Date |
Text |
2006-06-18 00:00:00 | REVIEW IN PROGRESS. |
| ****** UNSAT 2ND REVIEW ****** |
| |
| ** PLEASE SEE SOME COMMENTS FROM FIRST |
| REVIEW AND SOME NEW COMMENTS DUE TO |
| COMPLETE RISER ETC NOW SUBMITTED. |
| |
| |
| ** IMPORTANT** |
| WHEN SUBMITTING MANUFACTURES SPECS/CUT |
| SHEETS, PRODUCT APPROVALS, STRUCTURAL |
| CALCS ETC,PLEASE PLACE IN A BINDER OF |
| SOME TYPE AND LABEL EACH SECTION/PRODUCT |
| FOR EASY REFERENCE. THIS WOULD HELP |
| GREATLY IN THE PLAN REVIEW PROCESS AND |
| KEEPING ALL SUBMITTIALS IN ORDER. |
| |
| 1) NOTE: PLEASE CORRELATE ALL |
| SPEC/MANUFACTURES CUT SHEETS SUBMITTED |
| WITH PLANS. |
| PLEASE SEE TWO DIFFERENT GENERATORS, TWO |
| DIFFERENT SIZES, TWO DIFFERENT ATS'S. |
| PLEASE SEE RISER AND PLANS. |
| 215.5 |
| |
| 2) NOTE: PLEASE SEE SEE ATS IS STILL |
| BEING SHOWN AS 3-POLE ON PLANS/ RISER |
| AND SUBMITTIALS. |
| PLEASE SEE RISER ALSO INDICATES 4-POLE |
| AS REQUIRED IN ONE LOCATION. |
| PLEASE SEE E-19 SHOWS 3-POLE ALSO. |
| 215.5 |
| |
| 3) NOTE: PLEASE SEE FIRE PUMP SPECS FOR |
| DIESEL FP TANK, INDICATES 300 GALS IN ON |
| ONE SHEET AND 270 GALS ON ANOTHER? |
| PLEASE SPECIFY THE CORRECT SIZE TANK, |
| PLEASE SPECIFY THE GPH CONSUMPTION OF |
| THE DIESEL FIRE PUMP. |
| ** PLEASE VERIFY MIN 8HRS? |
| 215.5, UNABLE TO VERIFY. PLEASE SEE |
| NFPA-20 CHAPTER 11 |
| |
| 4) NOTE: PLEASE SEE NO "JOBSITE SPEC |
| BOOKS" WERE SUBMITTED. THIS IS REQUIRED. |
| |
| 5) NOTE: PLEASE SEE RISER NOTE #7A IS |
| BEING INDICATED YET THIS COULD NOT BE |
| LOCATED ON RISER. THIS IS FOR METER/UNIT |
| RISER. |
| 215.5 |
| |
| 6) NOTE: PLEASE SEE NOTE #3 ON HOUSE |
| RISER INDICATES GFI PROTECTION. (SHOULD |
| BE GFP.) |
| 215.5 |
| |
| 7) NOTE: PLEASE SEE NOTE #5 HOUSE RISER |
| NOTES, (3-POLE ATS), SEE NOTES ABOVE AND |
| CORRELATE. |
| 215.5 |
| |
| 8) NOTE: PLEASE SEE MAIN FOR "TDP" IS |
| SHOWN AS 1000A'S ON E-19, YET THIS IS |
| NOTED ON HOUSE RISER NOTES AS BEING |
| 1200A'S FOR FUTURE> |
| THE LOAD ON THIS "TDP" IS NOT KNOWN AT |
| THIS TIME>?? |
| PLEASE VERIFY AS A 1000A DISCONNECT MAY |
| FEED A 1200A DISC, AND IS BEING NOTED |
| FOR COORDINATION. |
| 215.5 |
| |
| 9) NOTE: PLEASE SEE UNIT C-2 MISSING |
| CIRCUITING FOR KITCHEN WALL. |
| THIS WAS NOTED AND REDLINED ON PREVIOUS |
| PLANS. |
| 215.5 |
| ** THIS CAN BE REDLINED** |
| |
| 10) NOTE: PLEASE SEE UNIT C-9 AS |
| LOCATION OF SD IN DEN SHOULD BE LOCATED |
| WITHIN 12" OF THE HIGHEST POINT OF THE |
| CEILING. IN UNIT C-9.1 THE SD WAS |
| RELOCATED AND SEEMS TO BE THE SMAE |
| LAYOUT. |
| NFPA-72 11.8.3.5 |
| ** THIS CAN BE REDLINED.** |
| |
| 11) NOTE: PLEASE SEE PANEL NOTATIONS ON |
| E-20 INDICATE PANELS "TR1", TR2" AND TF |
| PANELS BEING LOCATED ON THAT PAGE, |
| HOWEVER THESE ARE ON E-22 |
| 215.5 |
| |
| 12) NOTE: PLEASE SEE MISPRINT FOR TWO |
| PANELS "LP'S" ON LOWER RIGHT HAND CORNER |
| OF E-22. |
| ** THIS CAN BE REDLINED ** |
| |
| 13) NOTE: PLEASE INDICATE THE |
| PHOTO-METRICS FOR STAIRS UNDER EM POWER, |
| AS ONLY THE TYPICAL DETAILS FOR TWO |
| STAIR TOWERS WERE LOCATED FOR LEVELS |
| UNDER NORMAL. |
| LS 101 7.8.1.3,7.9.2.2 |
| |
| **PLEASE BE AWARE OF ANY COMMENTS FROM |
| OTHER TRADES WHICH HAVE AN AFFECT ON |
| ELECTRICAL PLANS. |
| |
| ** WHEN RESUBMITTING PLANS, PLEASE BE |
| SURE TO REMOVE ANY OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2006-06-11 00:00:00 | ONE ROLL IN ELECTRICAL FOR REVIEW, |