2006-06-26 00:00:00 | PROVISO:2001 FBC/BUILDING 10/4 UNIT |
| PLEASE REVISE PLANS TO REFLECT THE |
| IMPLEMENTATION OF THE PROVISO'S. |
| |
| COMMENT #6:SPECIFIC DRYER TO BE |
| INSTALLED WHICH WILL ELIMINATE THE NEED |
| OF THE BOOSTER FAN.PLEASE NOTE, |
| SPECIFIC DRYER IS TO BE INSTALLED FOR |
| FINAL INSPECTION 2001 FMC 504.6. |
| |
| COMMENT #7:PLAN SHEET M0.1 THE OUTSIDE |
| AIR CALCULATIONS ARE BASED ON |
| "INFILTRATION RATES".THE INFILTRATION |
| RATES ARE "MAXIMUM RATES" ALLOWED BY |
| CODE AND MAY NOT ACTUALLY EXIST.THE |
| "ACTUAL" RATE IS NOT KNOWN UNLESS |
| TESTED.OUTSIDE AIR CALCULATIONS ARE TO |
| BE PER 2001 FMC 402.2, 402.2.1 OR TABLE |
| 403.3.PLEASE PROVIDE CALCULATIONS. |
| PLEASE NOTE, PLAN SHEET M2 INDICATES 6" |
| OUTSIDE AIR DUCT, PLEASE REMOVE FROM THE |
| PLANS IF THIS DUCT IS NOT GOING TO BE |
| INSTALLED. |
| |
| COMMENT #8:AHU CLOSET IS USED AS A |
| RETURN AIR PLENUM.PLAN SHEET M0.1 AHU |
| DETAIL 15 ANNOTATES "NO COMBUSTIBLES |
| ALLOWED IN THE RETURN AIR PLENUM". |
| HOWEVER, PLAN SHEETS A-4.0.2 THROUGH |
| A-4.5.3, THE DOOR SCHEDULE INDICATES THE |
| AHU CLOSET DOOR WILL BE A WOOD LOUVERED |
| DOOR.PLEASE NOTE, THE DOOR AND FRAME |
| ARE REQUIRED TO MEET THE 25 FLAME/50 |
| SMOKE INDEX WHEN TESTED UNDER ASTM 84. |
| PLEASE VERIFY THE DOOR & FRAME MEET THIS |
| REQUIREMENT PER 2001 FMC 602.2.1. |
| |