2007-06-25 19:38:05BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 5/11/07 FOR DECORAWALL "PROMOULD"
 ARCHITECTURAL DETAILS.
  
 1)FBC 1406.2.2ARCHITECTURAL TRIM.ARCHITECTURAL
 TRIM MORE THAN 40 FEET ABOVE GRADE, ON TYPE I AND II
 BUILDINGS, SHALL BE CONSTRUCTED OF APPROVED
 NON-COMBUSTIBLE MATERIALS AND SHALL BE SECURED WITH
 METAL OR OTHER APPROVED NON-COMBUSTIBLE BRACKETS.THE
 SUBMITTED SHOP DRAWINGS AND SPECIFICATION DO NOT CALL
 OUT MECHANICAL FASTENING FOR THE MOLDINGS ON THIS
 PROJECT.ALSO, THE SUBMITTED SPECIFICATION DOES NOT
 SHOW THAT THE CORE MATERIAL HAS BEEN TESTED IN
 ACCORDANCE WITH ASTM E 136 TO VERIFY THAT IS
 NON-COMBUSTIBLE (REF: FBC 703.4.1).IT IS NOTED THAT
 THE "COATING" HAS BEEN TESTED TO ASTM E 84, BUT NO TEST
 DATA WAS SUBMITTED FOR THE CORE MATERIAL.SUBMIT
 DOCUMENTATION (MARKED UP IF NECESSARY) TO SHOW
 COMPLIANCE WITH THE MECHANICAL FASTENING AND ASTM E 136
 NON-COMBUSTIBILITY REQUIREMENTS.
  
 2) FBC 1609.1WIND LOADS.SUBMIT TEST DATA AND/OR
 ATTACHMENT CALCULATIONS TO JUSTIFY THE MOULDING
 ATTACHMENT RESISTANCE TO WIND LOAD AND SELF WEIGHT.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS