Plan Review Notes
Plan Review Notes For Permit 05091425
Permit Number 05091425
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) INFORMATIVE:
 A SEPARATE PERMIT APPLICATION WILL BE
 REQUIRED FOR THE SWIMMING POOL AND SPA.
 ALSO, A SEPARATE PERMIT APPLICATION WILL
 BE REQUIRED FOR THE CANVAS CANOPIES AND
 FRAMES IF FULL MATERIAL AND DESIGN
 DETAILS ARE NOT PROVIDED AS PART OF THE
 BUILDING PERMIT PLAN SET.
  
 4) FBC 1606.1.1WIND TUNNEL TEST
 REPORT.SUBMIT THREE COPIES OF THE RWDI
 REPORT 05-1427, REFERENCED ON SHEET
 S-0.0 UNDER THE GENERAL NOTES
 SUB-HEADING 'WIND LOADS'
  
 5) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 6) SUBMIT PRODUCT APPROVALS FOR THE
 FIXED WINDOWS, SINGLE HUNG WINDOWS,
 STOREFRONT, SLIDING GLASS DOORS,
 EXTERIOR DOORS AND BUILT-UP ROOFING,
 CONCRETE TILE AND METAL PANEL ROOF
 COVERINGS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE WWW.
 FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
 (IF YOU FIND THAT THE QUOTED WEB PAGE IS
 NO LONGER AVAILABLE, PLEASE INFORM THE
 PLAN REVIEWER)
  
 7) FBC 503.2.6TYPE II CONSTRUCTION,
 SPECIAL UNLIMITED HEIGHT.THIS SECTION
 ALLOWS THE BUILDING HEIGHT TO EXCEED THE
 80' LIMIT STATED IN TABLE 600 FOR TYPE
 II CONSTRUCTION, BUT IT REQUIRES THE
 ROOF AND ITS SUPPORTING STRUCTURE TO
 HAVE A FIRE RESISTANCE OF NOT LESS THAN
 1-1/2 HOURS.THE TABLE ON SHEET A-0.1,
 UNDER GENERAL NOTE 7, STATES THAT THE
 FIRE RESISTANCE OF THE ROOF IS TO BE A
 MINIMUM OF 1 HOUR.AMEND THIS TO 1-1/2
 HOURS.
  
 8) FBC 411.4.1FOR AN ENCLOSED PARKING
 GARAGE (GROUP S) OF TYPE II
 CONSTRUCTION, TABLE 500 LIMITS THE
 MAXIMUM NUMBER OF STORIES TO 6.SHEET
 A-0.1, GENERAL NOTE #5, STATES THE THE
 RESIDENTIAL AND PARKING GARAGE
 OCCUPANCIES ARE CONSIDERED MIXED USE.
 ALTHOUGH FBC 303.2 STATES THAT A MIXED
 OCCUPANCY BUILDING IS GOVERNED BY THE
 HEIGHT AND AREA LIMITATIONS OF IT'S
 PRINCIPAL USE (IN THIS CASE
 RESIDENTIAL), IT GOES ON TO STATE THAT
 ACCESSORY OCCUPANCIES SHALL NOT BE
 LOCATED AT A HEIGHT GREATER THAN THAT
 PERMITTED FOR SUCH AN OCCUPANCY GROUP IN
 THE THE TYPE OF CONSTRUCTION BEING USED.
 IN A TYPE II RESIDENTIAL BUILDING, THE
 PARKING GARAGE OCCUPANCY SHALL NOT
 OCCUPY ANY SPACE ABOVE THE SIXTH STORY.
 AMEND THE CONSTRUCTION TYPE.
  
 9) FBC 11-4.1.2(5)(B)VAN ACCESSIBLE
 PARKING. THE PARKING DATA ON SHEET A-0.1
 STATES THAT 17 ACCESSIBLE SPACES ARE
 BEING PROVIDED.1 IN EVERY 8 ACCESSIBLE
 SPACES SHALL BE VAN ACCESSIBLE.A
 MINIMUM VERTICAL CLEARANCE OF 98 INCHES
 IS REQUIRED AT SUCH SPACES, AND ALONG AT
 LEAST ONE VEHICLE ACCESS ROUTE TO THE
 SPACE FROM THE SITE ENTRANCE.PLEASE
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.ALSO, THE NOTE ABOUT
 PARKING GARAGE BARRIER HEIGHT, ON SHEET
 A-2.7.1 IS NOT CLEAR. AMEND THE NOTE TO
 DEMONSTRATE COMPLIANCE WITH THE ABOVE
 REQUIREMENT.
  
 10) FBC 412.5SMOKE CONTROL.THE PLANS
 SHALL CLEARLY DESCRIBE THE PROVISION OF
 ONE OF THE FORMS OF SMOKE CONTROL LISTED
 IN THE CODE.ANNOTATE THE PLANS.
  
  
 11) FBC* 104.2.1FIRE SEPARATION PLANS.
 PLEASE ADD CLEAR ANNOTATION TO THE PLANS
 (OR USE LINE TYPES AND A LEGEND) TO
 DEMONSTRATE COMPLIANCE WITH CHAPTER 7,
 FIRE RESISTANT MATERIALS AND
 CONSTRUCTION.THE REFERENCE TO THESE
 REQUIREMENTS ON SHEET A-0.1, GENERAL
 NOTE #5 AND SHEET A-1.1 NOTE #4 IS
 ACKNOWLEDGED, BUT CLEAR DIAGRAMMATIC
 REPRESENTATION IS REQUIRED.FOR
 EXAMPLE, SHEET A-2.1.5 STATES "SHADING
 INDICATES 4 HR FIRE RATED MASONRY WALL &
 COLUMNS" AT THE FPL TRANSFORMER VAULT,
 BUT NO SHADING IS SHOWN.THE WALLS ARE
 SHOWN THE SAME AS THE 2 HR RATED WALLS.
  
 12) FBC* 104.2.1LIFE SAFETY PLANS.SO
 THAT COMPLIANCE WITH CHAPTER 10, MEANS
 OF EGRESS CAN BE DETERMINED, PLEASE
 SUBMIT 1/8"=1'-0" SCALE PLANS, FOR EACH
 STORY, SHOWING OCCUPANCY COUNTS AND
 DISTANCE TO EXIT FOR THE RESIDENTIAL,
 GARAGE, POOL DECK AND OTHER COMMON
 OCCUPANCY AREAS.
  
 13) FBC* 104.2.1ROOM DESIGNATIONS,
 SHEET A-1.5.THE OCCUPANCY FOR THE
 ROOMS TO THE NORTH AND WEST OF THE POOL
 HAVE NOT BEEN STATED.AMEND THE PLAN.
 IT IS NOTED THAT THESE ROOMS ARE
 REFERENCED ON SHEETS A-2.4.2 AND A-2.4.5
 AS FITNESS CENTER AND CLUBROOM UNDER
 SEPARATE PERMIT.FOR CLARITY, A NOTE
 SHOULD BE ADDED TO SHEET A-1.5 ALSO.
  
 14) FBC 1001.1POOL DECK EGRESS.THE
 EXIT DOOR LEADING TO STAIR #4 IS NOTED,
 BUT THE EXIT DOOR LEADING TO STAIR #3 IS
 SHOWN AS A SINGLE DOOR.THE DOORS WITH
 SCHEDULE REFERENCE NUMBER 50, LEAD FROM
 THE POOL DECK INTO THE 'FITNESS CENTER
 AND CLUBROOM' WHICH DO NOT APPEAR TO
 COMMUNICATE WITH THE EXIT ACCESS
 CORRIDOR.PLEASE CLARIFY THE PROVISION
 OF EXITTING FROM THE POOL DECK AREA.
 SEE THE TWO RELATED COMMENTS ABOVE.
  
 15) FBC 1003.3.5WIDTH OF EXIT, SHEET
 A-2.1.1.THE EXIT PASSEGEWAY LEADING TO
 THE EXIT DISCHARGE FROM STAIR NO.1 IS
 SHOWN AS REDUCING IN WIDTH FROM 5'-0" TO
 4'-0".AT NO POINT ALONFG AN EXIT PATH
 MAY THE EXIT WIDTH BE DECREASED.
  
 16) FBC 411.2.3VEHICLE IMPACT
 WALLS/GUARDRAILS, SHEETS A-2.7.1 TO
 A-2.7.4.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENT FOR IMPACT GUARDING AT THE
 ENDS OF THE 2ND FLOOR PARKING SPACES
 THAT ARE ADJACENT TO THE VOID OVER THE
 COMMERCIAL TENANT SPACE, AND THE PARKING
 SPACES, ON ALL FLOORS, THAT ARE ADJACENT
 TO THE RAMP, WHERE THE DIFFERENCE IN
 ADJACENT FLOOR ELEVATION IS GREATER THAN
 1'-0".THE SAME APPLIES TO THE 2ND FOOR
 TO 8TH FLOOR PARKING SPACES ADJACENT TO
 THE EAST EXTERIOR WALL.
  
 17) FBC 1608.2.1HANDRAIL STRENGTH,
 SHEET A-3.1 STAIR RAILING NOTE #2 IS
 ACKNOWLEDGED.PLEASE ADD A NOTE TO THE
 PLANS TO STATE THAT THE HANDRAILS SHALL
 BE DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB AND A LINE
 LOAD OF 50 PLF.THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY BUT SHALL BE
 APPLIED INDIVIDUALLY AT ANY POINT, AND
 IN ANY DIRECTION, TO PRODUCE MAXIMUM
 STRESS IN EACH OF THE COMPONENTS OR
 SUPPORTS.SEE THE COMMENT BELOW, ALSO,
 WITH RESPECT TO THE GUARDING
 REQUIREMENT FOR THE STAIRS.
  
 18) FBC 1608.2.2GUARDRAIL STRENGTH,
 SHEET A-3.5.ANNOTATE THE PLAN TO STATE
 THAT THE BALCONY RAILINGS (GUARDRAILS)
 SHALL BE DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED IN
 ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL, A CONCENTRATED HORIZONTAL
 LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA
 AT ANY POINT, AND A LINE LOAD OF 50 PLF
 APPLIED HORIZONTALLY AT THE REQUIRED
 GUARDRAIL HEIGHT WITH A SIMULTANEOUS
 LINE LOAD OF 100 PLF APPLIED VERTICALLY
 DOWNWARD ON THE TOP OF THE GUARDRAIL.
 THESE LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT
 SHALL BE APPLIED INDIVIDUALLY TO PRODUCE
 MAXIMUM STRESS IN EACH OF THE COMPONENTS
 OR SUPPORTS.
  
 19) FBC 1015.2GUARDRAIL HEIGHT, SHEET
 A-3.5, SECTIONS 2 AND 3.CHAMFER/SLOPE
 THE CONCRETE CAP PROFILE INWARD SO THAT
 IT DOES NOT PROVIDE A 'STEP' WHICH WOULD
 REDUCE THE EFFECTIVE HEIGHT OF THE
 GUARDRAIL.
  
 20) FBC* 104.2.1DYPLAST MOLDINGS,
 SHEET A-6.9.PLEASE PROVIDE
 MANUFACTURER'S SPECIFICATION FOR THE
 FLAME SPREAD AND COMBUSTIBILITY OF THE
 DYPLAST MOLDINGS.
  
 21) FBC 1606.1SOFFITS AND CEILINGS,
 SHEETS A-7.15 AND A-7.16.THE
 BREEZEWAY, ARCADE AND COVERED ENTRY
 DRIVE CEILINGS SHALL BE DESIGNED TO
 RESIST THE WIND PRESSURES FOR COMPONENTS
 AND CLADDING.
  
 22) FAIR HOUSING ACT, SHEET A-0.1.ALL
 OF THE DWELLING UNITS ARE 'COVERED
 UNITS'. IT IS NOTED THAT THERE ARE NO
 TYPICAL PLANS FOR THE UNIT TYPES TO SHOW
 HOW THEY WILL MEET THE REQUIREMENTS OF
 THE FAIR HOUSING ACT.SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 23) FBC 2103MASONRY WALL DETAILS,
 SHEET S0.03.THE VERTICAL REINFORCEMENT
 COLUMN OF THE TABLE ON THE 'TYPICAL
 EXTERIOR REINFORCED MASONRY WALL
 DETAILS' IS INCOMPLETE.
  
 24) FBC* 104.2.1IT IS NOTED THAT THE
 SUBMITTED PLANS ARE NOT COMPLETE.
 ADDITIONAL COMMENTS MAY ARISE WHEN THE
 REQUIRED PLANS ARE SUBMITTED.
  
 25) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]