Plan Review Notes For Permit 05091425 |
Permit Number |
05091425 |
|
Review Stop |
B |
Sequence Number |
171 |
|
Notes |
Date |
Text |
2007-10-01 20:36:17 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 9/24/07 FOR EIFS SYSTEMS TEST REPORT. | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) THE SUBMITTED METAL FRAMING CALCULATIONS ARE OK AND | | HAVE BEEN STAMPED | | | | 2) THE REVISED ARCHITECTURAL SHEETS ARE OK AND HAVE | | BEEN STAMPED BECAUSE THEY STATE THE REQUIREMENT FOR | | ASTM E 136 COMPLIANCE. | | | | 3) FBC 202DEFINITION OF "NON-COMBUSTIBLE MATERIAL". | | NON-COMBUSTIBLE MATERIAL IS THAT WHICH HAS PASSED THE | | TEST PROCEDURE SET FORTH IN ASTM E 136.THE SUBMITTED | | PRODUCT TEST REPORT CANNOT BE STAMPED BECAUSE THE TEST | | STANDARD USED TO TEST THE STO CLASSIC NEXT SYSTEM WAS | | NFPA 285 NOT ASTM E 136, SO THE PRODUCT HAS NOT BEEN | | SHOWN TO MEET THE REQUIREMENTS FOR NON-COMBUSTIBLE | | MATERIAL.PROVIDE A TEST REPORT BASED ON THE ASTM E | | 136 TEST STANDARD. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] | | | | | | |
|