Plan Review Notes
Plan Review Notes For Permit 05091425
Permit Number 05091425
Review Stop M
Sequence Number 1
Notes
Date Text
2005-12-28 00:00:00DENIED:2001 FLORIDA BUILDING CODE
  
 1.PLAN SHEET AC-1 EMERGENCY GENERATOR
 NOTE STATES 'SEE 1/4" SCALE DRAWING ON
 THIS SHEET FOR LAYOUT.DETAIL FOR THE
 LAYOUT IS NOT SHOWN.
  
 2.PLEASE PROVIDE DISTANCE TO SIDEWALK
 FROM THE GENERATOR EXHAUST TERMINATION.
  
 3.PLEASE PROVIDE DETAIL FOR THE
 GENERATOR WITH THE ELEVATION FOR MUFFLER
 EXHAUST.PLAN SHEET A-2.1.6 INDICATES
 LOUVERS, PLEASE SPECIFY INTAKES &
 EXHAUST.
  
 4.PLAN SHEET AC-1 VENTILATION FOR
 VARIOUS ROOMS ARE NOT INDICATED
 (TELEPHONE, ELECTRICAL, PUMP ROOM,
 OFFICE AREAS, ETC).
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001 FBC
 TABLE 403.3.
  
 6.PROVIDE CALCULATIONS FOR THE GARAGE
 VENTILATION IN ACCORDANCE WITH 2001 FBC
 411.4.2.
  
 7.PLEASE NOTE, PLAN SHEET AC-1 FUTURE
 COMMERCIAL/RETAIL SPACE.SHOULD A
 RESTAURANT BE IN THE FUTURE PLANS
 CONSIDER LAYOUT FOR GREASE DUCT AND
 EXHAUST TERMINATION.
  
 8.PLAN SHEETS AC-8 & 9 MECHANICAL
 ROOMS.PLANS DO NOT INDICATE
 VENTILATION FOR THE ROOMS.
  
 9.PROVIDE LAYOUT FOR CONDENSER WATER
 PIPING.INDICATE PIPE SIZE & MATERIAL.
  
  
 10. AC-12 UNIT C-5 DEN AREA WEST OF THE
 KITCHEN AREA, RETURN AIR IN NOT
 INDICATED.PLAN SHEET A1.1 SHOWS DOOR
 SEPARATING DEN.SHOW COMPLIANCE WITH
 2001 FMC 601.4.PLEASE NOTE, RETURN AIR
 JUMPERS SHALL COMPLY WITH 2001 FMC 601.4
 EXCEPTION 1 & 3.
  
 11. PROVIDE INFORMATION & DETAILS FOR
 THE VENTILATION OF THE POOL EQUIPMENT
 ROOM.
  
 12. PLAN SHEET P-1 ITEM #2 INDICATES GAS
 LINE.PLEASE INDICATE ALL GAS
 APPLIANCES.
  
 13. PLAN SHEET P-7 INDICATES A BOILER
 ROOM.PLEASE PROVIDE VENTILATION &
 COMBUSTION AIR CALCULATIONS.
  
 14. PLEASE PROVIDE SEQUENCE OF
 OPERATION.
  
 15. PLEASE INDICATE METHOD OF SMOKE
 CONTROL PER 2001 FBC 412.5.
  
 16. DRYER SHAFT & TRASH CHUTE SHALL BE
 EQUIPPED WITH FIRE SPRINKLERS IN
 ACCORDANCE WITH 2001 FBC 705.2.4.6 &
 NFPA 13 SECTION 8.14.2.2.1 & 13.15.2.1.1
  
 17. PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE GENERATOR, DRYER,
 PUMPS, ETC.
  
 18. PLEASE PROVIDE ENERGY CALCULATIONS
 PER CHAPTER 13 OF THE 2001 FBC.
  
 PLEASE NOTE, PLANS APPEAR TO BE
 INCOMPLETE WHICH MAY GENERATE ADDITIONAL
 COMMENTS ON SUBSEQUENT REVIEWS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  