Plan Review Notes
Plan Review Notes For Permit 05091425
Permit Number 05091425
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-13 00:00:00********** UNSAT ***************
  
 SOUTH TOWER @CITY PLACE
 550 OKEECHOBEE BLVD.
  
 **** PLEASE KNOW, PLANS SUBMITTED ARE
 NOT COMPLETE, THERFORE A COMPLETE REVIEW
 FOR CODE COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
 PLEASE SEE THE BELOEW ITEMS KNOWN AT
 THIS TIME.
  
 1)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECIFICATION SHEETS/ CUT SHEETS FOR
 FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER,
 GENERATOR, AUTOMATIC TRANSFER SWITCH
 (ATS) AND ANY SUB BASE FUEL TANKS OR
 FUEL TANKS FOR DIESEL FIRE PUMP.
 PLEASE SURE ALL INFORMATION SUBMITTED
 MUST SHOW LISTINGS FROM A NATIONALLY
 RECOGNIZED TESTING LAB. (NRTL).
 PLEASE BE SURE ALL FIRE PUMP CONTROLLERS
 ETC COMPLY WITH NFPA-20 AND OTHER
 APPLICABLE CODES.
  
 2)NOTE: PLEASE SEE PLANS INDICATE 600KW,
 YET RISER DIAGRAM SHOWS 400KW GEN.
 PLEASE ALSO VERIFY IF THE ATS WILLL BE A
 4-POLE AND GEN TO BE SEPARTAELY DERIVED.
  
 PLEASE SEE 700.6DWHICH IN ORDER TO
 INDICATE A GROUND FAULT IN SOLIDLY
 GROUNDED WYE EMERGENCY SYSTEMS OF MORE
 THAN 150 VOLTS TO GROUND AND
 CIRCUIT-PROTECTIVE DEVICES RATED 1000
 AMPERES OR MORE. THE SENSOR FOR THE
 GROUND-FAULT SIGNAL DEVICES SHALL BE
 LOCATED AT, OR AHEAD OF, THE MAIN SYSTEM
 DISCONNECTING MEANS FOR THE EMERGENCY
 SOURCE, AND THE MAXIMUM SETTING OF THE
 SIGNAL DEVICES SHALL BE FOR A
 GROUND-FAULT CURRENT OF 1200 AMPERES.
 INSTRUCTIONS ON THE COURSE OF ACTION TO
 BE TAKEN IN EVENT OF INDICATED GROUND
 FAULT SHALL BE LOCATED AT OR NEAR THE
 SENSOR LOCATION.
 ALTHOUGH 700.26 INDICATES THAT
 GROUND-FAULT PROTECTION OF EQUIPMENT IS
 NOT REQUIRED ON THE ALTERNATE SOURCE FOR
 EMERGENCY SYSTEMS, GROUND FAULTS CAN
 OCCUR ON SUCH SYSTEMS, AND THEY CAN
 RESULT IN EQUIPMENT BURNDOWN. BECAUSE OF
 THE EMERGENCY NATURE OF SUCH SYSTEMS,
 AUTOMATIC DISCONNECT IN THE EVENT OF A
 GROUND FAULT IS INAPPROPRIATE. DETECTION
 OF SUCH A FAULT, HOWEVER, IS DESIRABLE
 SO THAT THE CONDITION CAN BE CORRECTED.
 PLEASE PROVIDE ALL INFORMATION AS NEEDED
 FROM MANUFACTURE TO VERIFY, AS SOME
 MANUFACTURES ALREADY KNOW TO THIS OFFICE
 DO REQUIRE THE SWITCHING OF THE NEUTRAL
 IN ORDER FOR THE GFP SENSING TO WORK
 CORRECTLY.
  
 3)NOTE:PLEASE SEE PLANS E-2 REFERENCE
 TO SEE LAYOUT OF FIRE COMMAND ROOM ON
 E-19, HOWEVER THIS LAYOUT IS "BLANK".
 PLEASE SEE NFPA-72, 101 WITH ALL MIN
 EQUIPMENT REQUIRED IN SUCH ROOM. PLEASE
 INDICATE THESE ITEMS ON PLANS.
 FIRE ALARM CONTROL PANEL, GENERATOR
 ANNUCIATOR PANEL, SHUNTS ETC.
 PLEASE ALSO SEE NOTE FOR EM LTS.
  
 4)NOTE: PLEASE SEE THAT NO PLANS WERE
 SUBMIT TO SHOW POOL AREA LAYOUT ,
 LIGHTING, RECEPTS ETC.
 UNABLE TO VERIFY MIN REQUIRED BY CODE
 FOR THESE AREAS.
  
 5)NOTE: PLEASE PROVIDE REFERENCE TO THE
 2002 NEC ON PLANS.
 PLEASE ALSO REFERENCE 2002 NFPA-72, AND
 THE 2003 NFPA-101.
  
 6)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL CORRIDOR, STAIR
 TOWER AND EGRESS PATHS. PLEASE SEE 101
 7.8 WHICH REQUIRES A MIN OF 10FT CANDLES
 MIN FOR STAIR WELLS AND 1FT MIN UNDER EM
 CONDITIONS.
 PLEASE SEE 7.9.2.2 WHICH REQUIRES WIRING
 OF EM LTS TO BE SUCH IN THE EVENT OF THE
 SWITCHING OF A SWITCH, BREAKER ETC OR
 THE TRIPPING OF A SINGLE OCP DEVICE WILL
 IN NO WAY LEAVE ANY ONE AREA OF EGRESS
 IN TOTAL DARKNESS. IN ORDER TO
 ALLEAVIATE THIS , A MIN BATTTERY BACK UP
 FIXTURE OF SOME TYPEWILL BE REQUIRED
 TO POVIDE THE MIN 1FT CANDLE FOR MIN
 TIME.
  
  
 7)NOTE: PLEASE SEE ALL MAIN ELECTRICAL
 ROOMS, FIRE COMMAND ROOM, GEN RM, FIRE
 PUMP RM AND ELEVATOR EQUIPMENT ROOMS ETC
 SHALL A BATTERY BACK UP TYPE OF LIGHTING
 FIXTURE.
 700.16, LS 101 7-9, 90.4
  
 8)NOTE: PLEASE SEE 620.23 AND 620.24
 WHICH REQUIRES EQUIPMENT ROOMS/AREAS TO
 HAVE A DEDICATED BRANCH CIRCUIT FOR
 RECEPTS AND LIGHTING.PLEASE SEE A
 DEDICATE CIRCUIT WAS LOCATED FOR RECEPT,
 HOWEVER LIGHTING COULD NOT BE VERIFIED.
  
 9)NOTE: PLEASE SEE FIRE REVIEW FOR EXACT
 LOCATIONS OF ANY "KNOX BOX" LOCATION(S)
 WHICH MAY BE REQUIRED. ONE OR MORE
 LOCATIONS SHALL BE PLACED/NOTED ON
 PLANS.
  
 10)NOTE: PLEASE SHOW ALL ROOM/AREA
 DESIGNATIONS ON PLANS. PLEASE SEE AREAS
 IN UNITS. PLEASE SEE AREAS WHICH NOW
 INDICATE THE 15A, #14 CIRCUITS IN AREAS
 WHICH APPEAR TO BE DINING AREAS.
 PLEASE SEE 210.52B1,210.11C1
  
 11)NOTE: : PLEASE SEE 210.63 FOR
 REQUIMENTS OF GFI RECEPTS FOR ALL A/C
 EQUIPMENT. PLEASE SEE THESE COULD NOT BE
 LOCATED ON ROOF PLANS ETC.
  
 12)NOTE: PLEASE PROVIDE SPECIFIC NOTES
 ON SHEETS CONTAINING A LARGER SCALE OF
 ELECTRICAL ROMMS. THE NOTE FOR 110.26
 WAS FOUND ON RISER SHEET, HOWEVER PLEASE
 INCLUDE THIS ON ABOVE SHEETS.
  
 13)NOTE: PLEASE SEE SOME AREAS, WHICH
 ARE LABELED AS ELEVATORS RMS ARE SHOWN
 BLANK?
 E-7
  
 14)NOTE: PLEASE PROVIDE DETAIL FOR ALL
 FLOOR PENETRATIONS AND PENETRATIONS FOR
 BUC-DUCT INDICATION THE MIN 4" CURBING.
 368.6B2
  
 15)NOTE: PLEASE INDICATE THE EQUIPMENT
 GROUNDING METHOD OF BUS-DUCT. PLEASE
 PROVIDE CUT SHEET FROM MANUFACTURE.
 PLEASE SEE LOCAL AMENDMENTS WHICH REUIRE
 THE EQUIPMENT GROUNDING TO BE
 COPPER.250.62
  
 16)NOTE: PLEASE PROVIDE COLOR CODING OF
 ELECTRICAL WIRING PER 215.8 OFLOCAL
 AMENDMENTS. 120/208 BLK,RED, BLUE,
 WHITE.
 277/480V BROWN, PURPLE, YELLOW, GREY.
 SEE OTHERS IF ANY OTHER ELECTRICAL
 VOLTAGES ARE TO BE USED.
  
  
 17)NOTE: PLEASE SEE SOME CIRCUTING
 MISSING ON UNITS PLANS. THESE HAVE BEEN
 REDLINED FOR AREAS OF COMMENT.
  
 18)NOTE: PLEASE SEE SOME UNITS MISSING
 RECEPTS PER 210.52.
 PLEASE SEE REDLINED SET, ONLY A COUPLE.
  
 19)NOTE: PLEASE SEE C 2.2 WHICH MENTIONS
 TO SEE ENLARGE AREA TO SHOW DETAIL,
 HOWEVER THIS SEEMS TO BE BLANK ON PLANS.
  
 20)NOTE:PLEASE SEE THAT ALL RECEPTS
 SHOWN IN CLOSETS FOR LV TRNSFORMERS TO
 BE "PLUGGED IN" SHALL BE LOCATED ATLEAST
 12" MIN FROM SHELVING. THESE MAY BE
 LOCATED ABOVE DOOR WAYS.
 PLEASE SEE PLUG-IN TYPE TRANSFORMERS
 CREATE VERY HIGH TEMPS AND SOME IN THIS
 JURISTICTION HAVE HEATED TO THE POINT OF
 MELTING, AND CUSE OF FIRE IN CLOSETS AND
 CLOSE PROIMITY TO COMBUSTIBLES. PLEASE
 SEE THIS CREATES A LIFE-SAFETY SITUATION
 AND ANY UNITS CONTAININGOCP, THERMAL
 CUT-OUT DEVICES WILL BE REQUIRED TO BE
 LOCATED AS ABOVE. 110.26,240.24D
  
 21)NOTE: PLEASE SEE SOME UNITS IN WHICH
 THERE SEEMS TO BE TWO DIFFERENT HEIGHTS
 IN BEDRM CEILINGS. PLEASE SEE NFPA-72
 11.8.3.5 WHICH REQUIRES THESE SD'S TO BE
 LOCATED WITHIN 12" OF THE HIGHESRT POINT
 OF THE FLAT CEILING AREA.
 PLEASE SEE REDLINED PLANS FOR LOCATIONS.
  
 22)NOTE: PLEASE SEE SOME UNITS WHICH
 INDICATE A HIGHER LOAD OF 122.5A'S ON A
 125A BREAKER. PLEASE VERIFY AS THIS DOES
 NOT SEEM TO LEAVE ANY ALLOTMENT FOR
 FURTURE WIRING EXPANTION OF LOADS.
 THIS IS THE LOAD AFTER ALL PERMITTED
 DE-RATING BY NEC.
 PLEASE ALSO SEE ANY ARE VERYCLOSE TO
 THE 100A'S PROVIDED.
 90.8
  
 23)NOTE: PLEASE SEE AREAS OF PLANS WHICH
 CONTAIN "WHITE-OUT" AND HAND-DRAWN
 CHNAGES MADE. (RISER SHEET).
 PLEASE SEE FS 471.025 ETC WHICH DOES NOT
 PERMIT ANY HAND DRAWN CHANGES TO PLANS,
 UNLESS EACH INDIVIDUAL CHANGE IS SIGNED
 AND DATED BY THE SAID ENGINEER OF
 RECORD.
  
 24)NOTE:PLEASE PROVIDE COMPLETE NOTES
 WITH RESPECT TO THE LOCATIONS OF SMOKE
 DETECTORS. 11.8.3.5
 SMOKE ALARMS AND SMOKE DETECTORS
 INSTALLED WITHIN A 6.1-M (20-FT)
 HORIZONTAL PATH OF A COOKING APPLIANCE
 SHALL BE EQUIPPED WITH AN
 ALARM-SILENCING MEANS OR BE OF THE
 PHOTOELECTRIC TYPE.
 SMOKE ALARMS AND SMOKE DETECTORS SHALL
 NOT BE INSTALLED WITHIN A 914-MM
 (36-IN.) HORIZONTAL PATH FROM A DOOR TO
 A KITCHEN OR A BATHROOM CONTAINING A
 SHOWER OR TUB.
 SMOKE ALARMS AND SMOKE DETECTORS SHALL
 NOT BE INSTALLED WITHIN A 914-MM
 (36-IN.) HORIZONTAL PATH FROM THE SUPPLY
 REGISTERS OF A FORCED AIR HEATING OR
 COOLING SYSTEM AND SHALL BE INSTALLED
 OUTSIDE OF THE DIRECT AIRFLOW FROM THOSE
 REGISTERS AND 5' MIN FROM RETURN AIR
 GRILLES.
 SMOKE ALARMS AND SMOKE DETECTORS SHALL
 NOT BE INSTALLED WITHIN A 914-MM
 (36-IN.) HORIZONTAL PATH FROM THE TIP OF
 THE BLADE OF A CEILING-SUSPENDED
 (PADDLE) FAN.
  
 25)NOTE:PLEASE SHOW GROUNDING SYSTEM
 FOR ALL TRANSFORMER. PLEASE INCLUDE
 GROUNDING OF THESE TRANSFOMERS ON RISER
 DIAGRAM IN NOTES/LINE DIAGRAM.
 250.30, 250.50 ETC.
 PLEASE PROVIDE THIS LINE DIAGRAM ON
 RISER SHEET.
  
 26)NOTE:PLEASE SEE NO GFP INDICATED FOR
 HDP. 230.95. 240.13 ETC.
  
 27)NOTE: PLEASE SEE ANY PROPOSED
 LIGHTNING PROTECTION SYSTEM SHALL BE
 INSTALLED AND ACCEPTABLE PER NFPA-780.
 ALTHOUGH A LIGHTNING PROTECTION SYSTEM
 IS NOT SHOWN ON ANY PLANS, PLEASE BE
 SURE A NOTE IS PLACED ON "ROOF-TOP"
 SHEET WITH REFERENCE TO NFPA-780.
 AS NOTED IN MEETING , "LIGHTNING
 PREVENTION" SYSTEMS ARE NOT PERMITTED OR
 ACCEPTABLE IN THIS JURISTICTION.
  
 28)NOTE: PLEASE SEE THIS NOTE IS ALL
 ENCOMPASSING OF ELECTRICAL RISER,
 EQUIPMENT SCHEDULE, LOAD CALCULATIONS,
 PANEL SCHEDULES AND CALCUALTIONS ETC.
  
 ** PLEASE COMPLETE ALL OF THE ABOVE AND
 SUBMIT FOR REVIEW.
 PLEASE CORRELATE ALL PANEL SCHEDULS ,
 EQUIPMENT WITH RISER
 PLEASE COMPLETE RISER WITH INFORMATION
 FOR EQUIPMENT, FEEDERS ETC.
 PLEASE SEE MANY AREAS OF LOAD
 CALCULATIONS WHICH ONLY INDICATE
 XXXXXXX'S.
 PLEASE SEE 2002 NEC.
  
 ** PLEASE KNOW THERE MAY BE OTHER
 COMMENTS DUE TO THE INCOMPLETE PLANS AT
 THIS TIME.
  
 ** PLEASE SEE REDLINED PLANS FOR
 POSSIBLE LOCATIONS.
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE TO GO OVER COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
2005-12-09 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved