Date |
Text |
2005-12-13 00:00:00 | ********** UNSAT *************** |
| |
| SOUTH TOWER @CITY PLACE |
| 550 OKEECHOBEE BLVD. |
| |
| **** PLEASE KNOW, PLANS SUBMITTED ARE |
| NOT COMPLETE, THERFORE A COMPLETE REVIEW |
| FOR CODE COMPLIANCE CAN NOT BE DONE AT |
| THIS TIME. |
| PLEASE SEE THE BELOEW ITEMS KNOWN AT |
| THIS TIME. |
| |
| 1)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| SPECIFICATION SHEETS/ CUT SHEETS FOR |
| FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER, |
| GENERATOR, AUTOMATIC TRANSFER SWITCH |
| (ATS) AND ANY SUB BASE FUEL TANKS OR |
| FUEL TANKS FOR DIESEL FIRE PUMP. |
| PLEASE SURE ALL INFORMATION SUBMITTED |
| MUST SHOW LISTINGS FROM A NATIONALLY |
| RECOGNIZED TESTING LAB. (NRTL). |
| PLEASE BE SURE ALL FIRE PUMP CONTROLLERS |
| ETC COMPLY WITH NFPA-20 AND OTHER |
| APPLICABLE CODES. |
| |
| 2)NOTE: PLEASE SEE PLANS INDICATE 600KW, |
| YET RISER DIAGRAM SHOWS 400KW GEN. |
| PLEASE ALSO VERIFY IF THE ATS WILLL BE A |
| 4-POLE AND GEN TO BE SEPARTAELY DERIVED. |
| |
| PLEASE SEE 700.6DWHICH IN ORDER TO |
| INDICATE A GROUND FAULT IN SOLIDLY |
| GROUNDED WYE EMERGENCY SYSTEMS OF MORE |
| THAN 150 VOLTS TO GROUND AND |
| CIRCUIT-PROTECTIVE DEVICES RATED 1000 |
| AMPERES OR MORE. THE SENSOR FOR THE |
| GROUND-FAULT SIGNAL DEVICES SHALL BE |
| LOCATED AT, OR AHEAD OF, THE MAIN SYSTEM |
| DISCONNECTING MEANS FOR THE EMERGENCY |
| SOURCE, AND THE MAXIMUM SETTING OF THE |
| SIGNAL DEVICES SHALL BE FOR A |
| GROUND-FAULT CURRENT OF 1200 AMPERES. |
| INSTRUCTIONS ON THE COURSE OF ACTION TO |
| BE TAKEN IN EVENT OF INDICATED GROUND |
| FAULT SHALL BE LOCATED AT OR NEAR THE |
| SENSOR LOCATION. |
| ALTHOUGH 700.26 INDICATES THAT |
| GROUND-FAULT PROTECTION OF EQUIPMENT IS |
| NOT REQUIRED ON THE ALTERNATE SOURCE FOR |
| EMERGENCY SYSTEMS, GROUND FAULTS CAN |
| OCCUR ON SUCH SYSTEMS, AND THEY CAN |
| RESULT IN EQUIPMENT BURNDOWN. BECAUSE OF |
| THE EMERGENCY NATURE OF SUCH SYSTEMS, |
| AUTOMATIC DISCONNECT IN THE EVENT OF A |
| GROUND FAULT IS INAPPROPRIATE. DETECTION |
| OF SUCH A FAULT, HOWEVER, IS DESIRABLE |
| SO THAT THE CONDITION CAN BE CORRECTED. |
| PLEASE PROVIDE ALL INFORMATION AS NEEDED |
| FROM MANUFACTURE TO VERIFY, AS SOME |
| MANUFACTURES ALREADY KNOW TO THIS OFFICE |
| DO REQUIRE THE SWITCHING OF THE NEUTRAL |
| IN ORDER FOR THE GFP SENSING TO WORK |
| CORRECTLY. |
| |
| 3)NOTE:PLEASE SEE PLANS E-2 REFERENCE |
| TO SEE LAYOUT OF FIRE COMMAND ROOM ON |
| E-19, HOWEVER THIS LAYOUT IS "BLANK". |
| PLEASE SEE NFPA-72, 101 WITH ALL MIN |
| EQUIPMENT REQUIRED IN SUCH ROOM. PLEASE |
| INDICATE THESE ITEMS ON PLANS. |
| FIRE ALARM CONTROL PANEL, GENERATOR |
| ANNUCIATOR PANEL, SHUNTS ETC. |
| PLEASE ALSO SEE NOTE FOR EM LTS. |
| |
| 4)NOTE: PLEASE SEE THAT NO PLANS WERE |
| SUBMIT TO SHOW POOL AREA LAYOUT , |
| LIGHTING, RECEPTS ETC. |
| UNABLE TO VERIFY MIN REQUIRED BY CODE |
| FOR THESE AREAS. |
| |
| 5)NOTE: PLEASE PROVIDE REFERENCE TO THE |
| 2002 NEC ON PLANS. |
| PLEASE ALSO REFERENCE 2002 NFPA-72, AND |
| THE 2003 NFPA-101. |
| |
| 6)NOTE: PLEASE PROVIDE COMPLETE |
| PHOTOMETRICS FOR ALL CORRIDOR, STAIR |
| TOWER AND EGRESS PATHS. PLEASE SEE 101 |
| 7.8 WHICH REQUIRES A MIN OF 10FT CANDLES |
| MIN FOR STAIR WELLS AND 1FT MIN UNDER EM |
| CONDITIONS. |
| PLEASE SEE 7.9.2.2 WHICH REQUIRES WIRING |
| OF EM LTS TO BE SUCH IN THE EVENT OF THE |
| SWITCHING OF A SWITCH, BREAKER ETC OR |
| THE TRIPPING OF A SINGLE OCP DEVICE WILL |
| IN NO WAY LEAVE ANY ONE AREA OF EGRESS |
| IN TOTAL DARKNESS. IN ORDER TO |
| ALLEAVIATE THIS , A MIN BATTTERY BACK UP |
| FIXTURE OF SOME TYPEWILL BE REQUIRED |
| TO POVIDE THE MIN 1FT CANDLE FOR MIN |
| TIME. |
| |
| |
| 7)NOTE: PLEASE SEE ALL MAIN ELECTRICAL |
| ROOMS, FIRE COMMAND ROOM, GEN RM, FIRE |
| PUMP RM AND ELEVATOR EQUIPMENT ROOMS ETC |
| SHALL A BATTERY BACK UP TYPE OF LIGHTING |
| FIXTURE. |
| 700.16, LS 101 7-9, 90.4 |
| |
| 8)NOTE: PLEASE SEE 620.23 AND 620.24 |
| WHICH REQUIRES EQUIPMENT ROOMS/AREAS TO |
| HAVE A DEDICATED BRANCH CIRCUIT FOR |
| RECEPTS AND LIGHTING.PLEASE SEE A |
| DEDICATE CIRCUIT WAS LOCATED FOR RECEPT, |
| HOWEVER LIGHTING COULD NOT BE VERIFIED. |
| |
| 9)NOTE: PLEASE SEE FIRE REVIEW FOR EXACT |
| LOCATIONS OF ANY "KNOX BOX" LOCATION(S) |
| WHICH MAY BE REQUIRED. ONE OR MORE |
| LOCATIONS SHALL BE PLACED/NOTED ON |
| PLANS. |
| |
| 10)NOTE: PLEASE SHOW ALL ROOM/AREA |
| DESIGNATIONS ON PLANS. PLEASE SEE AREAS |
| IN UNITS. PLEASE SEE AREAS WHICH NOW |
| INDICATE THE 15A, #14 CIRCUITS IN AREAS |
| WHICH APPEAR TO BE DINING AREAS. |
| PLEASE SEE 210.52B1,210.11C1 |
| |
| 11)NOTE: : PLEASE SEE 210.63 FOR |
| REQUIMENTS OF GFI RECEPTS FOR ALL A/C |
| EQUIPMENT. PLEASE SEE THESE COULD NOT BE |
| LOCATED ON ROOF PLANS ETC. |
| |
| 12)NOTE: PLEASE PROVIDE SPECIFIC NOTES |
| ON SHEETS CONTAINING A LARGER SCALE OF |
| ELECTRICAL ROMMS. THE NOTE FOR 110.26 |
| WAS FOUND ON RISER SHEET, HOWEVER PLEASE |
| INCLUDE THIS ON ABOVE SHEETS. |
| |
| 13)NOTE: PLEASE SEE SOME AREAS, WHICH |
| ARE LABELED AS ELEVATORS RMS ARE SHOWN |
| BLANK? |
| E-7 |
| |
| 14)NOTE: PLEASE PROVIDE DETAIL FOR ALL |
| FLOOR PENETRATIONS AND PENETRATIONS FOR |
| BUC-DUCT INDICATION THE MIN 4" CURBING. |
| 368.6B2 |
| |
| 15)NOTE: PLEASE INDICATE THE EQUIPMENT |
| GROUNDING METHOD OF BUS-DUCT. PLEASE |
| PROVIDE CUT SHEET FROM MANUFACTURE. |
| PLEASE SEE LOCAL AMENDMENTS WHICH REUIRE |
| THE EQUIPMENT GROUNDING TO BE |
| COPPER.250.62 |
| |
| 16)NOTE: PLEASE PROVIDE COLOR CODING OF |
| ELECTRICAL WIRING PER 215.8 OFLOCAL |
| AMENDMENTS. 120/208 BLK,RED, BLUE, |
| WHITE. |
| 277/480V BROWN, PURPLE, YELLOW, GREY. |
| SEE OTHERS IF ANY OTHER ELECTRICAL |
| VOLTAGES ARE TO BE USED. |
| |
| |
| 17)NOTE: PLEASE SEE SOME CIRCUTING |
| MISSING ON UNITS PLANS. THESE HAVE BEEN |
| REDLINED FOR AREAS OF COMMENT. |
| |
| 18)NOTE: PLEASE SEE SOME UNITS MISSING |
| RECEPTS PER 210.52. |
| PLEASE SEE REDLINED SET, ONLY A COUPLE. |
| |
| 19)NOTE: PLEASE SEE C 2.2 WHICH MENTIONS |
| TO SEE ENLARGE AREA TO SHOW DETAIL, |
| HOWEVER THIS SEEMS TO BE BLANK ON PLANS. |
| |
| 20)NOTE:PLEASE SEE THAT ALL RECEPTS |
| SHOWN IN CLOSETS FOR LV TRNSFORMERS TO |
| BE "PLUGGED IN" SHALL BE LOCATED ATLEAST |
| 12" MIN FROM SHELVING. THESE MAY BE |
| LOCATED ABOVE DOOR WAYS. |
| PLEASE SEE PLUG-IN TYPE TRANSFORMERS |
| CREATE VERY HIGH TEMPS AND SOME IN THIS |
| JURISTICTION HAVE HEATED TO THE POINT OF |
| MELTING, AND CUSE OF FIRE IN CLOSETS AND |
| CLOSE PROIMITY TO COMBUSTIBLES. PLEASE |
| SEE THIS CREATES A LIFE-SAFETY SITUATION |
| AND ANY UNITS CONTAININGOCP, THERMAL |
| CUT-OUT DEVICES WILL BE REQUIRED TO BE |
| LOCATED AS ABOVE. 110.26,240.24D |
| |
| 21)NOTE: PLEASE SEE SOME UNITS IN WHICH |
| THERE SEEMS TO BE TWO DIFFERENT HEIGHTS |
| IN BEDRM CEILINGS. PLEASE SEE NFPA-72 |
| 11.8.3.5 WHICH REQUIRES THESE SD'S TO BE |
| LOCATED WITHIN 12" OF THE HIGHESRT POINT |
| OF THE FLAT CEILING AREA. |
| PLEASE SEE REDLINED PLANS FOR LOCATIONS. |
| |
| 22)NOTE: PLEASE SEE SOME UNITS WHICH |
| INDICATE A HIGHER LOAD OF 122.5A'S ON A |
| 125A BREAKER. PLEASE VERIFY AS THIS DOES |
| NOT SEEM TO LEAVE ANY ALLOTMENT FOR |
| FURTURE WIRING EXPANTION OF LOADS. |
| THIS IS THE LOAD AFTER ALL PERMITTED |
| DE-RATING BY NEC. |
| PLEASE ALSO SEE ANY ARE VERYCLOSE TO |
| THE 100A'S PROVIDED. |
| 90.8 |
| |
| 23)NOTE: PLEASE SEE AREAS OF PLANS WHICH |
| CONTAIN "WHITE-OUT" AND HAND-DRAWN |
| CHNAGES MADE. (RISER SHEET). |
| PLEASE SEE FS 471.025 ETC WHICH DOES NOT |
| PERMIT ANY HAND DRAWN CHANGES TO PLANS, |
| UNLESS EACH INDIVIDUAL CHANGE IS SIGNED |
| AND DATED BY THE SAID ENGINEER OF |
| RECORD. |
| |
| 24)NOTE:PLEASE PROVIDE COMPLETE NOTES |
| WITH RESPECT TO THE LOCATIONS OF SMOKE |
| DETECTORS. 11.8.3.5 |
| SMOKE ALARMS AND SMOKE DETECTORS |
| INSTALLED WITHIN A 6.1-M (20-FT) |
| HORIZONTAL PATH OF A COOKING APPLIANCE |
| SHALL BE EQUIPPED WITH AN |
| ALARM-SILENCING MEANS OR BE OF THE |
| PHOTOELECTRIC TYPE. |
| SMOKE ALARMS AND SMOKE DETECTORS SHALL |
| NOT BE INSTALLED WITHIN A 914-MM |
| (36-IN.) HORIZONTAL PATH FROM A DOOR TO |
| A KITCHEN OR A BATHROOM CONTAINING A |
| SHOWER OR TUB. |
| SMOKE ALARMS AND SMOKE DETECTORS SHALL |
| NOT BE INSTALLED WITHIN A 914-MM |
| (36-IN.) HORIZONTAL PATH FROM THE SUPPLY |
| REGISTERS OF A FORCED AIR HEATING OR |
| COOLING SYSTEM AND SHALL BE INSTALLED |
| OUTSIDE OF THE DIRECT AIRFLOW FROM THOSE |
| REGISTERS AND 5' MIN FROM RETURN AIR |
| GRILLES. |
| SMOKE ALARMS AND SMOKE DETECTORS SHALL |
| NOT BE INSTALLED WITHIN A 914-MM |
| (36-IN.) HORIZONTAL PATH FROM THE TIP OF |
| THE BLADE OF A CEILING-SUSPENDED |
| (PADDLE) FAN. |
| |
| 25)NOTE:PLEASE SHOW GROUNDING SYSTEM |
| FOR ALL TRANSFORMER. PLEASE INCLUDE |
| GROUNDING OF THESE TRANSFOMERS ON RISER |
| DIAGRAM IN NOTES/LINE DIAGRAM. |
| 250.30, 250.50 ETC. |
| PLEASE PROVIDE THIS LINE DIAGRAM ON |
| RISER SHEET. |
| |
| 26)NOTE:PLEASE SEE NO GFP INDICATED FOR |
| HDP. 230.95. 240.13 ETC. |
| |
| 27)NOTE: PLEASE SEE ANY PROPOSED |
| LIGHTNING PROTECTION SYSTEM SHALL BE |
| INSTALLED AND ACCEPTABLE PER NFPA-780. |
| ALTHOUGH A LIGHTNING PROTECTION SYSTEM |
| IS NOT SHOWN ON ANY PLANS, PLEASE BE |
| SURE A NOTE IS PLACED ON "ROOF-TOP" |
| SHEET WITH REFERENCE TO NFPA-780. |
| AS NOTED IN MEETING , "LIGHTNING |
| PREVENTION" SYSTEMS ARE NOT PERMITTED OR |
| ACCEPTABLE IN THIS JURISTICTION. |
| |
| 28)NOTE: PLEASE SEE THIS NOTE IS ALL |
| ENCOMPASSING OF ELECTRICAL RISER, |
| EQUIPMENT SCHEDULE, LOAD CALCULATIONS, |
| PANEL SCHEDULES AND CALCUALTIONS ETC. |
| |
| ** PLEASE COMPLETE ALL OF THE ABOVE AND |
| SUBMIT FOR REVIEW. |
| PLEASE CORRELATE ALL PANEL SCHEDULS , |
| EQUIPMENT WITH RISER |
| PLEASE COMPLETE RISER WITH INFORMATION |
| FOR EQUIPMENT, FEEDERS ETC. |
| PLEASE SEE MANY AREAS OF LOAD |
| CALCULATIONS WHICH ONLY INDICATE |
| XXXXXXX'S. |
| PLEASE SEE 2002 NEC. |
| |
| ** PLEASE KNOW THERE MAY BE OTHER |
| COMMENTS DUE TO THE INCOMPLETE PLANS AT |
| THIS TIME. |
| |
| ** PLEASE SEE REDLINED PLANS FOR |
| POSSIBLE LOCATIONS. |
| |
| PLEASE SUBMITTHE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE TO GO OVER COMMENTS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
2005-12-09 00:00:00 | ONE ROLL IN ELECTRIC FOR REVIEW. |