Plan Review Notes
Plan Review Notes For Permit 05091425
Permit Number 05091425
Review Stop M
Sequence Number 2
Notes
Date Text
2006-07-06 00:00:00 
 RESPONSE TO COMMENTS FROM REVIEW DATED
 12/28/05
  
 COMMENT #1 - OK
 COMMENT #2 - OK (SEE COMMENT #3)
  
 COMMENT #3 - REPONSE INDICATES SHEET
 AC-5 PROVIDES MUFFLER ELEVATION.PLAN
 ONLY INDICATES MUFFLER EXHAUST TO
 TERMINATE A MINIMUM OF 10 FT FROM O/A
 INTAKES.PLEASE PROVIDE ELEVATION FROM
 THE ADJOINGING GRADE LEVEL.PLEASE
 NOTE, MUFFLER AND EF-23 EXHAUST
 TERMINATIONS ARE WITHIN 10 FT OF THE
 FRESH AIR INTAKE TO THE GENERATOR ROOM.
  
 COMMENT #4 - OK - PLEASE PROVIDE
 INFORMATION ON WHAT WILL BE STORED IN
 THE JANITOR CLOSET #1.
  
 COMMENT #5 - OK FOR THE COMMON AREAS
 ONLY.PLEASE PROVIDE O/A CALCULATIONS
 FOR THE RESIDENCE IN ACCORDANCE WITH
 2001 FBC 403.3, VENTILATION SYSTEMS FOR
 OTHER THAN R-E (ONE & TWO FAMILY
 DWELLINGS), SHALL BE DESIGNED TO HAVE
 THE CAPACITY TO SUPPLY THE MINIMUM
 OUTDOOR AIR FLOW RATE DETERMINED IN
 ACCORDANCE WITH TABLE 403.3.
  
 COMMENT #6 - OK
 COMMENT #7 - OK
 COMMENT #8 - OK
 COMMENT #9 - OK
 COMMENT #10 - PLAN SHEET AC-14 UNIT C-5,
 PLEASE NOTE, RETURN AIR TO BE EQUAL TO
 SUPPLY INTO THAT AREA.R/A SHALL BE A
 MINIMUM OF 8".
  
 COMMENT #11 - PLAN SHEET AC-4
 VENTILATION FOR THE POOL EXHAUST AND AIR
 MAKE-UP ARE TERMINATING IN THE ENCLOSED
 GARAGE.GARAGE VENTILATION IS NOT
 CONTINUOUS, THEREFORE HOW WILL THIS
 APPLICATION PROVIDE FRESH AIR INTO THIS
 ROOM.PLAN SHEET AC-7 THE POOL
 EQUIPMENT ROOM LOUVERED DOOR APPEARS TO
 BE WITHIN 3FT OF THE TERMINATION OF
 EF-12.PLEASE INDICATE WHAT CHEMICALS &
 THE AMOUNT THAT WILL BE STORED IN WHICH
 EQUIPMENT ROOM.
  
 COMMENT #12 - OK, PLEASE NOTE, RESPONSE
 INDICATES COMBUSTION AIR CALCULATIONS
 ARE INDICATED ON PLAN SHEET AC-9 &
 AC-11.THERE ARE NO COMBUSTION AIR
 CALCS ON AC-9 BUT AC-7 INSTEAD.
  
 COMMENT #13 - OK, SEE COMMENT 12.
  
 COMMENT #14 - OK
 COMMENT #15 - PLAN SHEET AC-29, PROPOSED
 SMOKE CONTROL SYSTEM.PLEASE INDICATE
 WHICH METHOD IS INTEND TO BE UTILIZED
 UNDER 2001 FBC 412.5 ITEMS 1, 2, 3 OR 4.
 SHOULD SUBMITTAL BE UNDER ITEM 4, THIS
 MUST BE SUBMITTED TO THE BUILDING
 OFFICAL, NEIL MELICK.PLEASE PROVIDE
 ALL SUPPORTING DOCUMENTATION.
  
 COMMENT #16 - OK
 COMMENT #17 - OK
 COMMENT #18 - OK
 ****************************************
 NEW COMMENT
 19. PLAN SHEET A-4.1 - THE DOOR SCHEDULE
 INDICATES THE A/C CLOSET DOOR IN THE
 APARTMENTS ARE TO BE WOOD.PLEASE
 VERIFY WITH THE DOOR MANUFACTURER IF
 THIS MEETS THE CRITERIA FOR A NON
 COMBUSTIBLE DOOR AS REQUIRED IN 2001 FMC
 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  