Plan Review Notes
Plan Review Notes For Permit 05091425
Permit Number 05091425
Review Stop P
Sequence Number 10
Notes
Date Text
2007-06-09 12:02:20REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P-1 NO CHANGES FROM LAST REVISION. (REVISION
 18). SEE SHEET SIGNED, SEALED, DATED 4-18-2007.
  
 2. SHT P-4 8TH FLOOR HUB DRAINS, (SAFE WASTE), NOT
 APPROVED. SECTION 1002.1 EACH FIXTURE SHALL HAVE ITS
 OWN TRAP. NO DOUBLE TRAPING. CONNECT EACH HUB DRAIN TO
 THE VENTED LINE. (COMBINATION WASTE & VENT).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]