2006-01-04 00:00:00 | ******DENIED****** |
| |
| PLAN REVIEW WAS STARTED BY F.M. M. |
| CARSILLO AND STOPPED AFTER 32 COMMENTS. |
| THE FOLLOWING IS A CONTINUATION OF THE |
| SAME PLAN REVIEW: |
| |
| 33) A MINIMUM OF (2) FIRE DEPARTMENT |
| CONNECTIONS REQUIRED FOR HIGHRISE |
| BUILDINGS. |
| |
| 34) THE FIRE ALARM SYSTEM SHALL BE UL |
| CERTIFIED FOR CENTRAL STATION SERVICE. |
| |
| 35) LOCKING KNOX BOX CAPS REQUIRED FOR |
| FIRE DEPARTMENT CONNECTIONS. |
| |
| 36) THE FIRE ALRM SYSTEM SHALL MEET THE |
| SURVIVABILITY REQUIREMENTS OF NFPA 72. |
| |
| 37) THE BUILDING IS TO MEET ALL HIGHRISE |
| REQUIREMENTS IN ACCORDANCE WITH |
| APPLICABLE BUILDING AND FIRE CODES. |
| |
| 38) SEPARATE SHOP DRAWINGS AND PERMITS |
| REQUIRED FOR FIRE SPRINKLER AND FIRE |
| ALARM SYSTEMS. |
| |
| 39) SEPARATE SHOP DRAWINGS AND |
| MANUFACTURER SPEC SHEETS REQUIRED FOR |
| FIRE PUMP AND ASSOCIATED EQUIPMENT. |
| |
| 40) PLEASE NOTE THAT VARIOUS CODE |
| EDITIONS ON SHT SP-14 ARE INCORRECT. |
| NFPA 101 AND NFPA 1, 2003 EDITION, NFPA |
| 13, 2002 EDITION, NFPA 14, 2003 EDITION, |
| AND NFPA 20, 2003 EDITION. |
| |
| 41) IN ADDITION TO ELECTRONIC SWITCHES, |
| THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL |
| BE SECURED WITH A LOCK AND CHAIN. |
| |
| 42) ALL ELEVATORS TO COMPLY WITH ASME |
| A17.1. |
| |
| 43) PARKING GARAGE TO COMPLY WITH THE |
| APPLICABLE BUILDING CODES AND NFPA 88A. |
| |
| 44) PLEASE PROVIDE INTERIOR FINISH |
| CLASSIFICATION FOR WALLS AND CEILINGS IN |
| TERMS OF CLASS A,B, OR C. |
| |
| 45) AN ADDRESS IS REQUIRED ON BUILDING |
| AND SHALL BE A MINIMUM OF 6" IN HEIGHT |
| AND CONTRASTING WITH BACKGROUND. |
| |
| 46) ALL SMOKE DETECTORS SHALL BE LOCATED |
| A MINIMUM OF (3) FEET FROM AC DIFFUSERS. |
| |
| 47) FIRE ALARM SYSTEM SHALL BE CLASS A, |
| STYLE D OR FULLY ADDRESSABLE. |
| |
| |
| MIKE WENNERGREN, CAPTAIN/WPFR |
| FIRE PLANS REVIEW (561) 805-6722 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
2005-11-18 00:00:00 | 1. CONSTRUCTION, DEMOLITION, AND |
| RENOVATION TO COMPLY WITH NFPA 241. |
| |
| 2. EXIT STAIRS ARE TO BE KEPT UP |
| WITH CONSTRUCTION. |
| |
| 3. TEMPORTARY STANDPIPES ARE |
| REQUIRED WHEN THE BUILDING REACHES |
| THREE STORIES OR THIRTY FEET IN HEIGHT. |
| |
| 4. DEBRIS REMOVAL SHALL OCCUR |
| DAILY. |
| |
| 5. NO CUTTING OR WELDING IS TO BE |
| PERFORMED WITHOUT APPROVAL FROM |
| THE BUREAU OF FIRE PREVENTION AND |
| COMPLIANCE WITH NFPA 51B. |
| |
| 6. WHAT WILL BE THE NAME OF THE NEW |
| STREET. |
| |
| 7. WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| TO, DURING ,AND AFTER CONSTRUCTION. |
| |
| 8. SUITABLE ROADS REQUIRED FOR FIRE |
| AND PARAMEDICAL EQUIPMENT. |
| |
| 9. COULD ONLY LOCATE ONLY TWO FIRE |
| HYDRANTS ON PAGE C-13. NOT ENOUGH |
| FIRE HYDRANTS. |
| |
| 10. PLEASE REVIEW CODE TAB BOX TO |
| ENSURE PROPER INFORMATION. |
| |
| 11. KNOX-BOXES WILL BE REQUIRED. |
| |
| 12. ALL COMMERCIAL SPACES MUST BE FIRE |
| SPRINKLER PROTECTED PRIOR TO |
| RECEIVING A C OF O. |
| |
| 13. COULD NOT LOCATE EXIT SIGNS GARAGE, |
| GROUND FLOOR. |
| |
| 14. NO EXIT SIGNS SECOND FLOOR, PAGE |
| E-3. |
| |
| 15. EXIT SIGNS APPEAR TO BE MISSING |
| ON PAGE E-4. WHERE ARE THE ARE THE |
| EXIT SIGNS LOCATED FOR THE GARAGE. |
| CORRIDOR NEAR ELECTRICAL ROOM # 3 |
| DISPLAYS NO EQUIPMENT. |
| |
| 16. SAME PROBLEM ON PAGE E-5. |
| |
| 17. EXIT SIGNS SHALL NOT EXCEED 100 |
| FEET APART. |
| |
| 18. ELECTRICAL PLANS DO NOT APPEAR TO |
| BE COMPLETE. |
| |
| 19. PLEASE INDICATE FIRE RATINGS OF |
| SHAFTS SHWON ON PAGE AC-14. |
| |
| 20. MECHANICAL EQUIPMENT SHOWN IN |
| SOME STAIRWELLS. ONLY CERTAIN |
| EQUIPMENT IS ALLOWED IN STAIRWELLS. |
| |
| 21. PLEASE XPLAIN GATE IN PARKING GARAGE |
| ON PAGE A-1.1. |
| |
| 22. PLEASE SUBMIT A LIFE SAFETY PLAN |
| FOR REVIEW. |
| |
| 23. DOORS FOR THE POOL DECK ON THE 9TH |
| FLOOR APPEAR TO SWING IN THE WRONG |
| DIRECTION. |
| |
| 24. PLEASE INDICATE OCCUPANT LOAD |
| FOR POOL AND POOL DECK. |
| |
| 25. PLEASE EXPLAIN CARD READERS AND HOW |
| THEY WILL EFFECT EXITING. |
| |
| 26. SOFFITS ARE NOT TO INTERFERE WITH |
| ANY OPERATION OF REQUIRED FIRE |
| SPRINKLERS. |
| |
| 27. PLEASE PROVIDE PRESCRIPTVE STRENGTH |
| REQUIREMENTS FOR ALL HANDRAILS AND |
| GUARDRAILS. |
| |
| 28. PLEASE INDICATE WHICH ELEVATORS |
| WILL BE STRETCHER ACCESSIBLE. SIGNS WILL |
| BE REQUIRED. |
| |
| 29. ELEVATOR WARNING SIGNS WILL BE |
| REQUIRED. |
| |
| 30. STAIRWELL SIGNS WILL BE REQUIRED. |
| |
| 31. TACTILE SIGNAGE REQUIRED AT STAIRS. |
| |
| 32. WHAT SIZE IS THE RISER AND TREADS |
| SHOWN ON PAGE A-2.1.3. |
| |
| ACCORDING TO DEWEY PALMER, NEW SHEETS |
| ARE TO BE SUBMITTED BY THE ARCHITECT. |
| THE REVIEW WAS STOPPED BECAUSE THE PLANS |
| WERE NOT COMPLETE. |
| |
| MIKE CARSILLO, CHIEF FIRE PREVENTION |
| OFFICER |
| 804-4709 |