Plan Review Notes
Plan Review Notes For Permit 05091425
Permit Number 05091425
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-18 00:00:00REVIEW IN PROGRESS.
 ****** UNSAT 2ND REVIEW ******
  
 ** PLEASE SEE SOME COMMENTS FROM FIRST
 REVIEW AND SOME NEW COMMENTS DUE TO
 COMPLETE RISER ETC NOW SUBMITTED.
  
  
 ** IMPORTANT**
 WHEN SUBMITTING MANUFACTURES SPECS/CUT
 SHEETS, PRODUCT APPROVALS, STRUCTURAL
 CALCS ETC,PLEASE PLACE IN A BINDER OF
 SOME TYPE AND LABEL EACH SECTION/PRODUCT
 FOR EASY REFERENCE. THIS WOULD HELP
 GREATLY IN THE PLAN REVIEW PROCESS AND
 KEEPING ALL SUBMITTIALS IN ORDER.
  
 1) NOTE: PLEASE CORRELATE ALL
 SPEC/MANUFACTURES CUT SHEETS SUBMITTED
 WITH PLANS.
 PLEASE SEE TWO DIFFERENT GENERATORS, TWO
 DIFFERENT SIZES, TWO DIFFERENT ATS'S.
 PLEASE SEE RISER AND PLANS.
 215.5
  
 2) NOTE: PLEASE SEE SEE ATS IS STILL
 BEING SHOWN AS 3-POLE ON PLANS/ RISER
 AND SUBMITTIALS.
 PLEASE SEE RISER ALSO INDICATES 4-POLE
 AS REQUIRED IN ONE LOCATION.
 PLEASE SEE E-19 SHOWS 3-POLE ALSO.
 215.5
  
 3) NOTE: PLEASE SEE FIRE PUMP SPECS FOR
 DIESEL FP TANK, INDICATES 300 GALS IN ON
 ONE SHEET AND 270 GALS ON ANOTHER?
 PLEASE SPECIFY THE CORRECT SIZE TANK,
 PLEASE SPECIFY THE GPH CONSUMPTION OF
 THE DIESEL FIRE PUMP.
 ** PLEASE VERIFY MIN 8HRS?
 215.5, UNABLE TO VERIFY. PLEASE SEE
 NFPA-20 CHAPTER 11
  
 4) NOTE: PLEASE SEE NO "JOBSITE SPEC
 BOOKS" WERE SUBMITTED. THIS IS REQUIRED.
  
 5) NOTE: PLEASE SEE RISER NOTE #7A IS
 BEING INDICATED YET THIS COULD NOT BE
 LOCATED ON RISER. THIS IS FOR METER/UNIT
 RISER.
 215.5
  
 6) NOTE: PLEASE SEE NOTE #3 ON HOUSE
 RISER INDICATES GFI PROTECTION. (SHOULD
 BE GFP.)
 215.5
  
 7) NOTE: PLEASE SEE NOTE #5 HOUSE RISER
 NOTES, (3-POLE ATS), SEE NOTES ABOVE AND
 CORRELATE.
 215.5
  
 8) NOTE: PLEASE SEE MAIN FOR "TDP" IS
 SHOWN AS 1000A'S ON E-19, YET THIS IS
 NOTED ON HOUSE RISER NOTES AS BEING
 1200A'S FOR FUTURE>
 THE LOAD ON THIS "TDP" IS NOT KNOWN AT
 THIS TIME>??
 PLEASE VERIFY AS A 1000A DISCONNECT MAY
 FEED A 1200A DISC, AND IS BEING NOTED
 FOR COORDINATION.
 215.5
  
 9) NOTE: PLEASE SEE UNIT C-2 MISSING
 CIRCUITING FOR KITCHEN WALL.
 THIS WAS NOTED AND REDLINED ON PREVIOUS
 PLANS.
 215.5
 ** THIS CAN BE REDLINED**
  
 10) NOTE: PLEASE SEE UNIT C-9 AS
 LOCATION OF SD IN DEN SHOULD BE LOCATED
 WITHIN 12" OF THE HIGHEST POINT OF THE
 CEILING. IN UNIT C-9.1 THE SD WAS
 RELOCATED AND SEEMS TO BE THE SMAE
 LAYOUT.
 NFPA-72 11.8.3.5
 ** THIS CAN BE REDLINED.**
  
 11) NOTE: PLEASE SEE PANEL NOTATIONS ON
 E-20 INDICATE PANELS "TR1", TR2" AND TF
 PANELS BEING LOCATED ON THAT PAGE,
 HOWEVER THESE ARE ON E-22
 215.5
  
 12) NOTE: PLEASE SEE MISPRINT FOR TWO
 PANELS "LP'S" ON LOWER RIGHT HAND CORNER
 OF E-22.
 ** THIS CAN BE REDLINED **
  
 13) NOTE: PLEASE INDICATE THE
 PHOTO-METRICS FOR STAIRS UNDER EM POWER,
 AS ONLY THE TYPICAL DETAILS FOR TWO
 STAIR TOWERS WERE LOCATED FOR LEVELS
 UNDER NORMAL.
 LS 101 7.8.1.3,7.9.2.2
  
 **PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER TRADES WHICH HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 ** WHEN RESUBMITTING PLANS, PLEASE BE
 SURE TO REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-06-11 00:00:00ONE ROLL IN ELECTRICAL FOR REVIEW,