Plan Review Notes For Permit 05091410 |
Permit Number |
05091410 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-28 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1. SHTS P2.1.1, P-2.2.4, P-3.1.1, P-3.2 | | AND P-3.2.4 WATER HAMMER ARRESTORS ARE | | REQUIRED AT THE WASH MACHINES OF ALL | | UNITS. PER SECTION 604.9. - ALL WATER | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | THE FIXTURES IN AN "EFFECTIVE RANGE", | | NOT IN THE CEILING AS SHOWN IN SOME | | CASES. PDI-WH 201 AND MANUF INSTALLATION | | INSTRUCTIONS. | | 2. IF INDIVIDUAL METERS NO BACKFLOW | | DEVISE IS REQUIRED, BUT IF SINGLE METER | | AN RPZV BACKFLOW WILL BE REQUIRED ON THE | | WATER SERVICE. PLEASE CLARIFY. SECTION | | 608.13.2. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|