2007-11-20 08:58:16REVIEW: 1ST
 ACTION: DENIED
  
 FBC 2001 W/ 2003 SUPPLEMENTS
 NFPA 37-94
  
 1. P-1A AND P-1B: INSTALLATIONS OF ABOVE GROUND FUEL
 TANKS IN EXCESS OF 550 GALLONS ARE REQUIRED TO BE
 APPROVED BY THE PALM BEACH COUNTY DEPARTMENT OF
 ENVIRONMENTAL RESOURCE MANAGEMENT. PLANS SHALL BE
 SUBMITTED AND APPROVED BY DERM PRIOR TO BEING REVIEWED
 FOR CODE COMPLIANCE AND MADE PART OF THE PERMIT RECORD.
 FOR MORE INFORMATION PLEASE CONTACT DERM AT
 561-233-2400 OR VISIT
 HTTP://WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP.
  
 2. P-1A AND P-1B: FUEL STORAGE FOR STATIONARY
 COMBUSTION ENGINES SHALL COMPLY WITH NFPA 37-94 IN
 ACCORDANCE WITH FBC, M 915.1. THE FOLLOWING CONDITIONS
 WHICH ARE SHOWN ON PLANS ARE IN VIOLATION OF NFPA 37-94
 SEC. 6-3.2.3.1:
  
 A) UNENCLOSED DAY TANKS (I.E., TANKS NOT IN A ROOM BY
 THEMSELVES) WHICH ARE USED FOR EMERGENCY PURPOSES SHALL
 NOT EXCEED 660 GALLONS.
 B) TWO OR MORE TANKS WITH AN AGGREGATE CAPACITY MORE
 THAN 660 GALLONS SHALL NOT BE CONNECTED TO ONE ENGINE.
 C) THE AGGREGATE CAPACITY OF ALL UNENCLOSED DAY AND
 SUPPLY TANKS IN A BUILDING SHALL NOT EXCEED 1,320
 GALLONS.
 D) DAY AND SUPPLY TANKS WITH INDIVIDUAL CAPACITIES
 LARGER THAN 660 GALLONS OR THOSE TANKS WHICH CAUSE THE
 AGGREGATE CAPACITY TO EXCEED 1,320 GALLONS IN A
 BUILDING SHALL BE ENCLOSED IN ACCORDANCE WITH SEC.
 6-3.5. ROOMS CONTAINING ONLY TANKS SHALL BE CONSTRUCTED
 OF WALLS, FLOOR AND TOP HAVING A FIRE RESISTANCE RATING
 OF NOT LESS THAN 3 HOURS WITH THE WALLS BONDED TO THE
 FLOOR IN ACCORDANCE WITH 6-3.5.1. PLEASE SEE THIS
 SECTION FOR ADDITIONAL REQUIREMENTS.
  
 3. IF THE 1500 GALLON DAY TANK IS ENCLOSED IN A 3-HOUR
 ROOM AS REQUIRED BY 6-3.2.3.1 AND 6-3.5, THEN THE
 AGGREGATE TOTAL OF THE SUPPLY TANKS FOR THE GENERATOR
 AND THE FIRE PUMP WILL BE LESS THAN THE MAXIMUM
 AGGREGATE 1,320 GALLONS ALLOWED FOR UNENCLOSED TANKS
 AND NO ADDITIONAL 3-HOUR ENCLOSURES WILL BE REQUIRED BY
 THIS SECTION.
  
 4. PLEASE VERIFY COMPLIANCE WITH SECTIONS 6-4 THROUGH
 6-8 REGARDING FUEL FLOW CONTROL, FILLING, PIPING AND
 TRANSFER OF LIQUID FUEL TO ENGINES.
  
 NOTE: A SEPARATE FUEL PERMIT IS REQUIRED FOR FUEL
 STORAGE SYSTEMS.
  