Plan Review Notes For Permit 05091425 |
Permit Number |
05091425 |
|
Review Stop |
M |
Sequence Number |
18 |
|
Notes |
Date |
Text |
2007-12-24 08:58:23 | ** SUBMITTAL FOR SAUNA ** | | *** PROVISO *** | | 1) A VENTILATION OPENING INTO THE SAUNA ROOM SHALL BE | | PROVIDED. THE OPENING SHALL BE NOT LESS THAN 4 INCHES | | BY 8 INCHES (102 MM BY 203 MM) LOCATED NEAR THE TOP OF | | THE DOOR INTO THE SAUNA ROOM. PER 2004 FBC/M 914.5. | | | | 2)WARNING NOTICE. | | THE FOLLOWING PERMANENT NOTICE, CONSTRUCTED OF APPROVED | | MATERIAL, SHALL BE MECHANICALLY ATTACHED TO THE SAUNA | | ROOM ON THE OUTSIDE: | | WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE | | EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR | | HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. | | THE WORDS SHALL CONTRAST WITH THE BACKGROUND AND THE | | WORDING SHALL BE IN LETTERS NOT LESS THAN 0.25-INCH | | (6.4 MM) HIGH. PER 2004 FBC/M 914.5.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | | | ** 4-30-08UPDATE TO PROVISO. IF THE SAUNA HEATER IS | | ELECTRIC AND NOT FUEL BURNING THEN VENTILATION WILL NOT | | BE REQUIRED AND SAUNA SHALL BE INSTALLED PER | | MANUFACTURES INSTRUCTIONS, PER 2004 FBC/M 304.1. ** | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|