Plan Review Notes For Permit 05091425 |
Permit Number |
05091425 |
|
Review Stop |
P |
Sequence Number |
10 |
|
Notes |
Date |
Text |
2007-06-09 12:02:20 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P-1 NO CHANGES FROM LAST REVISION. (REVISION | | 18). SEE SHEET SIGNED, SEALED, DATED 4-18-2007. | | | | 2. SHT P-4 8TH FLOOR HUB DRAINS, (SAFE WASTE), NOT | | APPROVED. SECTION 1002.1 EACH FIXTURE SHALL HAVE ITS | | OWN TRAP. NO DOUBLE TRAPING. CONNECT EACH HUB DRAIN TO | | THE VENTED LINE. (COMBINATION WASTE & VENT). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|