Date Text
2006-01-04 00:00:00******DENIED******
  
 PLAN REVIEW WAS STARTED BY F.M. M.
 CARSILLO AND STOPPED AFTER 32 COMMENTS.
 THE FOLLOWING IS A CONTINUATION OF THE
 SAME PLAN REVIEW:
  
 33) A MINIMUM OF (2) FIRE DEPARTMENT
 CONNECTIONS REQUIRED FOR HIGHRISE
 BUILDINGS.
  
 34) THE FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 35) LOCKING KNOX BOX CAPS REQUIRED FOR
 FIRE DEPARTMENT CONNECTIONS.
  
 36) THE FIRE ALRM SYSTEM SHALL MEET THE
 SURVIVABILITY REQUIREMENTS OF NFPA 72.
  
 37) THE BUILDING IS TO MEET ALL HIGHRISE
 REQUIREMENTS IN ACCORDANCE WITH
 APPLICABLE BUILDING AND FIRE CODES.
  
 38) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 39) SEPARATE SHOP DRAWINGS AND
 MANUFACTURER SPEC SHEETS REQUIRED FOR
 FIRE PUMP AND ASSOCIATED EQUIPMENT.
  
 40) PLEASE NOTE THAT VARIOUS CODE
 EDITIONS ON SHT SP-14 ARE INCORRECT.
 NFPA 101 AND NFPA 1, 2003 EDITION, NFPA
 13, 2002 EDITION, NFPA 14, 2003 EDITION,
 AND NFPA 20, 2003 EDITION.
  
 41) IN ADDITION TO ELECTRONIC SWITCHES,
 THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL
 BE SECURED WITH A LOCK AND CHAIN.
  
 42) ALL ELEVATORS TO COMPLY WITH ASME
 A17.1.
  
 43) PARKING GARAGE TO COMPLY WITH THE
 APPLICABLE BUILDING CODES AND NFPA 88A.
  
 44) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN
 TERMS OF CLASS A,B, OR C.
  
 45) AN ADDRESS IS REQUIRED ON BUILDING
 AND SHALL BE A MINIMUM OF 6" IN HEIGHT
 AND CONTRASTING WITH BACKGROUND.
  
 46) ALL SMOKE DETECTORS SHALL BE LOCATED
 A MINIMUM OF (3) FEET FROM AC DIFFUSERS.
  
 47) FIRE ALARM SYSTEM SHALL BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2005-11-18 00:00:001. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. EXIT STAIRS ARE TO BE KEPT UP
 WITH CONSTRUCTION.
  
 3. TEMPORTARY STANDPIPES ARE
 REQUIRED WHEN THE BUILDING REACHES
 THREE STORIES OR THIRTY FEET IN HEIGHT.
  
 4. DEBRIS REMOVAL SHALL OCCUR
 DAILY.
  
 5. NO CUTTING OR WELDING IS TO BE
 PERFORMED WITHOUT APPROVAL FROM
 THE BUREAU OF FIRE PREVENTION AND
 COMPLIANCE WITH NFPA 51B.
  
 6. WHAT WILL BE THE NAME OF THE NEW
 STREET.
  
 7. WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING ,AND AFTER CONSTRUCTION.
  
 8. SUITABLE ROADS REQUIRED FOR FIRE
 AND PARAMEDICAL EQUIPMENT.
  
 9. COULD ONLY LOCATE ONLY TWO FIRE
 HYDRANTS ON PAGE C-13. NOT ENOUGH
 FIRE HYDRANTS.
  
 10. PLEASE REVIEW CODE TAB BOX TO
 ENSURE PROPER INFORMATION.
  
 11. KNOX-BOXES WILL BE REQUIRED.
  
 12. ALL COMMERCIAL SPACES MUST BE FIRE
 SPRINKLER PROTECTED PRIOR TO
 RECEIVING A C OF O.
  
 13. COULD NOT LOCATE EXIT SIGNS GARAGE,
 GROUND FLOOR.
  
 14. NO EXIT SIGNS SECOND FLOOR, PAGE
 E-3.
  
 15. EXIT SIGNS APPEAR TO BE MISSING
 ON PAGE E-4. WHERE ARE THE ARE THE
 EXIT SIGNS LOCATED FOR THE GARAGE.
 CORRIDOR NEAR ELECTRICAL ROOM # 3
 DISPLAYS NO EQUIPMENT.
  
 16. SAME PROBLEM ON PAGE E-5.
  
 17. EXIT SIGNS SHALL NOT EXCEED 100
 FEET APART.
  
 18. ELECTRICAL PLANS DO NOT APPEAR TO
 BE COMPLETE.
  
 19. PLEASE INDICATE FIRE RATINGS OF
 SHAFTS SHWON ON PAGE AC-14.
  
 20. MECHANICAL EQUIPMENT SHOWN IN
 SOME STAIRWELLS. ONLY CERTAIN
 EQUIPMENT IS ALLOWED IN STAIRWELLS.
  
 21. PLEASE XPLAIN GATE IN PARKING GARAGE
 ON PAGE A-1.1.
  
 22. PLEASE SUBMIT A LIFE SAFETY PLAN
 FOR REVIEW.
  
 23. DOORS FOR THE POOL DECK ON THE 9TH
 FLOOR APPEAR TO SWING IN THE WRONG
 DIRECTION.
  
 24. PLEASE INDICATE OCCUPANT LOAD
 FOR POOL AND POOL DECK.
  
 25. PLEASE EXPLAIN CARD READERS AND HOW
 THEY WILL EFFECT EXITING.
  
 26. SOFFITS ARE NOT TO INTERFERE WITH
 ANY OPERATION OF REQUIRED FIRE
 SPRINKLERS.
  
 27. PLEASE PROVIDE PRESCRIPTVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 28. PLEASE INDICATE WHICH ELEVATORS
 WILL BE STRETCHER ACCESSIBLE. SIGNS WILL
 BE REQUIRED.
  
 29. ELEVATOR WARNING SIGNS WILL BE
 REQUIRED.
  
 30. STAIRWELL SIGNS WILL BE REQUIRED.
  
 31. TACTILE SIGNAGE REQUIRED AT STAIRS.
  
 32. WHAT SIZE IS THE RISER AND TREADS
 SHOWN ON PAGE A-2.1.3.
  
 ACCORDING TO DEWEY PALMER, NEW SHEETS
 ARE TO BE SUBMITTED BY THE ARCHITECT.
 THE REVIEW WAS STOPPED BECAUSE THE PLANS
 WERE NOT COMPLETE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709