORED IN |
| THE JANITOR CLOSET #1. |
| |
| COMMENT #5 - OK FOR THE COMMON AREAS |
| ONLY.PLEASE PROVIDE O/A CALCULATIONS |
| FOR THE RESIDENCE IN ACCORDANCE WITH |
| 2001 FBC 403.3, VENTILATION SYSTEMS FOR |
| OTHER THAN R-E (ONE & TWO FAMILY |
| DWELLINGS), SHALL BE DESIGNED TO HAVE |
| THE CAPACITY TO SUPPLY THE MINIMUM |
| OUTDOOR AIR FLOW RATE DETERMINED IN |
| ACCORDANCE WITH TABLE 403.3. |
| |
| COMMENT #6 - OK |
| COMMENT #7 - OK |
| COMMENT #8 - OK |
| COMMENT #9 - OK |
| COMMENT #10 - PLAN SHEET AC-14 UNIT C-5, |
| PLEASE NOTE, RETURN AIR TO BE EQUAL TO |
| SUPPLY INTO THAT AREA.R/A SHALL BE A |
| MINIMUM OF 8". |
| |
| COMMENT #11 - PLAN SHEET AC-4 |
| VENTILATION FOR THE POOL EXHAUST AND AIR |
| MAKE-UP ARE TERMINATING IN THE ENCLOSED |
| GARAGE.GARAGE VENTILATION IS NOT |
| CONTINUOUS, THEREFORE HOW WILL THIS |
| APPLICATION PROVIDE FRESH AIR INTO THIS |
| ROOM.PLAN SHEET AC-7 THE POOL |
| EQUIPMENT ROOM LOUVERED DOOR APPEARS TO |
| BE WITHIN 3FT OF THE TERMINATION OF |
| EF-12.PLEASE INDICATE WHAT CHEMICALS & |
| THE AMOUNT THAT WILL BE STORED IN WHICH |
| EQUIPMENT ROOM. |
| |
| COMMENT #12 - OK, PLEASE NOTE, RESPONSE |
| INDICATES COMBUSTION AIR CALCULATIONS |
| ARE INDICATED ON PLAN SHEET AC-9 & |
| AC-11.THERE ARE NO COMBUSTION AIR |
| CALCS ON AC-9 BUT AC-7 INSTEAD. |
| |
| COMMENT #13 - OK, SEE COMMENT 12. |
| |
| COMMENT #14 - OK |
| COMMENT #15 - PLAN SHEET AC-29, PROPOSED |
| SMOKE CONTROL SYSTEM.PLEASE INDICATE |
| WHICH METHOD IS INTEND TO BE UTILIZED |
| UNDER 2001 FBC 412.5 ITEMS 1, 2, 3 OR 4. |
| SHOULD SUBMITTAL BE UNDER ITEM 4, THIS |
| MUST BE SUBMITTED TO THE BUILDING |
| OFFICAL, NEIL MELICK.PLEASE PROVIDE |
| ALL SUPPORTING DOCUMENTATION. |
| |
| COMMENT #16 - OK |
| COMMENT #17 - OK |
| COMMENT #18 - OK |
| **************************************** |
| NEW COMMENT |
| 19. PLAN SHEET A-4.1 - THE DOOR SCHEDULE |
| INDICATES THE A/C CLOSET DOOR IN THE |
| APARTMENTS ARE TO BE WOOD.PLEASE |
| VERIFY WITH THE DOOR MANUFACTURER IF |
| THIS MEETS THE CRITERIA FOR A NON |
| COMBUSTIBLE DOOR AS REQUIRED IN 2001 FMC |
| 602.2.1. |
| |