2005-12-28 00:00:00 | DENIED:2001 FLORIDA BUILDING CODE |
| |
| 1.PLAN SHEET AC-1 EMERGENCY GENERATOR |
| NOTE STATES 'SEE 1/4" SCALE DRAWING ON |
| THIS SHEET FOR LAYOUT.DETAIL FOR THE |
| LAYOUT IS NOT SHOWN. |
| |
| 2.PLEASE PROVIDE DISTANCE TO SIDEWALK |
| FROM THE GENERATOR EXHAUST TERMINATION. |
| |
| 3.PLEASE PROVIDE DETAIL FOR THE |
| GENERATOR WITH THE ELEVATION FOR MUFFLER |
| EXHAUST.PLAN SHEET A-2.1.6 INDICATES |
| LOUVERS, PLEASE SPECIFY INTAKES & |
| EXHAUST. |
| |
| 4.PLAN SHEET AC-1 VENTILATION FOR |
| VARIOUS ROOMS ARE NOT INDICATED |
| (TELEPHONE, ELECTRICAL, PUMP ROOM, |
| OFFICE AREAS, ETC). |
| |
| 5.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH 2001 FBC |
| TABLE 403.3. |
| |
| 6.PROVIDE CALCULATIONS FOR THE GARAGE |
| VENTILATION IN ACCORDANCE WITH 2001 FBC |
| 411.4.2. |
| |
| 7.PLEASE NOTE, PLAN SHEET AC-1 FUTURE |
| COMMERCIAL/RETAIL SPACE.SHOULD A |
| RESTAURANT BE IN THE FUTURE PLANS |
| CONSIDER LAYOUT FOR GREASE DUCT AND |
| EXHAUST TERMINATION. |
| |
| 8.PLAN SHEETS AC-8 & 9 MECHANICAL |
| ROOMS.PLANS DO NOT INDICATE |
| VENTILATION FOR THE ROOMS. |
| |
| 9.PROVIDE LAYOUT FOR CONDENSER WATER |
| PIPING.INDICATE PIPE SIZE & MATERIAL. |
| |
| |
| 10. AC-12 UNIT C-5 DEN AREA WEST OF THE |
| KITCHEN AREA, RETURN AIR IN NOT |
| INDICATED.PLAN SHEET A1.1 SHOWS DOOR |
| SEPARATING DEN.SHOW COMPLIANCE WITH |
| 2001 FMC 601.4.PLEASE NOTE, RETURN AIR |
| JUMPERS SHALL COMPLY WITH 2001 FMC 601.4 |
| EXCEPTION 1 & 3. |
| |
| 11. PROVIDE INFORMATION & DETAILS FOR |
| THE VENTILATION OF THE POOL EQUIPMENT |
| ROOM. |
| |
| 12. PLAN SHEET P-1 ITEM #2 INDICATES GAS |
| LINE.PLEASE INDICATE ALL GAS |
| APPLIANCES. |
| |
| 13. PLAN SHEET P-7 INDICATES A BOILER |
| ROOM.PLEASE PROVIDE VENTILATION & |
| COMBUSTION AIR CALCULATIONS. |
| |
| 14. PLEASE PROVIDE SEQUENCE OF |
| OPERATION. |
| |
| 15. PLEASE INDICATE METHOD OF SMOKE |
| CONTROL PER 2001 FBC 412.5. |
| |
| 16. DRYER SHAFT & TRASH CHUTE SHALL BE |
| EQUIPPED WITH FIRE SPRINKLERS IN |
| ACCORDANCE WITH 2001 FBC 705.2.4.6 & |
| NFPA 13 SECTION 8.14.2.2.1 & 13.15.2.1.1 |
| |
| 17. PLEASE PROVIDE MANUFACTURER |
| SUBMITTAL DATA FOR THE GENERATOR, DRYER, |
| PUMPS, ETC. |
| |
| 18. PLEASE PROVIDE ENERGY CALCULATIONS |
| PER CHAPTER 13 OF THE 2001 FBC. |
| |
| PLEASE NOTE, PLANS APPEAR TO BE |
| INCOMPLETE WHICH MAY GENERATE ADDITIONAL |
| COMMENTS ON SUBSEQUENT REVIEWS. |
| |